| 2007-09-24 12:17:03 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PLEASE REMOVE THE ROOF FRAMING LAY-OUT FROM THE |
| | MECHANICAL PLAN PAGE 397-001-C19, AS IT CAN NOT BE READ |
| | AT THIS TIME. |
| | |
| | 2) PLEASE SUBMIT A MECHANICAL PLAN THAT SHOW THE |
| | LOCATION OF THE EXISTING A/C UNITS AND ANY NEW UNITS. |
| | SHOW ALL NEW AND EXISTING SUPPLY AND RETURN AIR DUCTS. |
| | STATE WHAT IS NEW AND EXISTING ON PLAN. |
| | |
| | 3) SHOW BATHROOM EXHAUST FANS AND CFM'S ON MECHANICAL |
| | PLAN, SEE FBC/M 403.3. |
| | |
| | 4) MECHANICAL PLAN SHOWS A RETURN AIR DUCT IN THE |
| | BATHROOM, RETURN AIR GRILLS ARE NOT PERMITTED IN |
| | RESTROOM, SEE FBC/M 407.1. PLEASE CORRECT. |
| | |
| | 5) THERE ARE TWO HVAC SCHEDULES ON THE MECHANICAL PLAN, |
| | PLEASE EXPLAIN OR CORRECT. |
| | |
| | 6) SHOW OUTDOOR AIR CALCULATIONS ON MECHANICAL PLAN, |
| | SEE FBC/M 401.2. |
| | |
| | 7)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, SEE F.B.C. 106.1.1. |
| | |
| | 8) THE CERTIFICATE OF AUTH. FOR YOUCHAK & YOUCHAK IS |
| | DELINQUENT, PLEASE CORRECT. |
| | |
| | 9) WHEN SIGNING AND SEALING PLANS THE DATE MUST ALSO |
| | APPEAR, SEE FAC 61G15-23.002. PLEASE CORRECT. |
| | |