| Plan Review Notes For Permit 07090045 |
| Permit Number |
07090045 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-17 08:25:23 | DENIED; | | | 1. OLD COMMENT 2F; (NO) FLOOR DRAINS ARE STILL SHOWN ON | | | SANITARY RISER DIAGRAM. ALL INDIRECT WASTES SHALL GO TO | | | AAPPROVED WASTE RECEPTOR AS DISCRIBED IN FBC-PLUMBING | | | SECTION 802.3. | | | NEW COMMENTS; | | | 2.TABLE 403.1(A-2) MIN. FIXTURE REQUIREMENTS HAS NOT | | | BEEN MET. WOMANS ROOM REQUIRES 3 TOILETS, AND A | | | DRINKING FOUNTAIN IS ALSO REQUIRED. | | | 3. WATER SERVICE IS NOT LARGE ENOUGH. SEE TABLE 603.1. | | | SHOW CALCULATIONS. | | | 4. SANITARY RISER DIAGRAM; HORIZONTAL DRY VENTS ARE NOT | | | PERMITED, SEE SECTION 905.3. (HI-LIGHTED) ON ONE SET OF | | | PLANS. | | | (A) THE 4" A.A.V.SHALL BE UPSTREAM OF THE | | | FIXTURE GROUP (BAR) SEE SECTION 909.1, WET VENT. | | | 5. PLUMBING FIXTURELIST;ARE ALL TOILETS HANDICAP | | | HIGHT? | | | 6. WATER RISER DIAGRAM; HOT WATER TO THE HAND SINKS AND | | | LAVATORY'S SHOULD BE NO HOTER THAN 110, THE DISHWASHERS | | | AND WASH SINKS WOULD REQUIRE HOTER WATER. SHOW HOW THIS | | | WILL BE DONE. |
|