Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-11 11:43:32******DENIED*****
  
  
 01.ON THE SHEET TITLED GENERAL NOTES & LEGEND
 (DRAWING NUMBER 397-001-C2) UNDER BUILDING DESIGN DATA,
 AN INCORRECT/MISPRINT REFERENCE TO NFPA 101(200
 EDITION) IS LISTED.AS LISTED IN THE APPLICABLE CODES
 OF THE SAME SHEET, THE 2003 EDITION SHALL BE
 REFERENCED.
  
 02.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 03.ALL STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS SHALL COMPLY WITH
 NFPA 241.
  
 04.THE DEMOLITION AND/OR THE CONSTRUCTION OPERATIONS
 SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING STREETS,
 ALLEYS, FIRE LANES) .
  
 05.PROVIDE TEMPORARY ADDRESS NUMBERS IF THE
 DEMOLITION EXTERIOR ELEVATION OPERATION HAS CAUSE FOR
 THE EXISTING ADRRESS TO BE REMOVED.
  
 06.ON THE NEW NITECLUB FRONT ELEVATION, SHOW/DISPLAY
 THE NUMERICAL ADDRESS ON THE BUILDING (NOT DOOR) TO BE
 VISIBLE FROM SOUTH NARCISSUS AVENUE.HURRICANE
 SHUTTERS SHALL NOT BE PERMITTED TO COVER OR CONCEAL
 ADDRESSES.
  
 07.PROVIDE A LIFE SAFETY PLAN SHEET WHICH ILLUSTRATES
 TRAVEL DISTANCE TO THE EXITS.EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) MAY ALSO BE INCLUDED
 ON THIS PLAN SHEET.
  
 08.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN IN THE
 REFLECTED CEILING LIGHTING PLAN.
  
 09.MEANS OF EGRESS FROM A ROOM OR SPACESHALL NOT BE
 PREMITTED THROUGH KITCHENS, STOREROOMS, RESTROOMS,
 CLOSETS, STAGES, DJ BOOTHS, OR HAZARDOUS AREAS.
  
 10.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 11.PROVIDE PRESCRITIVE STRENGHT AND SPECIFICATIONS
 FOR THE HANDRAILS.
  
 12.PROVIDE SPECIFIATIONS OR DETAILS OF THE ADA RAMP.
  
 13.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL FOR THE EXITS, EXIT AISLE CORRIDORS, AND ALL
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 14.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASS II.
  
 15.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY
 ADDRESSABLE, MONITORED, AND SHALL BE UL CERTIFICATED
 FOR CENTRAL STATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722