| 2007-11-08 10:27:51 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) SEE PLANS PAGE C19A SHOWS THREE 8" DIA. GRAVITY |
| | EXHAUSTS, PAGE C19 SHOWS ONLY TWO BATHROOM EXHAUST |
| | FANS, PLEASE EXPLAIN OR CORRECT. |
| | |
| | 2) PAGE C19A IS STATING GRAVITY EXHAUST. PAGE C19 FAN |
| | SCHEDULE SHOWS ELECTRICAL EXHAUST FANS, PLEASE EXPLAIN |
| | OR CORRECT. |
| | |
| | 3) PAGE C19 FAN SCHEDULE SHOWS TWO EXHAUST FANS EACH AT |
| | 405 CFM'S WITH A 4" DUCT, THAT WOULD PUT THE AIR |
| | VELOCITY AROUND 4,600 FPM. PLEASE SUBMIT DETAILED |
| | MANUFACTURER'S SPECIFICATION'S AND INSTALLATION |
| | INSTRUCTIONS FOR BATHROOM EXHAUST FANS. |
| | |
| | 4) HVAC SCHEDULE SHOW THE HEATERS AT 150 BTUH THAT |
| | WOULD BE ABOUT 0.04 KW, ELECTRICAL PLANS SHOW THE |
| | HEATERS AT 12 KW. PLEASE CORRECT. |
| | |
| | 5) PAGE C19 SHOWS THE SPACE ABOVE THE LAVATORIES IS AN |
| | OPEN PLENUM. PLEASE ADD A NOTE THAT STATES NO |
| | COMBUSTIBLE MATERIALS PERMITTED IN PLENUM, TO COMPLY |
| | WITH 2004 FBC/M 602.2.1. AND NO EXHAUST DUCTS UNDER |
| | POSITIVE PRESSURE, CHIMNEYS,OR VENTS PERMITTED IN |
| | PLENUM, TO COMPLY WITH 2004 FBC/M 601.3. |
| | |
| | 6) PAGE C19 SHOWS THREE FLEX DUCTS, PLEASE SHOW SIZE OF |
| | FLEX, SEE 2004 FBC 106.3.5. |
| | |
| | 7) PAGE C19 LEGEND SHOWS THE SYMBOL FOR AN EXHAUST FAN, |
| | SEE SYMBOLS IN BATHROOMS ARE SHOWING AS RETURN GRILLS. |
| | PLEASE CORRECT. |
| | |
| | 8) SEE PAGE C19 MAKEUP AIR VENTILATION RATE. DO YOU |
| | MEAN OUTDOOR AIR? SEE 2004 FBC/M CH. 2 DEFINITIONS. |
| | |
| | 9) MAKEUP AIR CALCULATIONS (OUTDOOR AIR ?) SHOWS 6000 |
| | CFM AND 810 CFM BEING EXHAUSTED AT BATHROOMS = 5,190 |
| | CFM OF POSITIVE PRESSURE. SEE 2004 FBC/M 403.1 |
| | VENTILATION SYSTEM. |
| | MECHANICAL VENTILATION SHALL BE PROVIDED BY A METHOD OF |
| | SUPPLY AIR AND RETURN OR EXHAUST AIR. THE AMOUNT OF |
| | SUPPLY AIR SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT |
| | OF RETURN AND EXHAUST AIR. IF OUTDOOR AIR CALCULATIONS |
| | WERE DONE BY ASHRAE 62.1 STANDARD THE BUILDING WOULD |
| | NOT BE AT SUCH A POSITIVE PRESSURE. PLEASE LOOK INTO. |
| | SEE 2004 FBC/M 403.4. |
| | |
| | 10) PAGE C19 SHOWS A LARGE 72" X 32" GRILL, SEE YELLOW |
| | HIGH LIGHT ON PLAN. PLEASE EXPLAIN OR CORRECT. |
| | |