| 2007-09-25 12:36:04 | ** DENIED** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON |
| | PLANS. |
| | PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE THE TOP OF397-001-C2 WHICH PRINTED THE |
| | LS CODE A EDITION 200. THIS SEEMS TO HAVE BEEN A |
| | MISPRINT. |
| | |
| | ** PLEASE SEE PLANS ALSO CALL FOR *PALM BEACH COUNTY |
| | AMENDMENTS* HOWEVER THIS PROJECT IS NOT LOCATED IN PALM |
| | BEACH COUNTY JURISDICTION. THIS IS LOCATED IN THE CITY |
| | OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SEE THE INFORMATION SHOWN ON TITLE |
| | BLOCKS FOR THE ENGINEERING FIRM IS IN A DELINQUENT |
| | STATUS WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGUALTION. |
| | PLEASE UPDATE. |
| | FS 471.023 |
| | |
| | 3) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AS THIS |
| | AND THE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH |
| | REQUIRES PLANS TO BE SIGNED, DATED AND SEALED BY THE |
| | DESIGN PROFESSIONAL. |
| | PLEASE SEE SOME SHEETS CONTAIN SEAL BUT NO SIGNATURE |
| | AND DATE, MOST SHEETS ARE NOT DATED AS REQUIRED. |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | |
| | 4) NOTE: PLEASE SEE PLANS DOE NOT INDICATE ANY |
| | EMERGENCY AND EXIT LIGHTS AS REQUIRED PER FBC CHAPTER |
| | 10, AND NFPA-101 7.8, 7.9. |
| | PLEASE SEE 700.12F OF NFPA-70 FOR CIRCUITING REQUIRED. |
| | PLEASE KNOW THE BATHROOMS WHEN CONTAINING PARTITIONS |
| | AND NOT A SINGLE POINT OF USE WILL REQUIRE AN EMERGENCY |
| | BATTERY BACK UP FIXTURE OF SOME SORT. |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL. |
| | |
| | 5) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5 AND |
| | LOAD FOR THIS SAME SIGN CIRCUIT. |
| | |
| | 6) NOTE: PLEASE SHOW AND COMPLETE LOCATIONS OF ALL A/C |
| | SYSTEMS ON ELECTRICAL PLANS. |
| | IT IS BEING ASSUMED THESE UNITS ARE ROOFTOP PACKAGE |
| | UNITS ALTHOUGH THE MECHANICAL PLANS ARE NOT CLEAR. |
| | PLEASE SEE MISSING REQUIRED DISCONNECTS PER 440.11 AND |
| | MISSING GFI RECEPTACLES PER 210.63 AND 210.8B. |
| | |
| | 7) NOTE: PLEASE SEE THE RISER INDICATES MAIN AHEAD OF |
| | PANELS HOWEVER THE PLANS DO NOT INDICATE THESE FOR |
| | THEIR LOCATIONS. |
| | PLEASE KNOW THE SERVICE DISCONNECTING MEANS IS NOT |
| | COMPLETE AT THIS TIME ON PLANS. |
| | PLEASE KNOW THE LOCATION OF THE SERVICE DISCONNECTING |
| | MEANS NEEDS TO BE DETERMINED FOR LOCATION. |
| | PLEASE SEE NOTE BELOW WITH RESPECT TO THE PANEL |
| | LOCATIONS WHICH DOES NOT MEET CODE. |
| | 230.70, 230.71, 110.26 |
| | |
| | 8) NOTE: PLEASE SEE THE RISER IS NOT COMPLETE WITH THE |
| | SERVICE ENTRANCE CONDUCTORS, CONDUCTORS TO MAINS, |
| | CONDUCTORS FROM MAINS TO PANELS ETC. |
| | 240.4, 310.16 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SEE MISSING COMPLETED GROUNDING |
| | ELECTRODE SYSTEM PER 250.50. PLEASE KNOW THAT QUOTING |
| | THE CODE IN LIEU OF THE REQUIRED MINIMUM DETAIL IS NOT |
| | ACCEPTABLE. |
| | PLEASE ADJUST RISER. |
| | PLEASE ALSO SEE THAT THE SIZE OF THE GROUNDING |
| | ELECTRODE CONDUCTOR IS NOT LARGE ENOUGH AND NEEDS TO |
| | MEET THE MINIMUM SIZES PER 250.66. |
| | |
| | 10) NOTE: PLEASE SEE THE LOCATION OF THE PANEL(S) IN DJ |
| | BOOTH AREA DOES NOT MEET 110.26. IN FACT THERE IS A |
| | COUNTER BEING SHOWN DIRECTLY IN FRONT OF ONE OF THE |
| | PANELS WHICH IS STRICTLY PROHIBITED. |
| | PLEASE SEE NOTES ABOVE WITH RESPECT TO SERVICE, PANELS, |
| | OVER CURRENT PROTECTION AND LOCATIONS OF ALL SERVICE |
| | EQUIPMENT AND PANELS. |
| | PLEASE ADJUST AS REQUIRED. |
| | |
| | 11) NOTE: PLEASE CORRELATE RISER DIAGRAM AND PANELS. |
| | PLEASE SEE PANEL CH IS SHOWN AS 225AMP AND ALSO AS |
| | 200AMP ON PANEL SCHEDULE. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT INCLUDING MAINS PER 110.9. |
| | FBC 106.1.2 |
| | |
| | 13)NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE |
| | SUBMITTED. IF INSTALLING NEW AIR CONDITIONED SPACE, |
| | THEN THESE WILL BE REQUIRED. IF NO NEW A/C EQUIPMENT IS |
| | BEING INSTALLED, THEN PLEASE SUBMIT LIGHTING |
| | PERFORMANCE CALCULATIONS PER 13-415.2 |
| | |
| | 14) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS IN |
| | WHICH THE KVA LOAD SHOWN FAR EXCEEDS THE RATING OF THE |
| | BRANCH CIRCUIT AND BRANCH CIRCUIT OVER CURRENT |
| | PROTECTION. |
| | PLEASE SEE FOR EXAMPLE 3.2 KVA ON SINGLE POLE 20AMP |
| | BRANCH CIRCUIT.(MAX 1920VA) |
| | PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT |
| | 125%. |
| | PLEASE SEE 215.3, 230.42, 408.4, 240.4, 310.16 ETC |
| | PLEASE BE SURE TO ADJUST PANEL SCHEDULE FOR CIRCUITING |
| | AND LOADS. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 15) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH |
| | PANEL SCHEDULES. PLEASE SEE FOR EXAMPLE CIRCUITS: CHP-5 |
| | ON PLANS, YET THIS IS CHP-5,7 ON PANEL SCHEDULE. CHP-3 |
| | ON PLANS, YET PANEL SCHEDULE INDICATES THIS AS ONE OF |
| | THE AIR HANDLERS. PLANS DO NOT INDICATE THE AIR HANDLER |
| | UNDER THE BAR. |
| | PLEASE CORRELATE ALL AND ADJUST CIRCUITS TO ALL AREAS, |
| | EQUIPMENT AND SPECIFIC ROOMS. |
| | PLEASE SEE 2-POLE CIRCUITS ON PANELS YET SHOWN AS |
| | SINGLE POLE CIRCUITS ON PLANS. |
| | PLEASE SEE 408.4, 310.16, 240.4 AS CIRCUITS, |
| | CONDUCTORS, LOADS ETC NEED TO BE VERIFIED AND CAN NOT |
| | BE DONE AT THIS TIME. |
| | |
| | 16) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS PER |
| | NEC 220. |
| | PLEASE SEE 220.12, 220.14, 220.42, 220.44 FOR EXAMPLE. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 17) NOTE: PLEASE SEE PLANS MENTIONS THERE WILL BE A |
| | FIRE ALARM PANEL AND DEVICES BEING SUBMITTED AND DONE |
| | UNDER A SEPARATE PERMIT. THIS IS OK, HOWEVER PLEASE |
| | KNOW THE MINIMUM LOCATIONS AND LEVELS FOR ADA |
| | COMPLIANCE PER FBC CHAPTER 11 IS REQUIRED TO BE SHOWN |
| | ON THE BASE PLANS FOR MINIMUM DESIGN INTENT. |
| | PLEASE SE E11-4.28, .1, .2 AND .3(4). |
| | |
| | 18) NOTE: PLEASE CORRELATE THE ELECTRICAL EQUIPMENT |
| | SCHEDULE AND PANEL SCHEDULE(S). |
| | FOR EXAMPLE PLEASE SEE THE DISHWASHER WHICH IS SHOWN AS |
| | 208, 40MP AND 208/50AMP. |
| | |
| | 19) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE |
| | ONLY. ALL LOW VOLTAGE SYSTEMS SUCH AS PHONE, CATV, AND |
| | DATA ETC ARE REQUIRED TO BE UNDER SEPARATE PERMITS. |
| | THE PLANS MAY CONTAIN THIS LOW VOLTAGE INFORMATION AND |
| | ANY LV PERMIT APPLICATIONS MAY REFERENCE THE BASE PLANS |
| | ONCE ISSUED FOR PERMIT. |
| | ANY LOW VOLTAGE NOT INCLUDED ON BASE BUILD OUT PLANS |
| | WILL REQUIRE SEPARATE PLANS. |
| | IF THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS REVIEWER. |
| | |
| | 20) NOTE: PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH |
| | ARE NOT ON PLANS AT THIS TIME OR NEED TO BE REVISED OR |
| | CHANGED, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIM. |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |