| Plan Review Notes For Permit 07090045 |
| Permit Number |
07090045 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-26 10:34:16 | DENIED; | | | 1.SEALED PLANS TO HAVE DATE WITH SIGNITURE. | | | 2. PLANS SEEM TO MEET FBC-2004 EXISTING BUILDING | | | CHAPTER 7 ( LEVEL 3 ). THIS WOULD MEAN THE BATHROOMS | | | ARE REQUIRED TO MEET THE REQUIREMENTS OF CHAPTER 11, | | | HANDICAP REQUIREMENTS. ( BATHROOMS DO NOT COMPLY) 3. | | | SHOW ON PLANS COMPLIANCE TO FBC-2004 PLUMBING TABLE | | | 403.1 (1A-2) NUMBER OF PEOPLE, FIXTURES REQUIRED. 4. | | | SANITARY RISER DIAGRAM; ( FROM LEFT TO RIGHT) | | | A)ICE BIN INDIRECT WASTE MUST GO DIRECTLY TO | | | FLOOR SINK, NOT TIE INTO HAND SINK. | | | B) DISHWASHER TO BE INDIRECTLY WASTED SEC.802.2 | | | TO A FLOOR SINK. | | | C) ICE BIN NOT PERMITED TODISCHARGEINTO | | | BATHROOM FLOOR DRAIN. (FLOOR SINK REQUIRED) | | | D) TOILETS NOT VENTED | | | E) ICE MACHINE CANNOT DISCHARGE INTO WOMANS ROOM | | | FLOOR DRAIN. | | | F) FLOOR SINKS OR HUB DRAINS ARE REQUIRED FOR | | | ALL INDIRECT WASTE SEE SECTIONS 802.3 AND 802.3.1 | | | G) WATER AND SANITARY RISER DIAGRAMS ARE REQUIRED TO BE | | | ISOMETRIC IN DESIGN AND REFLECT THE FLOOR PLAN. | | | 5. HOT WATER IS REQUIRED FOR THE HAND SINKS AND | | | DISHWASHERS SECTION607.1.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|