Plan Review Notes
Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-06 15:31:26** DENIED 3RD REVIEW **
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS BASED ON
 CHANGES MADE AND NEW ITEMS NOT ON PREVIOUS PLANS. SOME
 OTHER ITEMS ARE ONLY NOW BEING SUBMITTED FOR THE FIRST
 REVIEW.
  
 1) NOTE: PLEASE SEE THE METHOD ON HOW LIGHTING
 PERFORMANCE CALCULATIONS ARE DONE WAS SUBMITTED HOWEVER
 ACTUAL LIGHTING PERFORMANCE CALCULATIONS ARE SHOWN.
 13-415.2
  
 2) NOTE: PLEASE SEE THE CIRCUITING IS NOW SHOWN,
 HOWEVER PLEASE SEE THE CIRCUITING FOR EMERGENCY AND
 EXIT LIGHTS ARE NOT PER 700.12F WHICH REQUIRES THE
 FIXTURES TO BE CIRCUITED TO THE LOCAL LIGHTING IN ANY
 ONE AREA.
 FOR EXAMPLE: IF THE BREAKER FOR THE NORMAL LIGHTING IN
 THE BATHROOMS WERE TO TRIP, THE EMERGENCY LIGHT WOULD
 NOT ILLUMINATE.
 PLEASE SEE NFPA-101 7.9.2.2
  
 3) NOTE: PLEASE SEE THE PANEL SCHEDULE *C* NOW SHOWS A
 NEW TANK-LESS WATER HEATER AT 17250 WATTS, YET THE OVER
 CURRENT PROTECTION IS TOO LOW BASED ON THE KW AND
 VOLTAGE AS SHOWN.
 PLEASE PROVIDE MANUFACTURE CUT SHEET WHICH INDICATES A
 LISTING FROM A NRTL.
 90.7, 110.3
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE NEW PANEL SCHEDULES SUBMITTED
 ALONG WITH LOAD CALCULATIONS HAVE BEEN CHANGED AND
 THERE ARE ITEMS WHICH CAN NOT BE SEEN.
 THE PRINT IS VERY FAINT IN LOCATIONS FOR MANY ITEMS.
 PLEASE SEE THE TITLE AT THE TOP OF THE PANEL WHICH SHOW
 LOAD. THIS CAN NOT BE FIGURED AT THIS TIME.
 PLEASE SEE THE PREVIOUS PANEL SCHEDULE SHOWS THE LOAD
 FOR THE TANK-LESS WATER HEATER NOTED ABOVE AS WHAT
 APPEARS TO BE 8KW, YET CALCULATIONS DO NOT SHOW THE
 SAME??
 PLEASE SEE THE PANEL SCHEDULE ALSO DOES NOT SHOW ANY
 CONDUCTOR SIZES FOR BRANCH CIRCUITS. 240.4,408.4,310.16
 ETC
 PLEASE SEE NEC 220 FOR LOAD CALCULATIONS AND
 ADJUSTMENTS NEED.
 HOW ARE LOADS DERIVED? PLEASE CLARIFY LOADS ON
 CALCULATIONS DO NOT SEEM TO CORRELATE WITH PANEL. FOR
 EXAMPLE: PLEASE SEE AHU LOADS ON PANEL, WHICH ARE NOT
 THE SAME ON CALCULATIONS. THIS IS THE SAME AS TANK-LESS
 WATER HEATER.
 THESE ARE A COUPLE OF EXAMPLES.
 PLEASE GO OVER ALL AND MAKE ADJUSTMENTS.
  
 5) NOTE: PLEASE SEE THE RISER NOW HAS SOME OF THE
 SERVICE ENTRANCE CONDUCTORS AND FEEDERS SHOWN HOWEVER
 THE SIZES OF THESE CONDUCTORS ARE NOT RATED FOR THE
 OVER CURRENT PROTECTION.
 PLEASE KNOW THIS IS A COMMERCIAL BUILDING AND THE
 DE-RATINGS PERMITTED IN 310.15B6 MAY NOT BE USED.
 PLEASE SEE PREVIOUS NOTES MENTIONED THESE WERE NOT
 LARGE ENOUGH BASED ON 310.16, 240.4 AND 110.14 3/0'S
 ARE ONLY RATED FOR 200AMPS, YET THE MAINS ARE 225AMPS.
 PLEASE ADJUST CONDUCTORS ON BOTH SIDES OF MAIN
 DISCONNECTS.
  
 6) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF
 DISCONNECT PER 250.110, 250.24, 250.122.
 PLEASE INCLUDE ONLY AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 7) NOTE: PLEASE CORRELATE AND GO OVER ALL CIRCUITING AS
 SHOWN.
 PLEASE SEE FOR EXAMPLE, THE LIGHTING AND POWER PLANS
 INDICATE CIRCUIT CHP-29 FOR SOME LIGHTS OUTSIDE AND
 POWER PLANS SHOWS THIS SAME CIRCUIT FEEDING SOME
 RECEPTACLES, HOWEVER THE PANEL SCHEDULE MENTIONS THIS
 CIRCUIT IS FOR *RAMP LIGHTS*.
 WHERE ARE THE * RAMP LIGHTS* ?
 PLEASE COORDINATE CIRCUITING AS NOTED ABOVE FOR
 EMERGENCY LIGHTING AND OTHER ITEMS ON PLANS. 408.4,
 310.16, 240.4
 FBC 106.3.5.1.2, 106.1.2
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]