| Plan Review Notes For Permit 07090045 |
| Permit Number |
07090045 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-12-21 09:20:48 | DENIED; | | | FROM OLD PLAN REVIEW; | | | 1. OK | | | 2. NO. MINUMUM PLUMBING FIXTURES TABLE 403.1 (A-2) THE | | | TOP TABLE SHOULD BE USED IN THIS SECTION, THIS IS A | | | NIGHTCLUB/BAR. NO KITCHEN TO PREPARE FOOD. 4-TOILETS | | | ARE REQUIRED IN EACH BATHROOM, 1/40. | | | 3. YES | | | 4. NO NOTE ABOUT DRY VENT TO BE WASHED IS NOT THE | | | ANSURE VENTS ARE STILL SHOWN IN AN AREA WHERE NO | | | FIXTURE WILL WASH THEM. | | | | | | 5. NO VENTING OF THE SANITARY SYSTEM IS STILL NOT | | | CORRECT. I.E. NO VENTSHOWN ON SANITARY RISER DIAGRAM | | | BACK BAR. VENTS IN BATHROOMS SHOULD | | | COME FROM THE FIXTURES, NOT OF THE BRANCH DRAINS. | | | (EXSTEND URINAL PIPE INTO A VENT. | | | 6. YES | | | NEW COMMENTS | | | 1. RISER DIAGRAMS ARE VERY HARD TO FOLLOW. FBC BUILDING | | | CHAPTER 1 WPB ADMINISTRATION SECTION 106.1.1. PLEASE | | | DELETE THE OUTLINES OF THE EQUIPMENT, CEILING AND | | | FLOOR. INDIRECT WASTE LINES LOOK LIKE THERE TIED INTO | | | THE SANITARY SYSTEM, I.E. DISH WASHERS, SEE FBC | | | PLUMBING SECTION 802.2. | | | 2. DRINKING FOUNTAIN IS NOT PERMITED TO BE IN A | | | BATHROOM. PLUMBING SECTION 410.2. ALSO DRINKING | | | FOUNTAIN IS REQUIRED TO MEAT THE ACCESSIBILITY CODE | | | SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON | | | PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|