| 2007-12-14 05:45:56 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07090045 |
| | ADD: 114 S. NARCISSUS AVE |
| | CONT: YOUCHAK & YOUCHAK, INC. |
| | TEL: (561)832-3800 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006/2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | **= NEW COMMENT** |
| | REVIEW: 3RD 12/13/07 |
| | ACTION: DENIED |
| | |
| | 1) OK |
| | 2)FBC 3202.2DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOOR ON THE |
| | SOUTH ELEVATION CANNOT SWING OVER THE PROPERTY LINE. |
| | **THE DOORS SHALL BE RECESS, TO PREVENT THEM FROM |
| | SWINGING INTO THE PUBLIC RIGHT-RIGHT- WAY. ** SHOW THE |
| | ENTRANCE DOOR CHANGE ON ALL PAGES REFLECTING THE |
| | ENTRANCE. ** |
| | SHEET C6A WHICH SHOWS THE PROPOSED NEW MAIN ENTRANCE |
| | INDICATES THE NEW DOOR AS A 3? X 7?. THE PRODUCT |
| | APPORVAL SUBMITTED IS FOR A 4-0 X 7-0 DOOR. WILL THE |
| | EXISTING GLASS REMAIN OR WILL IT BE REMOVED TO CREATE A |
| | LARGER OPENING? CLARIFY. |
| | |
| | 3)PER FBC TABLE 704.8 NO OPENINGS ARE PERMITTED IN |
| | WALLS 3 FEET OR LESS FROM THE PROPERTY LINE. FOR MORE |
| | INFORMATION SEE TABLE 602. INDICATE THE DISTANCE |
| | BETWEEN EACH PROPERTY LINE AT THE NORTH ELEVATION. |
| | **THE LOCATION OF THE PREVIOUS DOOR ON NARCISSUS WAS |
| | CONSTRUCTED TO PREVENT IT FROM SWINGING OVER THE PUBLIC |
| | RIGHT-OF WAY. THE NEW DOOR LOCATION SHALL MEET THE |
| | REQUIREMENT OF FBC 3202.2. WHEN THE OCCUPANT LOAD IS |
| | MORE THAN 50 THE DOOR SHALL SWING IN THE DIRECTION OF |
| | EGRESS TRAVEL FBC 1008.1.2. ** THE DOORS SHALL BE |
| | RECESS, TO PREVENT THEM FROM SWINGING INTO THE PUBLIC |
| | RIGHT-OF- WAY. |
| | **THE MAIN ENTRANCE DOOR IS IN THE SAME LOCATION |
| | SWINGING INTO THE PUBLIC RIGHT-OF-WAY ON MANY PAGES. |
| | ALL PAGES WHICH SHOW THE MAIN ENTRANCE SHALL SHOW |
| | CLEARLY HOW IT WILL BE CONSTRUCTED. IF CHANGES WERE |
| | MADE, SHOW IT ON ALL PAGES. ** |
| | |
| | 4)OK |
| | 5)OK |
| | 6)OK |
| | 7)OK |
| | 8)OK |
| | 9)OK |
| | 10)OK |
| | 11)OK |
| | |
| | PAGES 9-11 DO NOT SHOW THE ITEMS SPECIFIC TO THE |
| | SHUTTERS. |
| | 12)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. THE PRODUCT |
| | APPROVALS SUBMITTED SHALL INDICATE WHICH ITEMS OR |
| | SYSTEMS WILL BE USED TO INSTALL THE PRODUCT. THE |
| | PRODUCT APPROVALS SHALL BE APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. |
| | **NOTED: ON THE PRODUCT APPROVAL, MARK WHICH DETAILS |
| | APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A |
| | HIGHLIGHTER. COMPLETE THE ATTACHED INSTALLATION |
| | SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE |
| | COMPLIANCE IN ANOTHER FORMAT (SHUTTERS) **ON PAGES 9-11 |
| | INDICATE WHICH ROW AND COLUMN PERTAIN TO THE SHUTTER |
| | INSTALLATION. ** |
| | |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |
| | |