| 2008-06-18 12:08:04 | ** DENIED3RD REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE TWO |
| | PREVIOUS REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING. |
| | THERE ARE ALSO SOME NEW COMMENTS DUE TO SOME CHANGES |
| | MADE TO PREVIOUS PLANS, DESIGN ETC. |
| | |
| | 1) NOTE: THERE WAS A MEETING HELD AFTER THE LAST REVIEW |
| | IN WHICH THE LIGHTING CONTROL SYSTEM WAS GOING TO BE |
| | SUBSTANTIALLY CHANGED/REVISED. THIS REVIEWER MENTIONED |
| | TO POSSIBLY HAVE AN ADDITIONAL MEETING BEFORE PLANS |
| | WERE RESUBMITTED TO GO OVER ANY QUESTIONS FOR CHANGES |
| | WHICH WERE GOING TO BE MADE. NO CONTACT WAS MADE TO |
| | THIS REVIEWER. THE COMMENTS BELOW ARE BASED ON PLANS |
| | AND SUPPORTING REQUIRED DOCUMENTS WHICH DO NOT SHOW * |
| | MINIMUM* BUILDING CODE COMPLIANCE. |
| | |
| | ** THERE ARE EXTENSIVE EXAMPLES WHICH ARE LISTED BELOW |
| | UNDER NOTES. THESE ARE GIVEN AS A BENEFIT IN AN EFFORT |
| | FOR PLANS TO BE CORRECTED ON THE FOLLOWING REVIEW FOR |
| | PERMIT ISSUANCE. THE EXAMPLES ARE GIVEN AS A BENEFIT |
| | ONLY AND NOT AN EXHAUSTED LIST OF EVERY SPECIFIC ITEM. |
| | THE CODE SECTIONS ARE ONCE AGAIN GIVEN. |
| | |
| | 2) NOTE: PLEASE SEE FBC 13-415.2.ABC.1.1, .1.2, .1.3, |
| | 13-400, 13-400.3.A, 13-415.2 ETC AS THE SUBMITTED |
| | ENERGY CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED |
| | PLANS. PLEASE SEE THERE SEVERAL LIGHTING FIXTURES, |
| | WATTAGES ETC ON PLANS WHICH ARE NOT SHOWN FOR THE |
| | CORRECT NUMBER OF FIXTURES, WATTAGES OF FIXTURES IN THE |
| | INPUT DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS. |
| | THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE |
| | REMAINDER OF THIS COMMENT. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE FIXTURE M WHICH IS SHOWN FOR AN EXTERIOR |
| | LIGHT FIXTURE ON PLANS AT THE FRONT ENTRANCE AND ON THE |
| | FIXTURE LEGEND HOWEVER THESE ARE NOT SHOWN/LISTED ON |
| | THE IDR FOR EXTERIOR LIGHT FIXTURES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE PLANS WHICH SHOWS A TOTAL OF 50+ 35W |
| | FIXTURES WHICH ARE LABELED WITH DIFFERENT ALPHA |
| | DESIGNATIONS YET THE IDR ONLY SHOWS 22- TOTAL 35W |
| | FIXTURES. PLANS CLEARLY SHOW A SUBSTANTIALLY HIGHER |
| | AMOUNT OF FIXTURES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE *H-1* FIXTURE SHOWN ON PLANS WHICH IS |
| | LISTED ON THE FIXTURE LEGEND AS 2-26W BULBS WHICH IS |
| | ABOUT 52WATTS/VA, YET THE IDR DOES NOT INCLUDE ANY 52W |
| | FIXTURES. THE CLOSEST WATTAGE OR VA LISTED IS NOTED AS |
| | THE STAIR FIXTURES. THE STAIR FIXTURES LISTED ON THE |
| | FIXTURE LEGEND ARE SHOWN AS 28W AND TWO IN EACH RAIL |
| | GIVES THE 56WATTS ALREADY ACCOUNTED FOR. |
| | |
| | ***** THIS IS ONLY A FEW EXAMPLES OF THE EXTERIOR |
| | LIGHTS SHOWN ON PLANS WHICH DO NOT COORDINATE WITH THE |
| | SUBMITTED ENERGY CALCULATIONS. THERE ARE OTHERS. |
| | |
| | PLEASE SEE THE SAME SECTIONS OF THE CODES ABOVE IN THIS |
| | SAME NOTE FOR ALL FIXTURES ON THE INTERIOR OF THE |
| | BUILDING WHICH IS REQUIRED TO BE PLACED INTO THE |
| | SUBMITTED IDR/ENERGY CALCULATIONS. |
| | SOME ADDITIONAL EXAMPLES OF FIXTURES ON THE INTERIOR |
| | LIGHTS WILL ALSO BE GIVEN AS A BENEFIT. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE AREAS SUCH AS ROOM #100/SANCTUARY WHICH |
| | ARE STILL SHOWING FIXTURES WHICH ARE NOT LISTED ON THE |
| | IDR. |
| | PLEASE SEE THE TRACK LIGHTING FIXTURES WHICH BASED ON |
| | THE WATTAGE OF FIXTURE LEGEND IS NOT LISTED ON THE |
| | IDR. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE *G1* FIXTURES IN SAME ROOM #100 ARE NOT |
| | THE SAME AS ON IDR. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THERE ARE STILL LIGHTING FIXTURES SHOWN IN |
| | ROOM # 100 WHICH DO NOT DESIGNATIONS AND ARE NOT LISTED |
| | ON THE IDR. THE SYMBOL IS SHOWING THESE TO BE LIGHTING |
| | FIXTURES WHICH ARE A PENDANT TYPE BASED ON THE SYMBOL |
| | LEGEND. THERE IS ROUGHLY AN 11 OF THESE FIXTURES NOT |
| | ACCOUNTED FOR. PLEASE SEE COMMENTS WITH RESPECT TO |
| | CONTROLS. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE AHU-1 ZONE. THESE FIXTURES ARE SHOWN IN THE |
| | IDR AS 71W YET THE PLANS DO NOT SHOW THESE SAME TYPES |
| | AND WATTAGES? |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE FIXTURES SUCH AS Z-1 WHICH ARE NOT LISTED ON |
| | THE LEGEND WITH ANY TYPE OF WATTAGE OR ALLOWANCE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE FIXTURE *T* WHICH IS NOT LISTED WITH ANY |
| | WATTAGE. THIS CAN NOT BE CONFIRMED IN ZONE RTU3B. IN |
| | FACT THE PLANS CALL FOR *TBD* WHICH IS * TO BE |
| | DETERMINED*. THE MINIMUM CODE COMPLIANCE IS REQUIRED ON |
| | PLANS. FIXTURES DURING ANY PROJECT MAY BE REVISED. WHEN |
| | FIXTURES ARE REVISED PLANS ALONG WITH REVISED ENERGY |
| | CALCULATIONS ARE REQUIRED AND SUBMITTED BEFORE |
| | INSPECTIONS/FINALS. PLANS AND CALCULATIONS ARE REQUIRED |
| | TO SHOWN MINIMUM CODE COMPLIANCE BEFORE ISSUANCE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE PLANS SHOW *TT* FIXTURES IN RTU5 ZONE. AS |
| | THE FIXTURE LEGEND DOES NOT LIST ANY TYPE *TT* FIXTURE |
| | ON ELECTRICAL OR ARCHITECTURAL PLANS IT IS NOT KNOWN |
| | WHAT THESE ARE GOING TO BE? NEED TO COMPLETE MINIMUM AT |
| | THIS TIME. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT INCLUDE ANY |
| | *F1* FIXTURE AS SHOWN ON PLANS AND LISTED ON THE |
| | FIXTURE LEGEND. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE SAME ZONE RTU-5 WHICH DOES NOT LIST ANY TYPE |
| | *C* FIXTURES WHICH ARE LISTED ON PLANS AND ON FIXTURE |
| | LEGEND. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THIS SAME ZONE RTU-5 WHICH SHOWS A TOTAL OF |
| | 24-8A WATT *B* FIXTURES YET PLANS CLEARLY SHOW 32-84W |
| | FIXTURES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE AHU11 WHICH SHOWS A 42W FIXTURE HOWEVER |
| | PLANS SHOW ALL 84 WATT FIXTURES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE FIXTURES NOW ADDED IN CHAPEL NOT IN THE IDR. |
| | (A2) |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THERE ARE SEVERAL FIXTURES LISTED ON PLANS |
| | YET THEY ARE NOT LISTED ON THE FIXTURE LEGEND WITH ANY |
| | TYPE OF WATTAGE. THESE ARE REQUIRED TO BE COMPLETE AT |
| | THIS TIME WITH MINIMUM DESIGN ALLOWANCES. |
