| 2007-10-11 11:43:32 | ******DENIED***** |
| | |
| | |
| | 01.ON THE SHEET TITLED GENERAL NOTES & LEGEND |
| | (DRAWING NUMBER 397-001-C2) UNDER BUILDING DESIGN DATA, |
| | AN INCORRECT/MISPRINT REFERENCE TO NFPA 101(200 |
| | EDITION) IS LISTED.AS LISTED IN THE APPLICABLE CODES |
| | OF THE SAME SHEET, THE 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 02.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE |
| | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 03.ALL STRUCTURES UNDERGOING CONSTRUCTION, |
| | ALTERATION, OR DEMOLITION OPERATIONS SHALL COMPLY WITH |
| | NFPA 241. |
| | |
| | 04.THE DEMOLITION AND/OR THE CONSTRUCTION OPERATIONS |
| | SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS |
| | TO THE PROPERTY OR VICINITY THEREOF (INCLUDING STREETS, |
| | ALLEYS, FIRE LANES) . |
| | |
| | 05.PROVIDE TEMPORARY ADDRESS NUMBERS IF THE |
| | DEMOLITION EXTERIOR ELEVATION OPERATION HAS CAUSE FOR |
| | THE EXISTING ADRRESS TO BE REMOVED. |
| | |
| | 06.ON THE NEW NITECLUB FRONT ELEVATION, SHOW/DISPLAY |
| | THE NUMERICAL ADDRESS ON THE BUILDING (NOT DOOR) TO BE |
| | VISIBLE FROM SOUTH NARCISSUS AVENUE.HURRICANE |
| | SHUTTERS SHALL NOT BE PERMITTED TO COVER OR CONCEAL |
| | ADDRESSES. |
| | |
| | 07.PROVIDE A LIFE SAFETY PLAN SHEET WHICH ILLUSTRATES |
| | TRAVEL DISTANCE TO THE EXITS.EXIT LIGHTS, EMERGENCY |
| | LIGHTS, AND FIRE EXTINGUISHER(S) MAY ALSO BE INCLUDED |
| | ON THIS PLAN SHEET. |
| | |
| | 08.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN IN THE |
| | REFLECTED CEILING LIGHTING PLAN. |
| | |
| | 09.MEANS OF EGRESS FROM A ROOM OR SPACESHALL NOT BE |
| | PREMITTED THROUGH KITCHENS, STOREROOMS, RESTROOMS, |
| | CLOSETS, STAGES, DJ BOOTHS, OR HAZARDOUS AREAS. |
| | |
| | 10.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | 11.PROVIDE PRESCRITIVE STRENGHT AND SPECIFICATIONS |
| | FOR THE HANDRAILS. |
| | |
| | 12.PROVIDE SPECIFIATIONS OR DETAILS OF THE ADA RAMP. |
| | |
| | 13.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIAL FOR THE EXITS, EXIT AISLE CORRIDORS, AND ALL |
| | OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 14.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF |
| | CLASS I OR CLASS II. |
| | |
| | 15.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY |
| | ADDRESSABLE, MONITORED, AND SHALL BE UL CERTIFICATED |
| | FOR CENTRAL STATION. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |