Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop E
Sequence Number 3
Notes
Date Text
2008-06-18 12:08:04** DENIED3RD REVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE TWO
 PREVIOUS REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SOME NEW COMMENTS DUE TO SOME CHANGES
 MADE TO PREVIOUS PLANS, DESIGN ETC.
  
 1) NOTE: THERE WAS A MEETING HELD AFTER THE LAST REVIEW
 IN WHICH THE LIGHTING CONTROL SYSTEM WAS GOING TO BE
 SUBSTANTIALLY CHANGED/REVISED. THIS REVIEWER MENTIONED
 TO POSSIBLY HAVE AN ADDITIONAL MEETING BEFORE PLANS
 WERE RESUBMITTED TO GO OVER ANY QUESTIONS FOR CHANGES
 WHICH WERE GOING TO BE MADE. NO CONTACT WAS MADE TO
 THIS REVIEWER. THE COMMENTS BELOW ARE BASED ON PLANS
 AND SUPPORTING REQUIRED DOCUMENTS WHICH DO NOT SHOW *
 MINIMUM* BUILDING CODE COMPLIANCE.
  
 ** THERE ARE EXTENSIVE EXAMPLES WHICH ARE LISTED BELOW
 UNDER NOTES. THESE ARE GIVEN AS A BENEFIT IN AN EFFORT
 FOR PLANS TO BE CORRECTED ON THE FOLLOWING REVIEW FOR
 PERMIT ISSUANCE. THE EXAMPLES ARE GIVEN AS A BENEFIT
 ONLY AND NOT AN EXHAUSTED LIST OF EVERY SPECIFIC ITEM.
 THE CODE SECTIONS ARE ONCE AGAIN GIVEN.
  
 2) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2, .1.3,
 13-400, 13-400.3.A, 13-415.2 ETC AS THE SUBMITTED
 ENERGY CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED
 PLANS. PLEASE SEE THERE SEVERAL LIGHTING FIXTURES,
 WATTAGES ETC ON PLANS WHICH ARE NOT SHOWN FOR THE
 CORRECT NUMBER OF FIXTURES, WATTAGES OF FIXTURES IN THE
 INPUT DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE
 REMAINDER OF THIS COMMENT.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURE M WHICH IS SHOWN FOR AN EXTERIOR
 LIGHT FIXTURE ON PLANS AT THE FRONT ENTRANCE AND ON THE
 FIXTURE LEGEND HOWEVER THESE ARE NOT SHOWN/LISTED ON
 THE IDR FOR EXTERIOR LIGHT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE PLANS WHICH SHOWS A TOTAL OF 50+ 35W
 FIXTURES WHICH ARE LABELED WITH DIFFERENT ALPHA
 DESIGNATIONS YET THE IDR ONLY SHOWS 22- TOTAL 35W
 FIXTURES. PLANS CLEARLY SHOW A SUBSTANTIALLY HIGHER
 AMOUNT OF FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE THE *H-1* FIXTURE SHOWN ON PLANS WHICH IS
 LISTED ON THE FIXTURE LEGEND AS 2-26W BULBS WHICH IS
 ABOUT 52WATTS/VA, YET THE IDR DOES NOT INCLUDE ANY 52W
 FIXTURES. THE CLOSEST WATTAGE OR VA LISTED IS NOTED AS
 THE STAIR FIXTURES. THE STAIR FIXTURES LISTED ON THE
 FIXTURE LEGEND ARE SHOWN AS 28W AND TWO IN EACH RAIL
 GIVES THE 56WATTS ALREADY ACCOUNTED FOR.
  
 ***** THIS IS ONLY A FEW EXAMPLES OF THE EXTERIOR
 LIGHTS SHOWN ON PLANS WHICH DO NOT COORDINATE WITH THE
 SUBMITTED ENERGY CALCULATIONS. THERE ARE OTHERS.
  
 PLEASE SEE THE SAME SECTIONS OF THE CODES ABOVE IN THIS
 SAME NOTE FOR ALL FIXTURES ON THE INTERIOR OF THE
 BUILDING WHICH IS REQUIRED TO BE PLACED INTO THE
 SUBMITTED IDR/ENERGY CALCULATIONS.
 SOME ADDITIONAL EXAMPLES OF FIXTURES ON THE INTERIOR
 LIGHTS WILL ALSO BE GIVEN AS A BENEFIT.
  
 FOR EXAMPLE:
 PLEASE SEE THE AREAS SUCH AS ROOM #100/SANCTUARY WHICH
 ARE STILL SHOWING FIXTURES WHICH ARE NOT LISTED ON THE
 IDR.
 PLEASE SEE THE TRACK LIGHTING FIXTURES WHICH BASED ON
 THE WATTAGE OF FIXTURE LEGEND IS NOT LISTED ON THE
 IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THE *G1* FIXTURES IN SAME ROOM #100 ARE NOT
 THE SAME AS ON IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE STILL LIGHTING FIXTURES SHOWN IN
 ROOM # 100 WHICH DO NOT DESIGNATIONS AND ARE NOT LISTED
 ON THE IDR. THE SYMBOL IS SHOWING THESE TO BE LIGHTING
 FIXTURES WHICH ARE A PENDANT TYPE BASED ON THE SYMBOL
 LEGEND. THERE IS ROUGHLY AN 11 OF THESE FIXTURES NOT
 ACCOUNTED FOR. PLEASE SEE COMMENTS WITH RESPECT TO
 CONTROLS.
  
 FOR EXAMPLE:
 PLEASE SEE AHU-1 ZONE. THESE FIXTURES ARE SHOWN IN THE
 IDR AS 71W YET THE PLANS DO NOT SHOW THESE SAME TYPES
 AND WATTAGES?
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURES SUCH AS Z-1 WHICH ARE NOT LISTED ON
 THE LEGEND WITH ANY TYPE OF WATTAGE OR ALLOWANCE.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURE *T* WHICH IS NOT LISTED WITH ANY
 WATTAGE. THIS CAN NOT BE CONFIRMED IN ZONE RTU3B. IN
 FACT THE PLANS CALL FOR *TBD* WHICH IS * TO BE
 DETERMINED*. THE MINIMUM CODE COMPLIANCE IS REQUIRED ON
 PLANS. FIXTURES DURING ANY PROJECT MAY BE REVISED. WHEN
 FIXTURES ARE REVISED PLANS ALONG WITH REVISED ENERGY
 CALCULATIONS ARE REQUIRED AND SUBMITTED BEFORE
 INSPECTIONS/FINALS. PLANS AND CALCULATIONS ARE REQUIRED
 TO SHOWN MINIMUM CODE COMPLIANCE BEFORE ISSUANCE.
  
 FOR EXAMPLE:
 PLEASE SEE PLANS SHOW *TT* FIXTURES IN RTU5 ZONE. AS
 THE FIXTURE LEGEND DOES NOT LIST ANY TYPE *TT* FIXTURE
 ON ELECTRICAL OR ARCHITECTURAL PLANS IT IS NOT KNOWN
 WHAT THESE ARE GOING TO BE? NEED TO COMPLETE MINIMUM AT
 THIS TIME.
  
 FOR EXAMPLE:
 PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT INCLUDE ANY
 *F1* FIXTURE AS SHOWN ON PLANS AND LISTED ON THE
 FIXTURE LEGEND.
  
 FOR EXAMPLE:
 PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT LIST ANY TYPE
 *C* FIXTURES WHICH ARE LISTED ON PLANS AND ON FIXTURE
 LEGEND.
  
 FOR EXAMPLE:
 PLEASE SEE THIS SAME ZONE RTU-5 WHICH SHOWS A TOTAL OF
 24-8A WATT *B* FIXTURES YET PLANS CLEARLY SHOW 32-84W
 FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE AHU11 WHICH SHOWS A 42W FIXTURE HOWEVER
 PLANS SHOW ALL 84 WATT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURES NOW ADDED IN CHAPEL NOT IN THE IDR.
 (A2)
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE SEVERAL FIXTURES LISTED ON PLANS
 YET THEY ARE NOT LISTED ON THE FIXTURE LEGEND WITH ANY
 TYPE OF WATTAGE. THESE ARE REQUIRED TO BE COMPLETE AT
 THIS TIME WITH MINIMUM DESIGN ALLOWANCES.
 SEE Z1, TT, T, ETC. SOME ALREADY NOTED ABOVE.
 SEE CHAPEL FOR SYMBOLS SHOWN BUT NOT ANY DESIGNATIONS.
  
