| 2007-11-07 15:24:01 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW |
| | AND SEVERAL NEW COMMENTS DUE TO NEW INFORMATION/DETAILS |
| | NOW ON PLANS WHICH HAVE CREATED NEW COMMENTS. |
| | |
| | 1) NOTE: PLEASE SEE THAT NO LIGHTING ENERGY/PERFORMANCE |
| | CALCULATIONS WERE SUBMITTED. |
| | PLEASE SEE 13-101.1.3, 13-415.2 |
| | (PREVIOUS REVIEW ) |
| | |
| | 2) NOTE: PLEASE SEE MISSING ADA LEVELS FOR FA DEVICES. |
| | PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). |
| | DEVICE LOCATIONS ARE SHOWN HOWEVER NO MINIMUM LEVELS |
| | COULD BE LOCATED. |
| | |
| | 3) NOTE: PLEASE SEE THE ELECTRICAL SERVICE RISER IS IN |
| | NEED OF CHANGES. |
| | PLEASE SEE NO SERVICE ENTRANCE CONDUCTORS ARE SHOWN. |
| | CAN NOT DETERMINE OR REVIEW AMPACITY OF CONDUCTORS AT |
| | THIS TIME AS NONE ARE SHOWN. |
| | PLEASE SEE THE CONDUCTORS FROM METER TO MAIN AND MAIN |
| | TO PANELS ARE NOT OF SUFFICIENT SIZE. PLEASE ALSO SEE |
| | THAT THE NUMBER OF CONDUCTORS IS NOT SHOWN. |
| | PLEASE SEE NEC 240.4, 310.16. |
| | |
| | 4) NOTE: PLEASE SEEM MISSING COLD WATER PIPE FOR |
| | GROUNDING ELECTRODE SYSTEM 250.50 |
| | |
| | 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE |
| | FOR A RESIDENTIAL DWELLING. |
| | PLEASE SEE NEC 220, 220.12,220.14, 220.42, 220.44, ETC |
| | PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT |
| | 125%. 215.3, 230.42 |
| | |
| | 6) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE |
| | SEE THERE ARE ELECTRICAL ITEMS ON PLANS WHICH ONLY |
| | CONTAIN PART OF THE NUMERICAL CIRCUIT DESIGNATION. |
| | (EXAMPLE ICE MACHINE). |
| | PLEASE THERE ARE SEVERAL ELECTRICAL RECEPTACLE |
| | LOCATIONS WHICH DO NOT INDICATE ANY CIRCUITS. |
| | PLEASE SEE AS THE ELECTRICAL DISCONNECTS FOR A/C RT |
| | UNITS ARE NOT SHOWN ON ELECTRICAL PLANS PLEASE INDICATE |
| | CIRCUITS. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NEC 408.4. |
| | |
| | 7) NOTE: PLEASE CLARIFY THE SAME CLEARANCE REQUIREMENTS |
| | FOR THE PANELS. ONE DETAIL ON SHEET 24, INDICATES |
| | MINIMUM CLEARANCES HOWEVER THERE IS ONE DETAIL WHICH |
| | SHOWS AN ELEVATION OF A COUNTER IN FRONT OF PANELS |
| | WHICH IS NOT PERMITTED. ONE OTHER DETAIL SHOWS A JOG IN |
| | COUNTER AND ANOTHER DETAIL DOES NOT. |
| | |
| | 8) NOTE: PLEASE SEE DETAILS FOR FLOOR TILE LIGHTS WHERE |
| | THE CONNECTION DETAILS AS SHOWN DO NOT COMPLY WITH |
| | MANUFACTURES INSTALLATION OR WITH APPROVED CONNECTORS |
| | FOR USE. *SEAL-TITE* CONNECTORS ARE NOT FOR USE WITH |
| | THESE CABLES ARE MENTIONED. |
| | PLEASE KNOW THAT ALL INSTALLATIONS SHALL MEET NEC 300, |
| | 110.3 ETC. |
| | THE DETAIL AS SHOWN AND AS PREVIOUSLY SPOKE ABOUT IS |
| | STILL NOT APPROVED AS SHOWN. |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WIHT RESPECT TOP |
| | REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL CHANGES NEEDED AND |
| | ITEMS WHICH CAN NOT BE REVIEWED. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |