Plan Review Notes
Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-25 12:36:04** DENIED**
  
  
  
 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 PLANS.
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE THE TOP OF397-001-C2 WHICH PRINTED THE
 LS CODE A EDITION 200. THIS SEEMS TO HAVE BEEN A
 MISPRINT.
  
 ** PLEASE SEE PLANS ALSO CALL FOR *PALM BEACH COUNTY
 AMENDMENTS* HOWEVER THIS PROJECT IS NOT LOCATED IN PALM
 BEACH COUNTY JURISDICTION. THIS IS LOCATED IN THE CITY
 OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE THE INFORMATION SHOWN ON TITLE
 BLOCKS FOR THE ENGINEERING FIRM IS IN A DELINQUENT
 STATUS WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGUALTION.
 PLEASE UPDATE.
 FS 471.023
  
 3) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AS THIS
 AND THE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH
 REQUIRES PLANS TO BE SIGNED, DATED AND SEALED BY THE
 DESIGN PROFESSIONAL.
 PLEASE SEE SOME SHEETS CONTAIN SEAL BUT NO SIGNATURE
 AND DATE, MOST SHEETS ARE NOT DATED AS REQUIRED.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 4) NOTE: PLEASE SEE PLANS DOE NOT INDICATE ANY
 EMERGENCY AND EXIT LIGHTS AS REQUIRED PER FBC CHAPTER
 10, AND NFPA-101 7.8, 7.9.
 PLEASE SEE 700.12F OF NFPA-70 FOR CIRCUITING REQUIRED.
 PLEASE KNOW THE BATHROOMS WHEN CONTAINING PARTITIONS
 AND NOT A SINGLE POINT OF USE WILL REQUIRE AN EMERGENCY
 BATTERY BACK UP FIXTURE OF SOME SORT.
 ** PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL.
  
 5) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5 AND
 LOAD FOR THIS SAME SIGN CIRCUIT.
  
 6) NOTE: PLEASE SHOW AND COMPLETE LOCATIONS OF ALL A/C
 SYSTEMS ON ELECTRICAL PLANS.
 IT IS BEING ASSUMED THESE UNITS ARE ROOFTOP PACKAGE
 UNITS ALTHOUGH THE MECHANICAL PLANS ARE NOT CLEAR.
 PLEASE SEE MISSING REQUIRED DISCONNECTS PER 440.11 AND
 MISSING GFI RECEPTACLES PER 210.63 AND 210.8B.
  
 7) NOTE: PLEASE SEE THE RISER INDICATES MAIN AHEAD OF
 PANELS HOWEVER THE PLANS DO NOT INDICATE THESE FOR
 THEIR LOCATIONS.
 PLEASE KNOW THE SERVICE DISCONNECTING MEANS IS NOT
 COMPLETE AT THIS TIME ON PLANS.
 PLEASE KNOW THE LOCATION OF THE SERVICE DISCONNECTING
 MEANS NEEDS TO BE DETERMINED FOR LOCATION.
 PLEASE SEE NOTE BELOW WITH RESPECT TO THE PANEL
 LOCATIONS WHICH DOES NOT MEET CODE.
 230.70, 230.71, 110.26
  
 8) NOTE: PLEASE SEE THE RISER IS NOT COMPLETE WITH THE
 SERVICE ENTRANCE CONDUCTORS, CONDUCTORS TO MAINS,
 CONDUCTORS FROM MAINS TO PANELS ETC.
 240.4, 310.16 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE MISSING COMPLETED GROUNDING
 ELECTRODE SYSTEM PER 250.50. PLEASE KNOW THAT QUOTING
 THE CODE IN LIEU OF THE REQUIRED MINIMUM DETAIL IS NOT
 ACCEPTABLE.
 PLEASE ADJUST RISER.
 PLEASE ALSO SEE THAT THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR IS NOT LARGE ENOUGH AND NEEDS TO
 MEET THE MINIMUM SIZES PER 250.66.
  
 10) NOTE: PLEASE SEE THE LOCATION OF THE PANEL(S) IN DJ
 BOOTH AREA DOES NOT MEET 110.26. IN FACT THERE IS A
 COUNTER BEING SHOWN DIRECTLY IN FRONT OF ONE OF THE
 PANELS WHICH IS STRICTLY PROHIBITED.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO SERVICE, PANELS,
 OVER CURRENT PROTECTION AND LOCATIONS OF ALL SERVICE
 EQUIPMENT AND PANELS.
 PLEASE ADJUST AS REQUIRED.
  
 11) NOTE: PLEASE CORRELATE RISER DIAGRAM AND PANELS.
 PLEASE SEE PANEL CH IS SHOWN AS 225AMP AND ALSO AS
 200AMP ON PANEL SCHEDULE.
 FBC 106.1.2 FOR COORDINATION.
  
 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT INCLUDING MAINS PER 110.9.
 FBC 106.1.2
  
 13)NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE
 SUBMITTED. IF INSTALLING NEW AIR CONDITIONED SPACE,
 THEN THESE WILL BE REQUIRED. IF NO NEW A/C EQUIPMENT IS
 BEING INSTALLED, THEN PLEASE SUBMIT LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2
  
 14) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS IN
 WHICH THE KVA LOAD SHOWN FAR EXCEEDS THE RATING OF THE
 BRANCH CIRCUIT AND BRANCH CIRCUIT OVER CURRENT
 PROTECTION.
 PLEASE SEE FOR EXAMPLE 3.2 KVA ON SINGLE POLE 20AMP
 BRANCH CIRCUIT.(MAX 1920VA)
 PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%.
 PLEASE SEE 215.3, 230.42, 408.4, 240.4, 310.16 ETC
 PLEASE BE SURE TO ADJUST PANEL SCHEDULE FOR CIRCUITING
 AND LOADS.
 FBC 106.1.2, 106.3.5.1.2
  
 15) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 PANEL SCHEDULES. PLEASE SEE FOR EXAMPLE CIRCUITS: CHP-5
 ON PLANS, YET THIS IS CHP-5,7 ON PANEL SCHEDULE. CHP-3
 ON PLANS, YET PANEL SCHEDULE INDICATES THIS AS ONE OF
 THE AIR HANDLERS. PLANS DO NOT INDICATE THE AIR HANDLER
 UNDER THE BAR.
 PLEASE CORRELATE ALL AND ADJUST CIRCUITS TO ALL AREAS,
 EQUIPMENT AND SPECIFIC ROOMS.
 PLEASE SEE 2-POLE CIRCUITS ON PANELS YET SHOWN AS
 SINGLE POLE CIRCUITS ON PLANS.
 PLEASE SEE 408.4, 310.16, 240.4 AS CIRCUITS,
 CONDUCTORS, LOADS ETC NEED TO BE VERIFIED AND CAN NOT
 BE DONE AT THIS TIME.
  
 16) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS PER
 NEC 220.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44 FOR EXAMPLE.
 FBC 106.3.5.1.2, 106.1.2
  
 17) NOTE: PLEASE SEE PLANS MENTIONS THERE WILL BE A
 FIRE ALARM PANEL AND DEVICES BEING SUBMITTED AND DONE
 UNDER A SEPARATE PERMIT. THIS IS OK, HOWEVER PLEASE
 KNOW THE MINIMUM LOCATIONS AND LEVELS FOR ADA
 COMPLIANCE PER FBC CHAPTER 11 IS REQUIRED TO BE SHOWN
 ON THE BASE PLANS FOR MINIMUM DESIGN INTENT.
 PLEASE SE E11-4.28, .1, .2 AND .3(4).
  
 18) NOTE: PLEASE CORRELATE THE ELECTRICAL EQUIPMENT
 SCHEDULE AND PANEL SCHEDULE(S).
 FOR EXAMPLE PLEASE SEE THE DISHWASHER WHICH IS SHOWN AS
 208, 40MP AND 208/50AMP.
  
 19) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE
 ONLY. ALL LOW VOLTAGE SYSTEMS SUCH AS PHONE, CATV, AND
 DATA ETC ARE REQUIRED TO BE UNDER SEPARATE PERMITS.
 THE PLANS MAY CONTAIN THIS LOW VOLTAGE INFORMATION AND
 ANY LV PERMIT APPLICATIONS MAY REFERENCE THE BASE PLANS
 ONCE ISSUED FOR PERMIT.
 ANY LOW VOLTAGE NOT INCLUDED ON BASE BUILD OUT PLANS
 WILL REQUIRE SEPARATE PLANS.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER.
  
 20) NOTE: PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH
 ARE NOT ON PLANS AT THIS TIME OR NEED TO BE REVISED OR
 CHANGED, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIM.
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  