| 2008-08-27 16:05:02 | |
| | |
| | |
| | |
| | |
| | ** TEMPORARY DENIED ** |
| | |
| | *** NOTE #1 NEEDS TO BE ADDRESSED AT THIS TIME. COMMENT |
| | #2 AND #3 CAN BE DONE AS A PROVISO. |
| | |
| | |
| | 1) NOTE: THE LETTER OF UNDERSTANDING FROM OWNER NEEDS |
| | TO BE SUBMITTED WITH REFERENCE TO THE 4X FEE WHICH WAS |
| | NOT PAID. THE LETTER IS TO ACKNOWLEDGE THE FEE AMOUNT |
| | AND UNDERSTAND THAT A HOLD WILL BE PLACED ON THE |
| | CERTIFICATE OF OCCUPANCY UNTIL FEE IS PAID IN FULL. FOR |
| | ANY TECHNICAL LEGAL QUESTIONS PLEASE CONTACT THE CITY |
| | ATTORNEY?S OFFICE. |
| | |
| | 2) NOTE: LOCATION OF UPS IN HALL WITH THE SIZE AS |
| | SPECIFIED ON THE MANUFACTURE CUT SHEETS NEEDS TO BE |
| | VERIFIED. IN FACT BASED ON THE UNIT SPEC SHEETS THE |
| | UNIT AS SUBMITTED IS TOO LARGE FOR LOCATION. |
| | PLEASE REVISE AND SUBMIT DOCUMENTS AS NEEDED. |
| | |
| | 2) NOTE: SHEETS E-7.0 AND E-8.0 CONTAIN THE NOTES FOR |
| | MINIMUM CD LEVELS FOR STROBE DEVICES TO MEET FBC |
| | 11-4.28.3(4) HOWEVER PLANS STILL SHOW SEVERAL STROBE |
| | LOCATIONS WITH CANDELA LEVELS BELOW THE MINIMUM OF 75. |
| | (MANY AT 15) |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |