Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop P
Sequence Number 3
Notes
Date Text
2008-06-04 14:50:20 
  
  
 PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P-14.0.
  
 REVISE CONDENSATE RISER C/1 TO SHOW RELIEF VENT LINE
 FOR CONDENSATE RISER AS INDICATED ON THE FLOOR PLAN.
 (SHT P-1.0).
  
 REVISE CONDENSATE RISER C/5 TO INCLUDE CONDENSATE FROM
 AHU-15 AS INDICATED ON THE FLOOR PLAN. (SHT P-3.0).
  