| | SEE Z1, TT, T, ETC. SOME ALREADY NOTED ABOVE. |
| | SEE CHAPEL FOR SYMBOLS SHOWN BUT NOT ANY DESIGNATIONS. |
| | |
| | *** THESE ARE SOME EXAMPLES AS A BENEFIT TO THE DESIGN |
| | TEAM TO SEE THE TYPES OF ITEMS WHICH ARE STILL IN NEED |
| | OF CORRECTIONS. THIS IS IN NO WAY AN EXHAUSTED LIST. ** |
| | THIS REVIEWER CAN NOT EMPHASIZE ENOUGH TO PLEASE BE |
| | SURE ALL COMPONENTS SHOWN AND LISTED IN BUILDING ARE |
| | PLACED INTO THE INPUT DATA REPORT. (IDR). THIS IS |
| | REQUIRED FOR ALL TRADE COMPONENTS. |
| | **** |
| | THERE WILL BE COMMENTS BELOW WHICH MAY VERY WELL AFFECT |
| | ENERGY CALCULATIONS. |
| | |
| | 3) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW |
| | LIGHTING CONTROLS FOR ALL FIXTURES IN ALL AREAS ARE NOT |
| | SHOWN TO BE COMPLETE/COMPLIANT AT THIS TIME. PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2, .1.3, AND .1.4. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE FIXTURES AS NOTED ABOVE IN NOTES WHICH ARE |
| | LOCATED IN ROOM #100. THESE SHOW A NUMBER IN A ROUND |
| | CIRCLE HOWEVER THERE IS NOT LEGEND OR NOTES ON WHAT |
| | THESE NUMBERS REPRESENT. AS THE FIXTURES ARE NOT |
| | LABELED IT IS NOT POSSIBLE TO GIVE EXACT LOCATION. |
| | THESE ARE THE FIXTURES (BASED ON SYMBOL LEGEND) THAT |
| | HAVE THE CIRCLE NUMERICAL DESIGNATIONS, 10, 11, 13 AND |
| | 14. THESE ARE NOTED AS PENDANT FIXTURES ON SYMBOL |
| | LEGEND. THERE ARE OTHER FIXTURES SUCH AS THE *G1* WHICH |
| | ARE SHOWING A FIXTURE DESIGNATION HOWEVER THE ONLY A |
| | NUMBER 12 IN A CIRCLE. |
| | PLEASE CLARIFY. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE SOME OUTSIDE EXTERIOR LIGHTS WHICH ARE NOTED |
| | TO TIME CLOCK YET THE TIME CLOCK SCHEDULE DOES NOT LIST |
| | ANY OF THESE CIRCUITS. SEE THE TC SCHEDULE IS MISSING |
| | #22, #37. |
| | |
| | ** PLEASE SEE COMMENTS BELOW WITH RESPECT TO EGRESS |
| | LIGHTING WHICH WILL HAVE AN AFFECT ON CIRCUITING, |
| | LIGHTS ETC. |
| | |
| | 4) NOTE: PLEASE SEE THERE ARE CIRCUITS LISTED ON THE |
| | PLANS TO NOW GO TO A NEW UPS FOR EMERGENCY BACK UP |
| | FIXTURES YET THE SCHEDULE SHOWN ON E-12.0 DOES NOT SHOW |
| | THESE FIXTURES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE MISSING CIRCUITS, 1L3-1, 1L3-22 AND 1L3-37. |
| | THE PLANS SHOW LIGHT FIXTURES *H* AT FRONT ENTRANCE TO |
| | THIS UNIT, THE FIXTURES *H* AT REAR ENTRY/COVERED ARE |
| | ALSO BUT NOT LISTED. |
| | |
| | FOR EXAMPLE: |
| | PLEASE VERIFY FIXTURES *W-2* WHICH ARE LISTED AS THE |
| | WATER FEATURE LIGHTS ON THE UPS. |
| | |
| | NFPA-101 2003 7.8, 7.9, |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 5) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE MINIMUM |
| | LIFE SAFETY CODE HAS NOT BEEN SHOWN AT THIS TIME. THERE |
| | ARE ALSO SEVERAL COMMENTS WITH RESPECT TO COORDINATION |
| | OF PLANS. |
| | PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2. AS THE |
| | SUBMITTED PHOTO-METRICS DO NOT COORDINATE WITH PLANS IN |
| | MANY LOCATIONS THERE IS THE NEED FOR MANY ITEMS TO BE |
| | ADJUSTED AND REVISED. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE ELECTRICAL LIGHTING PLANS CLEARLY SHOW |
| | FIXTURES A AND AE IN OUTSIDE CORRIDORS YET THE |
| | SUBMITTED PHOTO-METRICS CLEARLY DO NOT SHOW THESE SAME |
| | FIXTURES. IN FACT IN THE SOUTH OUTSIDE CORRIDORSHOWN |
| | ON THE PHOTO-METRICS SHOWS A EM-2 FIXTURE. THIS |
| | FIXTURES HAS A LISTED 2000 LUMENS ON PHOTO-METRIC |
| | SHEETS YET THE FIXTURES WHICH ARE ACTUALLY SHOWN ON |
| | PLANS ARE 1400 LUMEN FIXTURES. HOW IS THIS POSSIBLE? |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE PLATFORM EGRESS AREA ON THE EAST SIDE OF |
| | BUILDING WHICH BASED ON THE PHOTO-METRICS SHOWN ON |
| | SHEET E-16.0 IS BLANK. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE AREAS SUCH AS ROOM 334 WHICH DOES NOT MATCH |
| | WITH ELECTRICAL PLANS. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE LIBRARY WHICH SHOWS EMERGENCY FIXTURES ON |
| | ELECTRICAL BUT NOT THE SAME AS PHOTO-METRICS. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE SEVERAL OF THE FIXTURE TYPES ON PHOTO-METRIC |
| | PLANS DO NOT CORRELATE WITH THE LIGHTING WHICH IS SHOWN |
| | ONE ELECTRICAL PLANS OR ELECTRICAL FIXTURE LEGEND. |
| | PLEASE ALSO SEE FIXTURE HR AS LISTED ON PHOTO-METRICS |
| | YET THIS FIXTURE IS NOT LISTED ON ELECTRICAL PLANS |
| | FIXTURE LEGEND OR SHOWN ON PLANS. |
| | PLEASE SEE SITE PLANS WHICH SHOW COMPLETELY DIFFERENT |
| | FIXTURES THAN ON FIXTURE LEGEND FOR THE SAME FIXTURES. |
| | |
| | PLEASE BE SURE TO COORDINATE ALL FIXTURES ON SITE PLAN |
| | AS LISTED, ELECTRICAL PLANS AND PHOTO-METRICS. |
| | |
| | ** AS SOME AREAS ARE NOT COMPLETE, NOT SAME FIXTURES, |
| | SAME WATTAGE, LEVELS ETC COMPLIANCE HAS NOT BEEN |
| | SHOWN. |
| | |
| | 6) NOTE: PLEASE SEE CIRCUITS ON E-4.0 WHICH SHOWS FRONT |
| | DOOR J-BOXES WITH P1-22,24 AND 26, YET THE PANEL |
| | SCHEDULE FOR P1 SHOWS OTHER LOCATIONS AND CIRCUITS |
| | BEING SERVED. |
| | |
| | 7) NOTE: THE RISER NOW SHOWS TWO NEW MAINS INSTEAD OF |
| | THE PREVIOUS MLO MAIN DISTRIBUTION BOARD. PLEASE BE |
| | SURE TO SHOW A BOND FROM EACH MAIN ON RISER TO EACH |
| | GROUNDING ELECTRODE AS SHOWN. 250.58 |
| | |
| | 8) NOTE: AS THE RISER HAS NOW BEEN REVISED TO SHOW TO |
| | MAINS INSIDE BUILDING. PLEASE SEE THE SITE ELECTRICAL |
| | PLANS E-000 IS STILL SHOWING A MAIN OUTSIDE. |
| | |
| | 9) NOTE: PLEASE SEE REVISED LAYOUT OF LIGHTING ON E-6.0 |
| | IS NOT THE SAME AS E-3.0. |
| | PLEASE ALSO SEE THE ARCHITECTURAL PLANS WHICH ARE ALSO |
| | REQUIRED TO SHOW MINIMUM LIGHTING FOR LIFE SAFETY CODE/ |
| | NFPA-101 2003 DO NOT CORRELATE WITH THE ELECTRICAL |
| | PLANS. |
| | |
| | FOR EXAMPLE: |
| | IN FACT PLEASE SEE SHEET A-3.0 FOR EXAMPLE WHICH DOES |
| | NOT SHOW ANY EMERGENCY EGRESS LIGHTS IN ROOM #100. THIS |
| | ROOM ON THE ELECTRICAL PLANS HAS SEVERAL EMERGENCY |
| | LIGHTS WHICH ARE SHOWN. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE ROOM #105 WHICH DOES NOT SHOW ANY EMERGENCY |
| | LIGHT FIXTURES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE OUTSIDE CORRIDORS, LIBRARY, ETC. THESE |
| | ARE SOME EXAMPLES, BUT THERE ARE TOO NUMEROUS TO LIST. |
| | |
| | ** IT IS IMPORTANT TO KNOW THE LIGHTING REQUIRED TO BE |
| | SHOWN BY THE ARCHITECT FOR LIFE SAFETY PLANS NEED TO |
| | COORDINATE. THESE CORRECTIONS ARE REQUIRED WHETHER OR |
| | NOT COMMENT IS MADE BY ANY OTHER TRADE OR REVIEWER. |
| | PLEASE ALSO KNOW EVEN IF ANY OF THESE SHEETS CONTAIN |
| | STAMPS FROM OTHER TRADES, THEY NEED TO BE REVISED AND |
| | CORRECTED. |
| | |
| | 10) NOTE: PLEASE BE SURE TO SUBMIT THREE COMPLETE SETS, |
| | SIGNED DATED AND SEALED BY THE DESIGNERS OF RECORD AS |
| | REQUIRED BY FAC 61G15-23.002. IT HAS NO BEARING ON |
| | WHETHER OR NOT THE SET IS THE PLANS WHICH REMAIN ON |
| | FILE. THE FLORIDA ADMINISTRATIVE CODE SECTION GIVEN |
| | REQUIRES ALL SETS AND DOCUMENTS DONE BY ANY LICENSED |
| | PROFESSIONAL ENGINEER TO CONTAIN AN ORIGINAL SIGNATURE |
| | DATE AND RAISED SEAL. |
| | PLEASE SEE SHEET(S) WHICH ARE IN FACT PHOTO-COPIES OF |
| | SIGNED AND SEALED PLANS WHICH ARE IN ONE OF THESE SETS |
| | SUBMITTED. |
| | PLEASE BE SURE TO GO THROUGH ALL SHEETS, PLANS AND |
| | DOCUMENTS. |
| | |
| | 11) NOTE: PLEASE TAKE A LOOK AT THE SIZE AND SPECS FOR |
| | THE NEW UPS FOR EMERGENCY LIGHT FIXTURES WHICH IS BEING |
| | SHOWN TO BE INSTALLED FLASH INSIDE THE CORRIDOR WALL. |
| | PLEASE BE SURE THIS CAN BE INSTALLED INSIDE THE WALL AS |
| | SHOWN WITH TEMPERATURE AND HEAT CONSIDERATIONS PER |
| | LISTING. |
| | PLEASE ALSO SEE THE DIMENSIONS APPEAR TO BE LARGER THAN |
| | THE AREA IN WHICH IS SHOWN ON PLANS. |
| | THIS IS NOT SOMETHING THAT WANTS TO BE FOUND OUT AT A |
| | LATER DATE CAUSING WALLS ETC TO BE MOVED OR |
| | RE-DESIGNED. IF THIS IS VERIFIED THEN WILL BE AN |
| | ON-SITE ITEM. THIS IS ONLY NOTED FOR LISTING, |
| | INSTALLATION ETC AT THIS TIME. |
| | 110.3,90.7. |
| | |
| | 12) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO AIC |
| | RATING HAS PANELS AND RISER NOW REVISED SHOWING RATINGS |
| | FOR PANELS AND BRANCH BREAKERS. ALL BRANCH BREAKERS |
| | SHOWN WITH 42K RATING. |
| | NO RESPONSE NEEDED. |
| | |
| | 13) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO |
| | FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. THE SECOND REVIEW THE |
| | SECTION OF THE STATUTE WAS GIVEN AS THERE WERE CODE |
| | SECTIONS REPEATED FOR THE SAME CODE COMPLIANCE REQUIRED |
| | ON PLANS AND SUPPORTING DOCUMENTS. THERE WERE ONCE |
| | AGAIN REPEATED CODE SECTIONS NOT IN COMPLIANCE. PLEASE |
| | KNOW AS REQUIRED UNDER THE ABOVE STATUE AS GIVEN THE |
| | FEE OF FOUR TIMES THE PERMIT FEE ATTRIBUTED TO PLAN |
| | REVIEW HAS BEEN ASSESSED. THIS FEE IS ASSESSED UNDER A |
| | STATUTORY REQUIREMENT AND IS NOT A REQUIRED FEE ON A |
| | LOCAL LEVEL. THE FLORIDA STATUTES ALSO REQUIRES THIS |
| | FEE TO BE PAID BEFORE PLANS ARE TO BE RESUBMITTED.THE |
| | FEE WHICH IS NOW ASSESSED AND REQUIRED TO BE PAID IS |
| | $46,097.90. |
| | ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND |
| | SUPPORTING ENERGY CALCULATIONS WILL BE RETAINED BY THIS |
| | OFFICE AND PLACED WITH PREVIOUS RETAINED PLANS. |
| | ** IT IS RECOMMENDED THAT A MEETING BE HELD TO GO OVER |
| | COMMENTS BEFORE PLANS ARE RESUBMITTED FOR THE FOURTH |
| | REVIEW. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |