2007-09-24 12:17:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE REMOVE THE ROOF FRAMING LAY-OUT FROM THE
 MECHANICAL PLAN PAGE 397-001-C19, AS IT CAN NOT BE READ
 AT THIS TIME.
  
 2) PLEASE SUBMIT A MECHANICAL PLAN THAT SHOW THE
 LOCATION OF THE EXISTING A/C UNITS AND ANY NEW UNITS.
 SHOW ALL NEW AND EXISTING SUPPLY AND RETURN AIR DUCTS.
 STATE WHAT IS NEW AND EXISTING ON PLAN.
  
 3) SHOW BATHROOM EXHAUST FANS AND CFM'S ON MECHANICAL
 PLAN, SEE FBC/M 403.3.
  
 4) MECHANICAL PLAN SHOWS A RETURN AIR DUCT IN THE
 BATHROOM, RETURN AIR GRILLS ARE NOT PERMITTED IN
 RESTROOM, SEE FBC/M 407.1. PLEASE CORRECT.
  
 5) THERE ARE TWO HVAC SCHEDULES ON THE MECHANICAL PLAN,
 PLEASE EXPLAIN OR CORRECT.
  
 6) SHOW OUTDOOR AIR CALCULATIONS ON MECHANICAL PLAN,
 SEE FBC/M 401.2.
  
 7)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 8) THE CERTIFICATE OF AUTH. FOR YOUCHAK & YOUCHAK IS
 DELINQUENT, PLEASE CORRECT.
  
 9) WHEN SIGNING AND SEALING PLANS THE DATE MUST ALSO
 APPEAR, SEE FAC 61G15-23.002. PLEASE CORRECT.
  