| 2007-12-06 15:31:26 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS BASED ON |
| | CHANGES MADE AND NEW ITEMS NOT ON PREVIOUS PLANS. SOME |
| | OTHER ITEMS ARE ONLY NOW BEING SUBMITTED FOR THE FIRST |
| | REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THE METHOD ON HOW LIGHTING |
| | PERFORMANCE CALCULATIONS ARE DONE WAS SUBMITTED HOWEVER |
| | ACTUAL LIGHTING PERFORMANCE CALCULATIONS ARE SHOWN. |
| | 13-415.2 |
| | |
| | 2) NOTE: PLEASE SEE THE CIRCUITING IS NOW SHOWN, |
| | HOWEVER PLEASE SEE THE CIRCUITING FOR EMERGENCY AND |
| | EXIT LIGHTS ARE NOT PER 700.12F WHICH REQUIRES THE |
| | FIXTURES TO BE CIRCUITED TO THE LOCAL LIGHTING IN ANY |
| | ONE AREA. |
| | FOR EXAMPLE: IF THE BREAKER FOR THE NORMAL LIGHTING IN |
| | THE BATHROOMS WERE TO TRIP, THE EMERGENCY LIGHT WOULD |
| | NOT ILLUMINATE. |
| | PLEASE SEE NFPA-101 7.9.2.2 |
| | |
| | 3) NOTE: PLEASE SEE THE PANEL SCHEDULE *C* NOW SHOWS A |
| | NEW TANK-LESS WATER HEATER AT 17250 WATTS, YET THE OVER |
| | CURRENT PROTECTION IS TOO LOW BASED ON THE KW AND |
| | VOLTAGE AS SHOWN. |
| | PLEASE PROVIDE MANUFACTURE CUT SHEET WHICH INDICATES A |
| | LISTING FROM A NRTL. |
| | 90.7, 110.3 |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE NEW PANEL SCHEDULES SUBMITTED |
| | ALONG WITH LOAD CALCULATIONS HAVE BEEN CHANGED AND |
| | THERE ARE ITEMS WHICH CAN NOT BE SEEN. |
| | THE PRINT IS VERY FAINT IN LOCATIONS FOR MANY ITEMS. |
| | PLEASE SEE THE TITLE AT THE TOP OF THE PANEL WHICH SHOW |
| | LOAD. THIS CAN NOT BE FIGURED AT THIS TIME. |
| | PLEASE SEE THE PREVIOUS PANEL SCHEDULE SHOWS THE LOAD |
| | FOR THE TANK-LESS WATER HEATER NOTED ABOVE AS WHAT |
| | APPEARS TO BE 8KW, YET CALCULATIONS DO NOT SHOW THE |
| | SAME?? |
| | PLEASE SEE THE PANEL SCHEDULE ALSO DOES NOT SHOW ANY |
| | CONDUCTOR SIZES FOR BRANCH CIRCUITS. 240.4,408.4,310.16 |
| | ETC |
| | PLEASE SEE NEC 220 FOR LOAD CALCULATIONS AND |
| | ADJUSTMENTS NEED. |
| | HOW ARE LOADS DERIVED? PLEASE CLARIFY LOADS ON |
| | CALCULATIONS DO NOT SEEM TO CORRELATE WITH PANEL. FOR |
| | EXAMPLE: PLEASE SEE AHU LOADS ON PANEL, WHICH ARE NOT |
| | THE SAME ON CALCULATIONS. THIS IS THE SAME AS TANK-LESS |
| | WATER HEATER. |
| | THESE ARE A COUPLE OF EXAMPLES. |
| | PLEASE GO OVER ALL AND MAKE ADJUSTMENTS. |
| | |
| | 5) NOTE: PLEASE SEE THE RISER NOW HAS SOME OF THE |
| | SERVICE ENTRANCE CONDUCTORS AND FEEDERS SHOWN HOWEVER |
| | THE SIZES OF THESE CONDUCTORS ARE NOT RATED FOR THE |
| | OVER CURRENT PROTECTION. |
| | PLEASE KNOW THIS IS A COMMERCIAL BUILDING AND THE |
| | DE-RATINGS PERMITTED IN 310.15B6 MAY NOT BE USED. |
| | PLEASE SEE PREVIOUS NOTES MENTIONED THESE WERE NOT |
| | LARGE ENOUGH BASED ON 310.16, 240.4 AND 110.14 3/0'S |
| | ARE ONLY RATED FOR 200AMPS, YET THE MAINS ARE 225AMPS. |
| | PLEASE ADJUST CONDUCTORS ON BOTH SIDES OF MAIN |
| | DISCONNECTS. |
| | |
| | 6) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF |
| | DISCONNECT PER 250.110, 250.24, 250.122. |
| | PLEASE INCLUDE ONLY AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 7) NOTE: PLEASE CORRELATE AND GO OVER ALL CIRCUITING AS |
| | SHOWN. |
| | PLEASE SEE FOR EXAMPLE, THE LIGHTING AND POWER PLANS |
| | INDICATE CIRCUIT CHP-29 FOR SOME LIGHTS OUTSIDE AND |
| | POWER PLANS SHOWS THIS SAME CIRCUIT FEEDING SOME |
| | RECEPTACLES, HOWEVER THE PANEL SCHEDULE MENTIONS THIS |
| | CIRCUIT IS FOR *RAMP LIGHTS*. |
| | WHERE ARE THE * RAMP LIGHTS* ? |
| | PLEASE COORDINATE CIRCUITING AS NOTED ABOVE FOR |
| | EMERGENCY LIGHTING AND OTHER ITEMS ON PLANS. 408.4, |
| | 310.16, 240.4 |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |