Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop M
Sequence Number 3
Notes
Date Text
2008-06-03 16:06:46ALL PREVIOUS PLAN REVIEW COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED RELATED TO THE PLANS. PLANS HAVE BEEN STAMPED
 AS REVIEWED FOR CODE COMPLIANCE. THE FOLLOWING ISSUES
 ARE OUTSTANDING:
  
 1. THIS IS A THRESHOLD BUILDING AND AS SUCH, THREE
 COMPLETE SETS OF PLANS, SPECIFICATIONS AND SUBMITTALS
 ARE REQUIRED FOR PERMIT. PLEASE COLLATE AND SUBMIT
 THREE COMPLETE SETS OF ALL PERMIT DOCUMENTATION
 (INCLUDING PRODUCT APPROVALS, SUCH AS FOR THE
 PRE-ENGINEERED A/C STANDS) FOR PERMIT.
  
 2. THE WINDLOAD REPORT SUBMITTED BY THE MECHANICAL
 DESIGNER HAS NOT SUCCESSFULLY PASSED A BUILDING PLAN
 REVIEW. THE INFORMATION ON FANS, GRAVITY VENTS AND
 CONDENSING UNITS IS SUFFICIENT, BUT THERE ARE NOT THREE
 COPIES SUBMITTED. THE INFORMATION PROVIDED FOR THE
 ROOFTOP PACKAGE UNITS IS NOT ADEQUATE AS IT IS A REPORT
 FROM 1993. THERE HAVE BEEN MANY CHANGES TO THE CODES
 AND RELATED REFERENCE STANDARDS SINCE THAT TIME.
  
 BASED ON THE LANGUAGE IN FBCM 301.13, THE MANUFACTURER
 OF THE APPLIANCES, WHO IS RESPONSIBLE FOR THE DESIGN OF
 THE APPLIANCES, SHALL CERTIFY THAT THE APPLIANCES ARE
 DESIGNED TO WITHSTAND ANTICIPATED WIND PRESSURES IN
 ACCORDANCE WITH FBCB CHAPTER 16. ONCE THIS BECOMES THE
 ONLY OUTSTANDING ISSUE RELATED TO MECHANICAL. A PASSED
 STATUS WILL BE ENTERED AND THE MISSING WIND LOAD
 INFORMATION WILL BE COVERED IN A PROVISO IN ORDER TO
 ALLOW THE PROJECT TO MOVE FORWARD WHILE MISSING
 INFORMATION IS OBTAINED AND SUBMITTED.