Plan Review Notes
Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-07 15:24:01** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 AND SEVERAL NEW COMMENTS DUE TO NEW INFORMATION/DETAILS
 NOW ON PLANS WHICH HAVE CREATED NEW COMMENTS.
  
 1) NOTE: PLEASE SEE THAT NO LIGHTING ENERGY/PERFORMANCE
 CALCULATIONS WERE SUBMITTED.
 PLEASE SEE 13-101.1.3, 13-415.2
 (PREVIOUS REVIEW )
  
 2) NOTE: PLEASE SEE MISSING ADA LEVELS FOR FA DEVICES.
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4).
 DEVICE LOCATIONS ARE SHOWN HOWEVER NO MINIMUM LEVELS
 COULD BE LOCATED.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL SERVICE RISER IS IN
 NEED OF CHANGES.
 PLEASE SEE NO SERVICE ENTRANCE CONDUCTORS ARE SHOWN.
 CAN NOT DETERMINE OR REVIEW AMPACITY OF CONDUCTORS AT
 THIS TIME AS NONE ARE SHOWN.
 PLEASE SEE THE CONDUCTORS FROM METER TO MAIN AND MAIN
 TO PANELS ARE NOT OF SUFFICIENT SIZE. PLEASE ALSO SEE
 THAT THE NUMBER OF CONDUCTORS IS NOT SHOWN.
 PLEASE SEE NEC 240.4, 310.16.
  
 4) NOTE: PLEASE SEEM MISSING COLD WATER PIPE FOR
 GROUNDING ELECTRODE SYSTEM 250.50
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE
 FOR A RESIDENTIAL DWELLING.
 PLEASE SEE NEC 220, 220.12,220.14, 220.42, 220.44, ETC
 PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. 215.3, 230.42
  
 6) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE THERE ARE ELECTRICAL ITEMS ON PLANS WHICH ONLY
 CONTAIN PART OF THE NUMERICAL CIRCUIT DESIGNATION.
 (EXAMPLE ICE MACHINE).
 PLEASE THERE ARE SEVERAL ELECTRICAL RECEPTACLE
 LOCATIONS WHICH DO NOT INDICATE ANY CIRCUITS.
 PLEASE SEE AS THE ELECTRICAL DISCONNECTS FOR A/C RT
 UNITS ARE NOT SHOWN ON ELECTRICAL PLANS PLEASE INDICATE
 CIRCUITS.
 FBC 106.3.5.1.2, 106.1.2
 NEC 408.4.
  
 7) NOTE: PLEASE CLARIFY THE SAME CLEARANCE REQUIREMENTS
 FOR THE PANELS. ONE DETAIL ON SHEET 24, INDICATES
 MINIMUM CLEARANCES HOWEVER THERE IS ONE DETAIL WHICH
 SHOWS AN ELEVATION OF A COUNTER IN FRONT OF PANELS
 WHICH IS NOT PERMITTED. ONE OTHER DETAIL SHOWS A JOG IN
 COUNTER AND ANOTHER DETAIL DOES NOT.
  
 8) NOTE: PLEASE SEE DETAILS FOR FLOOR TILE LIGHTS WHERE
 THE CONNECTION DETAILS AS SHOWN DO NOT COMPLY WITH
 MANUFACTURES INSTALLATION OR WITH APPROVED CONNECTORS
 FOR USE. *SEAL-TITE* CONNECTORS ARE NOT FOR USE WITH
 THESE CABLES ARE MENTIONED.
 PLEASE KNOW THAT ALL INSTALLATIONS SHALL MEET NEC 300,
 110.3 ETC.
 THE DETAIL AS SHOWN AND AS PREVIOUSLY SPOKE ABOUT IS
 STILL NOT APPROVED AS SHOWN.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WIHT RESPECT TOP
 REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 ** PLEASE SEE THERE ARE SEVERAL CHANGES NEEDED AND
 ITEMS WHICH CAN NOT BE REVIEWED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]