| | BUILDING PLAN REVIEW |
| | PERMIT: 07090045 |
| | ADD: 114 S. NARCISSUS AVE |
| | CONT: YOUCHAK & YOUCHAK, INC. |
| | TEL: (561)832-3800 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006/2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | **= NEW COMMENT** |
| | REVIEW: 2ND 11/10/07 |
| | ACTION: DENIED |
| | |
| | 1) OK |
| | |
| | 2)FBC 3202.2DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOOR ON THE |
| | SOUTH ELEVATION CANNOT SWING OVER THE PROPERTY LINE. |
| | **THE DOORS SHALL BE RECESS, TO PREVENT THEM FROM |
| | SWINGING INTO THE PUBLIC RIGHT-RIGHT- WAY.** |
| | FBC11-4.5.2 CHANGES IN LEVEL GREATER THAN ? INCH SHALL |
| | BE ACCOMPLISHED BY MEANS OF A RAMP THAT COMPLIES WITH |
| | SECTION 11-4.7 OR 11-4.8. THIS SECTION REFERS TO ALL |
| | DOORS. |
| | |
| | 3)PER FBC TABLE 704.8 NO OPENINGS ARE PERMITTED IN |
| | WALLS 3 FEET OR LESS FROM THE PROPERTY LINE. FOR MORE |
| | INFORMATION SEE TABLE 602. INDICATE THE DISTANCE |
| | BETWEEN EACH PROPERTY LINE AT THE NORTH ELEVATION. |
| | **THE LOCATION OF THE PREVIOUS DOOR ON NARCISSUS WAS |
| | CONSTRUCTED TO PREVENT IT FROM SWINGING OVER THE PUBLIC |
| | RIGHT-OF WAY. THE NEW DOOR LOCATION SHALL MEET THE |
| | REQUIREMENT OF FBC 3202.2. WHEN THE OCCUPANT LOAD IS |
| | MORE THAN 50 THE DOOR SHALL SWING IN THE DIRECTION OF |
| | EGRESS TRAVEL FBC 1008.1.2. ** THE DOORS SHALL BE |
| | RECESS, TO PREVENT THEM FROM SWINGING INTO THE PUBLIC |
| | RIGHT-RIGHT- WAY.** FBC11-4.5.2 CHANGES IN LEVEL |
| | GREATER THAN ? INCH SHALL BE ACCOMPLISHED BY MEANS OF A |
| | RAMP THAT COMPLIES WITH SECTION 11-4.7 OR 11-4.8. THIS |
| | SECTION REFERS TO ALL DOORS. |
| | |
| | 4)OK |
| | 5)OK |
| | 6)OK |
| | 7)OK |
| | 8)OK |
| | |
| | 9)FBC 106.3.5.1.1 SUBMIT THE LIFE SAFETY PLAN |
| | INDICATING THE MEANS OF EGRESS, EXIT ACCESS, EXIT, EXIT |
| | DISCHARGE. THE EXTERIOR ELEVATIONS SHALL INCLUDE ALL |
| | STEPS, RAMPS AND LANDINGS LEADING TO OR FROM THE EGRESS |
| | DOORS. |
| | **ARE ALL THE EXITS SHOWN ON DRAWINGS HANDI-CAP |
| | ACCESSIBLE? IF NOT, THE ONES WHICH ARE SHALL BE CLEARLY |
| | SHOWN. |
| | |
| | 10)SHOW THE ACCESSIBLE ROUTE LEADING TO THE EXIT |
| | DOORS. SIGNS SHALL BE PLACE IN ACCORDANCE WITH SECTIONS |
| | 11-4.30.6 / 11-4.1/ 11-4.3. |
| | ** NOTED: HOWEVER, IT SEEMS AS THOUGH ALL THE DOORS ARE |
| | NOT HANDI-CAP ACCESSIBLE.** |
| | |
| | 11)OK |
| | 12)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. THE PRODUCT |
| | APPROVALS SUBMITTED SHALL INDICATE WHICH ITEMS OR |
| | SYSTEMS WILL BE USED TO INSTALL THE PRODUCT. THE |
| | PRODUCT APPROVALS SHALL BE APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. |
| | **NOTED: ON THE PRODUCT APPROVAL, MARK WHICH DETAILS |
| | APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A |
| | HIGHLIGHTER. COMPLETE THE ATTACHED INSTALLATION |
| | SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE |
| | COMPLIANCE IN ANOTHER FORMAT(SHUTTERS) |
| | |
| | **NEW** |
| | A) 2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. DUE TO THE FACT |
| | THAT THE INTERIOR CONSTRUCTION OF THE BUILDING WAS |
| | COMPLETELY DEMOED, THIS ALTERATION SEEMS TO BE A LEVEL |
| | 3 ALTERATION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |