| Plan Review Notes For Permit 07090042 |
| Permit Number |
07090042 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-10-10 16:13:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME | | | FOR CONSISTENCY | | | | | | 2.) IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR | | | TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL | | | 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE | | | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE | | | PERMIT APPLICATION. | | | | | | PLEASE PROVIDE IMPACT FEE RECEIPT. THE BILL AND STAMPED | | | PLANS WERE PROVIDED, BUT A RECEIPT SHOWING THIS HAS | | | BEEN PAID MUST BE SUBMITTED (EITHER VIA FAX 805-6731 OR | | | EMAIL OR DELIVER TO FRONT COUNTER). | | | | | | PERMIT WILL BE ISSUED WITH PROVISOS: | | | | | | SEPARATE ROOF PERMIT REQUIRED | | | | | | SUBMIT PRODUCT APPROVAL FOR WINDSOR REPUBLIC DOORS, | | | SKYLIGHTS (-87PSF) AS A REVISION | | | | | | SUBMIT MECHANICAL EQUIPMENT ENGINEERING FBC1609 | | | | | | CORRELATE REFLECTED CEILING PLAN WITH ELECTRICAL | | | DRAWINGS PRIOR TO INSTALLATION | | | | | | |
|