 *** THESE ARE SOME EXAMPLES AS A BENEFIT TO THE DESIGN
 TEAM TO SEE THE TYPES OF ITEMS WHICH ARE STILL IN NEED
 OF CORRECTIONS. THIS IS IN NO WAY AN EXHAUSTED LIST. **
 THIS REVIEWER CAN NOT EMPHASIZE ENOUGH TO PLEASE BE
 SURE ALL COMPONENTS SHOWN AND LISTED IN BUILDING ARE
 PLACED INTO THE INPUT DATA REPORT. (IDR). THIS IS
 REQUIRED FOR ALL TRADE COMPONENTS.
 ****
 THERE WILL BE COMMENTS BELOW WHICH MAY VERY WELL AFFECT
 ENERGY CALCULATIONS.
  
 3) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW
 LIGHTING CONTROLS FOR ALL FIXTURES IN ALL AREAS ARE NOT
 SHOWN TO BE COMPLETE/COMPLIANT AT THIS TIME. PLEASE SEE
 13-415.1.ABC.1.1, .1.2, .1.3, AND .1.4.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURES AS NOTED ABOVE IN NOTES WHICH ARE
 LOCATED IN ROOM #100. THESE SHOW A NUMBER IN A ROUND
 CIRCLE HOWEVER THERE IS NOT LEGEND OR NOTES ON WHAT
 THESE NUMBERS REPRESENT. AS THE FIXTURES ARE NOT
 LABELED IT IS NOT POSSIBLE TO GIVE EXACT LOCATION.
 THESE ARE THE FIXTURES (BASED ON SYMBOL LEGEND) THAT
 HAVE THE CIRCLE NUMERICAL DESIGNATIONS, 10, 11, 13 AND
 14. THESE ARE NOTED AS PENDANT FIXTURES ON SYMBOL
 LEGEND. THERE ARE OTHER FIXTURES SUCH AS THE *G1* WHICH
 ARE SHOWING A FIXTURE DESIGNATION HOWEVER THE ONLY A
 NUMBER 12 IN A CIRCLE.
 PLEASE CLARIFY.
  
 FOR EXAMPLE:
 PLEASE SEE SOME OUTSIDE EXTERIOR LIGHTS WHICH ARE NOTED
 TO TIME CLOCK YET THE TIME CLOCK SCHEDULE DOES NOT LIST
 ANY OF THESE CIRCUITS. SEE THE TC SCHEDULE IS MISSING
 #22, #37.
  
 ** PLEASE SEE COMMENTS BELOW WITH RESPECT TO EGRESS
 LIGHTING WHICH WILL HAVE AN AFFECT ON CIRCUITING,
 LIGHTS ETC.
  
 4) NOTE: PLEASE SEE THERE ARE CIRCUITS LISTED ON THE
 PLANS TO NOW GO TO A NEW UPS FOR EMERGENCY BACK UP
 FIXTURES YET THE SCHEDULE SHOWN ON E-12.0 DOES NOT SHOW
 THESE FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE MISSING CIRCUITS, 1L3-1, 1L3-22 AND 1L3-37.
 THE PLANS SHOW LIGHT FIXTURES *H* AT FRONT ENTRANCE TO
 THIS UNIT, THE FIXTURES *H* AT REAR ENTRY/COVERED ARE
 ALSO BUT NOT LISTED.
  
 FOR EXAMPLE:
 PLEASE VERIFY FIXTURES *W-2* WHICH ARE LISTED AS THE
 WATER FEATURE LIGHTS ON THE UPS.
  
 NFPA-101 2003 7.8, 7.9,
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE MINIMUM
 LIFE SAFETY CODE HAS NOT BEEN SHOWN AT THIS TIME. THERE
 ARE ALSO SEVERAL COMMENTS WITH RESPECT TO COORDINATION
 OF PLANS.
 PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2. AS THE
 SUBMITTED PHOTO-METRICS DO NOT COORDINATE WITH PLANS IN
 MANY LOCATIONS THERE IS THE NEED FOR MANY ITEMS TO BE
 ADJUSTED AND REVISED.
  
 FOR EXAMPLE:
 PLEASE SEE ELECTRICAL LIGHTING PLANS CLEARLY SHOW
 FIXTURES A AND AE IN OUTSIDE CORRIDORS YET THE
 SUBMITTED PHOTO-METRICS CLEARLY DO NOT SHOW THESE SAME
 FIXTURES. IN FACT IN THE SOUTH OUTSIDE CORRIDORSHOWN
 ON THE PHOTO-METRICS SHOWS A EM-2 FIXTURE. THIS
 FIXTURES HAS A LISTED 2000 LUMENS ON PHOTO-METRIC
 SHEETS YET THE FIXTURES WHICH ARE ACTUALLY SHOWN ON
 PLANS ARE 1400 LUMEN FIXTURES. HOW IS THIS POSSIBLE?
  
 FOR EXAMPLE:
 PLEASE SEE PLATFORM EGRESS AREA ON THE EAST SIDE OF
 BUILDING WHICH BASED ON THE PHOTO-METRICS SHOWN ON
 SHEET E-16.0 IS BLANK.
  
 FOR EXAMPLE:
 PLEASE SEE AREAS SUCH AS ROOM 334 WHICH DOES NOT MATCH
 WITH ELECTRICAL PLANS.
  
 FOR EXAMPLE:
 PLEASE SEE LIBRARY WHICH SHOWS EMERGENCY FIXTURES ON
 ELECTRICAL BUT NOT THE SAME AS PHOTO-METRICS.
  
 FOR EXAMPLE:
 PLEASE SEE SEVERAL OF THE FIXTURE TYPES ON PHOTO-METRIC
 PLANS DO NOT CORRELATE WITH THE LIGHTING WHICH IS SHOWN
 ONE ELECTRICAL PLANS OR ELECTRICAL FIXTURE LEGEND.
 PLEASE ALSO SEE FIXTURE HR AS LISTED ON PHOTO-METRICS
 YET THIS FIXTURE IS NOT LISTED ON ELECTRICAL PLANS
 FIXTURE LEGEND OR SHOWN ON PLANS.
 PLEASE SEE SITE PLANS WHICH SHOW COMPLETELY DIFFERENT
 FIXTURES THAN ON FIXTURE LEGEND FOR THE SAME FIXTURES.
  
 PLEASE BE SURE TO COORDINATE ALL FIXTURES ON SITE PLAN
 AS LISTED, ELECTRICAL PLANS AND PHOTO-METRICS.
  
 ** AS SOME AREAS ARE NOT COMPLETE, NOT SAME FIXTURES,
 SAME WATTAGE, LEVELS ETC COMPLIANCE HAS NOT BEEN
 SHOWN.
  
 6) NOTE: PLEASE SEE CIRCUITS ON E-4.0 WHICH SHOWS FRONT
 DOOR J-BOXES WITH P1-22,24 AND 26, YET THE PANEL
 SCHEDULE FOR P1 SHOWS OTHER LOCATIONS AND CIRCUITS
 BEING SERVED.
  
 7) NOTE: THE RISER NOW SHOWS TWO NEW MAINS INSTEAD OF
 THE PREVIOUS MLO MAIN DISTRIBUTION BOARD. PLEASE BE
 SURE TO SHOW A BOND FROM EACH MAIN ON RISER TO EACH
 GROUNDING ELECTRODE AS SHOWN. 250.58
  
 8) NOTE: AS THE RISER HAS NOW BEEN REVISED TO SHOW TO
 MAINS INSIDE BUILDING. PLEASE SEE THE SITE ELECTRICAL
 PLANS E-000 IS STILL SHOWING A MAIN OUTSIDE.
  
 9) NOTE: PLEASE SEE REVISED LAYOUT OF LIGHTING ON E-6.0
 IS NOT THE SAME AS E-3.0.
 PLEASE ALSO SEE THE ARCHITECTURAL PLANS WHICH ARE ALSO
 REQUIRED TO SHOW MINIMUM LIGHTING FOR LIFE SAFETY CODE/
 NFPA-101 2003 DO NOT CORRELATE WITH THE ELECTRICAL
 PLANS.
  
 FOR EXAMPLE:
 IN FACT PLEASE SEE SHEET A-3.0 FOR EXAMPLE WHICH DOES
 NOT SHOW ANY EMERGENCY EGRESS LIGHTS IN ROOM #100. THIS
 ROOM ON THE ELECTRICAL PLANS HAS SEVERAL EMERGENCY
 LIGHTS WHICH ARE SHOWN.
  
 FOR EXAMPLE:
 PLEASE SEE ROOM #105 WHICH DOES NOT SHOW ANY EMERGENCY
 LIGHT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE THE OUTSIDE CORRIDORS, LIBRARY, ETC. THESE
 ARE SOME EXAMPLES, BUT THERE ARE TOO NUMEROUS TO LIST.
  
 ** IT IS IMPORTANT TO KNOW THE LIGHTING REQUIRED TO BE
 SHOWN BY THE ARCHITECT FOR LIFE SAFETY PLANS NEED TO
 COORDINATE. THESE CORRECTIONS ARE REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY ANY OTHER TRADE OR REVIEWER.
 PLEASE ALSO KNOW EVEN IF ANY OF THESE SHEETS CONTAIN
 STAMPS FROM OTHER TRADES, THEY NEED TO BE REVISED AND
 CORRECTED.
  
 10) NOTE: PLEASE BE SURE TO SUBMIT THREE COMPLETE SETS,
 SIGNED DATED AND SEALED BY THE DESIGNERS OF RECORD AS
 REQUIRED BY FAC 61G15-23.002. IT HAS NO BEARING ON
 WHETHER OR NOT THE SET IS THE PLANS WHICH REMAIN ON
 FILE. THE FLORIDA ADMINISTRATIVE CODE SECTION GIVEN
 REQUIRES ALL SETS AND DOCUMENTS DONE BY ANY LICENSED
 PROFESSIONAL ENGINEER TO CONTAIN AN ORIGINAL SIGNATURE
 DATE AND RAISED SEAL.
 PLEASE SEE SHEET(S) WHICH ARE IN FACT PHOTO-COPIES OF
 SIGNED AND SEALED PLANS WHICH ARE IN ONE OF THESE SETS
 SUBMITTED.
 PLEASE BE SURE TO GO THROUGH ALL SHEETS, PLANS AND
 DOCUMENTS.
  
 11) NOTE: PLEASE TAKE A LOOK AT THE SIZE AND SPECS FOR
 THE NEW UPS FOR EMERGENCY LIGHT FIXTURES WHICH IS BEING
 SHOWN TO BE INSTALLED FLASH INSIDE THE CORRIDOR WALL.
 PLEASE BE SURE THIS CAN BE INSTALLED INSIDE THE WALL AS
 SHOWN WITH TEMPERATURE AND HEAT CONSIDERATIONS PER
 LISTING.
 PLEASE ALSO SEE THE DIMENSIONS APPEAR TO BE LARGER THAN
 THE AREA IN WHICH IS SHOWN ON PLANS.
 THIS IS NOT SOMETHING THAT WANTS TO BE FOUND OUT AT A
 LATER DATE CAUSING WALLS ETC TO BE MOVED OR
 RE-DESIGNED. IF THIS IS VERIFIED THEN WILL BE AN
 ON-SITE ITEM. THIS IS ONLY NOTED FOR LISTING,
 INSTALLATION ETC AT THIS TIME.
 110.3,90.7.
  
 12) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO AIC
 RATING HAS PANELS AND RISER NOW REVISED SHOWING RATINGS
 FOR PANELS AND BRANCH BREAKERS. ALL BRANCH BREAKERS
 SHOWN WITH 42K RATING.
 NO RESPONSE NEEDED.
  
 13) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. THE SECOND REVIEW THE
 SECTION OF THE STATUTE WAS GIVEN AS THERE WERE CODE
 SECTIONS REPEATED FOR THE SAME CODE COMPLIANCE REQUIRED
 ON PLANS AND SUPPORTING DOCUMENTS. THERE WERE ONCE
 AGAIN REPEATED CODE SECTIONS NOT IN COMPLIANCE. PLEASE
 KNOW AS REQUIRED UNDER THE ABOVE STATUE AS GIVEN THE
 FEE OF FOUR TIMES THE PERMIT FEE ATTRIBUTED TO PLAN
 REVIEW HAS BEEN ASSESSED. THIS FEE IS ASSESSED UNDER A
 STATUTORY REQUIREMENT AND IS NOT A REQUIRED FEE ON A
 LOCAL LEVEL. THE FLORIDA STATUTES ALSO REQUIRES THIS
 FEE TO BE PAID BEFORE PLANS ARE TO BE RESUBMITTED.THE
 FEE WHICH IS NOW ASSESSED AND REQUIRED TO BE PAID IS
 $46,097.90.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND
 SUPPORTING ENERGY CALCULATIONS WILL BE RETAINED BY THIS
 OFFICE AND PLACED WITH PREVIOUS RETAINED PLANS.
 ** IT IS RECOMMENDED THAT A MEETING BE HELD TO GO OVER
 COMMENTS BEFORE PLANS ARE RESUBMITTED FOR THE FOURTH
 REVIEW.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]