Plan Review Notes
Plan Review Notes For Permit 07090045
Permit Number 07090045
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-03 18:57:25BUILDING PLAN REVIEW
 PERMIT: 07090045
 ADD: 114 S. NARCISSUS AVE
 CONT: YOUCHAK & YOUCHAK, INC.
 TEL: (561)832-3800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)FBC 3202.2DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOOR ON THE
 SOUTH ELEVATION CANNOT SWING OVER THE PROPERTY LINE.
  
 3)PER FBC TABLE 704.8 NO OPENINGS ARE PERMITTED IN
 WALLS 3 FEET OR LESS FROM THE PROPERTY LINE. FOR MORE
 INFORMATION SEE TABLE 602. INDICATE THE DISTANCE
 BETWEEN EACH PROPERTY LINE AT THE NORTH ELEVATION.
  
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2006 AND 2007 REVISIONS. THERE IS SOME INFORMATION ON
 SHEET C2 WHICH REFER TO THE PREVIOUS CODE E.G. ASCE
 7-98 WAS IN THE 2001 CODE SEE CHAPTER 35 FOR THE NEW
 REFERENCE STANDARDS. WE ARE USING THE CITY OF WEST PALM
 BEACH AMENDMENTS NOT PALM BEACH COUNTY AMENDMENTS.
 THERE IS NO TABLE 500 IN THE 2004 FBC.
  
 5)61G15-23.002 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER 471,
 F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET.
  
 6)FBC 1003.5.2 WHERE CHANGE IN ELEVATION OF 12 INCHES
 OR LESS OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED. THE RAMP SHALL BE IN CONFORMANCE WITH SECTION
 11-4.8.
  
 7)INDICATE THE CLEAR FLOOR SPACE ON THE DRAWINGS FOR
 THE HANDI-CAP LAVATORIES AND URINALS PER SEC 11-4.18
 AND 11-4.19.
  
 8)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 9)FBC 106.3.5.1.1 SUBMIT THE LIFE SAFETY PLAN
 INDICATING THE MEANS OF EGRESS, EXIT ACCESS, EXIT, EXIT
 DISCHARGE. THE EXTERIOR ELEVATIONS SHALL INCLUDE ALL
 STEPS, RAMPS AND LANDINGS LEADING TO OR FROM THE EGRESS
 DOORS.
  
 10)SHOW THE ACCESSIBLE ROUTE IN LEADING TO THE EXIT
 DOORS. SIGNS SHALL BE PLACE IN ACCORDANCE WITH SECTIONS
 11-4.30.6 / 11-4.1/ 11-4.3.
  
 11)FBC 11-5.2 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34 INCHES IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTER SHALL BE 60
 INCHES IN LENGTH AND COMPLY WITH SECTION 11-4.32 OR
 SERVICE TABLES SHALL BE AVAILABLE. THE HEIGHT AND KNEE
 CLEARANCES SHALL MEET THE REQUIREMENTS OF 11-4.32.2/
 11-4.32.3 AND 11-4.32.4
  
 12)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. THE PRODUCT
 APPROVALS SUBMITTED SHALL INDICATE WHICH ITEMS OR
 SYSTEMS WILL BE USED TO INSTALL THE PRODUCT. THE
 PRODUCT APPROVALS SHALL BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 NOTE: ANY ROOFING WORK WILL REQUIRE A ROOFING
 CONTRACTOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]