Plan Review Notes
Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-21 09:20:48DENIED;
 FROM OLD PLAN REVIEW;
 1. OK
 2. NO. MINUMUM PLUMBING FIXTURES TABLE 403.1 (A-2) THE
 TOP TABLE SHOULD BE USED IN THIS SECTION, THIS IS A
 NIGHTCLUB/BAR. NO KITCHEN TO PREPARE FOOD. 4-TOILETS
 ARE REQUIRED IN EACH BATHROOM, 1/40.
 3. YES
 4. NO NOTE ABOUT DRY VENT TO BE WASHED IS NOT THE
 ANSURE VENTS ARE STILL SHOWN IN AN AREA WHERE NO
 FIXTURE WILL WASH THEM.
  
 5. NO VENTING OF THE SANITARY SYSTEM IS STILL NOT
 CORRECT. I.E. NO VENTSHOWN ON SANITARY RISER DIAGRAM
 BACK BAR. VENTS IN BATHROOMS SHOULD
 COME FROM THE FIXTURES, NOT OF THE BRANCH DRAINS.
 (EXSTEND URINAL PIPE INTO A VENT.
 6. YES
 NEW COMMENTS
 1. RISER DIAGRAMS ARE VERY HARD TO FOLLOW. FBC BUILDING
 CHAPTER 1 WPB ADMINISTRATION SECTION 106.1.1. PLEASE
 DELETE THE OUTLINES OF THE EQUIPMENT, CEILING AND
 FLOOR. INDIRECT WASTE LINES LOOK LIKE THERE TIED INTO
 THE SANITARY SYSTEM, I.E. DISH WASHERS, SEE FBC
 PLUMBING SECTION 802.2.
 2. DRINKING FOUNTAIN IS NOT PERMITED TO BE IN A
 BATHROOM. PLUMBING SECTION 410.2. ALSO DRINKING
 FOUNTAIN IS REQUIRED TO MEAT THE ACCESSIBILITY CODE
 SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  