2007-11-08 10:27:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE PLANS PAGE C19A SHOWS THREE 8" DIA. GRAVITY
 EXHAUSTS, PAGE C19 SHOWS ONLY TWO BATHROOM EXHAUST
 FANS, PLEASE EXPLAIN OR CORRECT.
  
 2) PAGE C19A IS STATING GRAVITY EXHAUST. PAGE C19 FAN
 SCHEDULE SHOWS ELECTRICAL EXHAUST FANS, PLEASE EXPLAIN
 OR CORRECT.
  
 3) PAGE C19 FAN SCHEDULE SHOWS TWO EXHAUST FANS EACH AT
 405 CFM'S WITH A 4" DUCT, THAT WOULD PUT THE AIR
 VELOCITY AROUND 4,600 FPM. PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR BATHROOM EXHAUST FANS.
  
 4) HVAC SCHEDULE SHOW THE HEATERS AT 150 BTUH THAT
 WOULD BE ABOUT 0.04 KW, ELECTRICAL PLANS SHOW THE
 HEATERS AT 12 KW. PLEASE CORRECT.
  
 5) PAGE C19 SHOWS THE SPACE ABOVE THE LAVATORIES IS AN
 OPEN PLENUM. PLEASE ADD A NOTE THAT STATES NO
 COMBUSTIBLE MATERIALS PERMITTED IN PLENUM, TO COMPLY
 WITH 2004 FBC/M 602.2.1. AND NO EXHAUST DUCTS UNDER
 POSITIVE PRESSURE, CHIMNEYS,OR VENTS PERMITTED IN
 PLENUM, TO COMPLY WITH 2004 FBC/M 601.3.
  
 6) PAGE C19 SHOWS THREE FLEX DUCTS, PLEASE SHOW SIZE OF
 FLEX, SEE 2004 FBC 106.3.5.
  
 7) PAGE C19 LEGEND SHOWS THE SYMBOL FOR AN EXHAUST FAN,
 SEE SYMBOLS IN BATHROOMS ARE SHOWING AS RETURN GRILLS.
 PLEASE CORRECT.
  
 8) SEE PAGE C19 MAKEUP AIR VENTILATION RATE. DO YOU
 MEAN OUTDOOR AIR? SEE 2004 FBC/M CH. 2 DEFINITIONS.
  
 9) MAKEUP AIR CALCULATIONS (OUTDOOR AIR ?) SHOWS 6000
 CFM AND 810 CFM BEING EXHAUSTED AT BATHROOMS = 5,190
 CFM OF POSITIVE PRESSURE. SEE 2004 FBC/M 403.1
 VENTILATION SYSTEM.
 MECHANICAL VENTILATION SHALL BE PROVIDED BY A METHOD OF
 SUPPLY AIR AND RETURN OR EXHAUST AIR. THE AMOUNT OF
 SUPPLY AIR SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT
 OF RETURN AND EXHAUST AIR. IF OUTDOOR AIR CALCULATIONS
 WERE DONE BY ASHRAE 62.1 STANDARD THE BUILDING WOULD
 NOT BE AT SUCH A POSITIVE PRESSURE. PLEASE LOOK INTO.
 SEE 2004 FBC/M 403.4.
  
 10) PAGE C19 SHOWS A LARGE 72" X 32" GRILL, SEE YELLOW
 HIGH LIGHT ON PLAN. PLEASE EXPLAIN OR CORRECT.
  