Plan Review Notes
Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop B
Sequence Number 2
Notes
Date Text
2007-11-14 13:55:34 
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090045
 ADD: 114 S. NARCISSUS AVE
 CONT: YOUCHAK & YOUCHAK, INC.
 TEL: (561)832-3800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 **= NEW COMMENT**
 REVIEW: 2ND 11/10/07
 ACTION: DENIED
  
 1) OK
  
 2)FBC 3202.2DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOOR ON THE
 SOUTH ELEVATION CANNOT SWING OVER THE PROPERTY LINE.
 **THE DOORS SHALL BE RECESS, TO PREVENT THEM FROM
 SWINGING INTO THE PUBLIC RIGHT-RIGHT- WAY.**
 FBC11-4.5.2 CHANGES IN LEVEL GREATER THAN ? INCH SHALL
 BE ACCOMPLISHED BY MEANS OF A RAMP THAT COMPLIES WITH
 SECTION 11-4.7 OR 11-4.8. THIS SECTION REFERS TO ALL
 DOORS.
  
 3)PER FBC TABLE 704.8 NO OPENINGS ARE PERMITTED IN
 WALLS 3 FEET OR LESS FROM THE PROPERTY LINE. FOR MORE
 INFORMATION SEE TABLE 602. INDICATE THE DISTANCE
 BETWEEN EACH PROPERTY LINE AT THE NORTH ELEVATION.
 **THE LOCATION OF THE PREVIOUS DOOR ON NARCISSUS WAS
 CONSTRUCTED TO PREVENT IT FROM SWINGING OVER THE PUBLIC
 RIGHT-OF WAY. THE NEW DOOR LOCATION SHALL MEET THE
 REQUIREMENT OF FBC 3202.2. WHEN THE OCCUPANT LOAD IS
 MORE THAN 50 THE DOOR SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL FBC 1008.1.2. ** THE DOORS SHALL BE
 RECESS, TO PREVENT THEM FROM SWINGING INTO THE PUBLIC
 RIGHT-RIGHT- WAY.** FBC11-4.5.2 CHANGES IN LEVEL
 GREATER THAN ? INCH SHALL BE ACCOMPLISHED BY MEANS OF A
 RAMP THAT COMPLIES WITH SECTION 11-4.7 OR 11-4.8. THIS
 SECTION REFERS TO ALL DOORS.
  
 4)OK
 5)OK
 6)OK
 7)OK
 8)OK
  
 9)FBC 106.3.5.1.1 SUBMIT THE LIFE SAFETY PLAN
 INDICATING THE MEANS OF EGRESS, EXIT ACCESS, EXIT, EXIT
 DISCHARGE. THE EXTERIOR ELEVATIONS SHALL INCLUDE ALL
 STEPS, RAMPS AND LANDINGS LEADING TO OR FROM THE EGRESS
 DOORS.
 **ARE ALL THE EXITS SHOWN ON DRAWINGS HANDI-CAP
 ACCESSIBLE? IF NOT, THE ONES WHICH ARE SHALL BE CLEARLY
 SHOWN.
  
 10)SHOW THE ACCESSIBLE ROUTE LEADING TO THE EXIT
 DOORS. SIGNS SHALL BE PLACE IN ACCORDANCE WITH SECTIONS
 11-4.30.6 / 11-4.1/ 11-4.3.
 ** NOTED: HOWEVER, IT SEEMS AS THOUGH ALL THE DOORS ARE
 NOT HANDI-CAP ACCESSIBLE.**
  
 11)OK
 12)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. THE PRODUCT
 APPROVALS SUBMITTED SHALL INDICATE WHICH ITEMS OR
 SYSTEMS WILL BE USED TO INSTALL THE PRODUCT. THE
 PRODUCT APPROVALS SHALL BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
 **NOTED: ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER. COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT(SHUTTERS)
  
 **NEW**
 A) 2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. DUE TO THE FACT
 THAT THE INTERIOR CONSTRUCTION OF THE BUILDING WAS
 COMPLETELY DEMOED, THIS ALTERATION SEEMS TO BE A LEVEL
 3 ALTERATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]