| Plan Review Notes For Permit 07090042 |
| Permit Number |
07090042 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-06-04 14:56:45 | | | | | | | PASSED/PROVISO | | | | | | A REVISION IS REQUIRED FOR SHT P-11.0. | | | | | | SUBMIT A REVISION FOR THE GAS RISER DIAGRAM SHOWING THE | | | BRANCH LINE AND SHUT OFF VALVE FOR APPLIANCE INDICATED | | | AS OVEN UNIT NUMBER G3 AND DELETE SHUT OFF VALVE AND | | | UNION IN THE CEILING. | | | | | | THE MANUF. SPECIFICATION SHEETS FOR THE G3 OVEN AND THE | | | SECOND STAGE REGULATOR ARE REQUIRED AT THE TIME OF GAS | | | PERMIT APPLICATION. | | | | | | | | | | | | | | | . |
|