| Plan Review Notes For Permit 07090042 |
| Permit Number |
07090042 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-06-04 14:50:20 | | | | | | | | | | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P-14.0. | | | | | | REVISE CONDENSATE RISER C/1 TO SHOW RELIEF VENT LINE | | | FOR CONDENSATE RISER AS INDICATED ON THE FLOOR PLAN. | | | (SHT P-1.0). | | | | | | REVISE CONDENSATE RISER C/5 TO INCLUDE CONDENSATE FROM | | | AHU-15 AS INDICATED ON THE FLOOR PLAN. (SHT P-3.0). | | | |
|