| 2008-06-10 10:36:32 | ****CORRECTIONS**** |
| | ***REVISED 6/23/08*** |
| | ***REVISED 7/22/08 (ITEM 54)** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME |
| | FOR CONSISTENCY |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE |
| | PERMIT APPLICATION. |
| | |
| | 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN |
| | FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA |
| | (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A |
| | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB |
| | INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE |
| | PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL |
| | DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL |
| | SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6. |
| | |
| | THREE COMPLETE COLLATED SETS OF PERMIT DOCUMENTS |
| | REQUIRED FOR PERMIT ISSUANCE.ONLY TWO SETS OF THE |
| | SUBMITTAL PREPARED BY WOJCIESZAK & ASSOCIATES (ROOFTOP |
| | EQUIPMENT) WERE SUBMITTED, AND THE SUBMITTAL INCLUDED |
| | PHOTOCOPIES OF ENGINEERING.SEE FAC61G15-23.002, |
| | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS.SEE OTHER COMMENT REGARDING THIS |
| | SUBMITTAL. |
| | |
| | 4.)PLEASE KEEP THE THRESHOLD INSPECTION PLAN (AND |
| | OTHER DOCUMENTS WHICH HAVE BEEN REVIEWED AND STAMPED) |
| | AS A PART OF THE PERMIT PACKAGE.THE PLAN AND THE |
| | PROPOSED SPECIAL INSPECTOR MUST BE APPROVED BY HAROLD |
| | PISKURA (SEE OTHER COMMENTS, 561-805-6711) PRIOR TO |
| | PERMIT ISSUANCE. |
| | |
| | 5.)ADDRESSED. |
| | |
| | 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD |
| | ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED |
| | (INFORMATIONAL ONLY). |
| | |
| | 7-38.) ADDRESSED. |
| | |
| | 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE |
| | ROOF PRODUCT APPROVAL. |
| | |
| | NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING |
| | CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION. THIS |
| | WILL BE A PROVISO ITEM. |
| | |
| | 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN |
| | ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE |
| | PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A |
| | LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA. |
| | |
| | PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS IF |
| | AVAILABLE, WWW.FLORIDABUILDING.ORG |
| | |
| | 41.)AN EVALUATION REPORT FOR WINDSOR REPUBLIC DOORS |
| | WAS SUBMITTED.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED.PLEASE SEE WWW.FLORIDABUILDING.ORG; THIS |
| | COMPANY HAS FIVE DIFFERENT PRODUCT APPROVALS FOR SIDE |
| | HINGED DOORS.IT IS LIKELY THAT THE INFORMATION |
| | REQUIRED IS AVAILABLE ON THIS WEBSITE. |
| | |
| | 42-46.) ADDRESSED. |
| | |
| | 47.) THE GATE SWING WAS REVISED, BUT DOOR 323 NOW DOES |
| | NOT COMPLY WITH FBC1007.2 (DOOR SWING CHANGED SINCE |
| | LAST REVIEW), DOOR ENCROACHMENT, AS THE DOOR NOW OPENS |
| | ONLY 90DEGREES (OBSTRUCTED BY THE GATE FROM OPENING |
| | 180DEGREES).AS DISCUSSED, THIS CAN BE REDLINED WITH A |
| | PROVISO THAT A REVISION BE SUBMITTED CHANGING DOOR |
| | HINGE OR DOOR SWING. |
| | |
| | 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER |
| | OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS |
| | AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE |
| | REVIEW. |
| | |
| | 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN |
| | ON A4.0, FAC9B72. |
| | |
| | 3RD REVIEW, THE NEGATIVE DESIGN PRESSURE FOR ROOF |
| | COMPONENTS & CLADDING, ZONES 2 AND 3, IS -87.THE |
| | SKYLIGHT SPECIFIED ON A4.0 HAS A DP LIMITATION OF -80. |
| | THE PRODUCT APPROVAL SUBMITTED WAS A FLORIDA STATE |
| | PRODUCT APPROVAL; THE PRODUCT SPECIFIED ON THE PLAN |
| | REFERS TO A MIAMIDADE NOA.PLEASE RESOLVE THE DESIGN |
| | PRESSURE ISSUE AND CORRELATE PAPERWORK. |
| | |
| | 50-53.) ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 54.) REGARDING THE SUBMITTAL PREPARED BY WOJCIESZAK & |
| | ASSOCIATES: |
| | |
| | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | AND ARE TO INCLUDE ALL INFORMATION REQUIRED BY |
| | FAC61G15-23.002, FS471 (CERTIFICATE OF AUTHORIZATION, |
| | PRINTED NAME AND LICENSE NUMBER OF INDIVIDUAL SEALING |
| | THE DOCUMENT, ETC.).THE ONLY EXCEPTION TO THIS |
| | REQUIREMENT IS PRODUCT APPROVALS, WHICH HAVE AN |
| | EXCEPTION TO THE REQUIREMENT FOR ORIGINAL DOCUMENTS |
| | WITHIN THE FLORIDA STATUTE.ALSO, PLEASE NOTE THE |
| | FOLLOWING: |
| | |
| | A. THE SUBMITTAL INCLUDES SPEC SHEETS (TOP RIGHT STATES |
| | JOB: SARI, LOUVER, MARK 4 AND JOB: TEMPLE ISRAEL, FAN, |
| | MARK SF 1 & 2) WHICH BOTH REFER TO NOA03-0422.05, |
| | GREENHECK SEVERE DUTY LOUVERED ENCLOSURES FLORIDA STATE |
| | PRODUCT APPROVAL 4825.1.PLEASE PRINT THE PRODUCT |
| | APPROVAL, THREE SETS.BASED ON THE NOA WHICH I VIEWED |
| | ONLINE, THIS PRODUCT APPEARS CODE COMPLIANT.SEE |
| | COMMENT 48; HAVE THE DESIGNER REVIEW THE PRODUCT PRIOR |
| | TO RESUBMITTAL (SHOP DRAWING REVIEW STAMP OR SIGNED AND |
| | SEALED LETTER). |
| | |
| | B. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE |
| | ENGINEERING WHICH STATES THAT H-CUE 060-200 (EXHAUST |
| | FAN, SPEC SHEET REFERS TO MARK EF 14 & 15), WILL |
| | WITHSTAND WINDS UP TO 150MPH.BASED ON THE INFORMATION |
| | FOUND AT |
| | HTTP://WWW.GREENHECK.COM/PDF/FANS/PROMOHIGHWINDFANSNOVE |
| | MBER2006.PDF, IT APPEARS THAT THIS PRODUCT MAY HAVE A |
| | MIAMIDADE NOA OR FLORIDA STATE PRODUCT APPROVAL, BUT I |
| | WAS UNABLE TO LOCATE.THE LETTER STATES THAT THIS |
| | PRODUCT IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT |
| | IS ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3. |
| | PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY |
| | DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS |
| | OR APPLY FOR LOCAL PRODUCT APPROVAL IF AN EVALUATION |
| | REPORT (MIAMIDADE NOA OR FLORIDA STATE PRODUCT |
| | APPROVAL) IS NOT AVAILABLE.IT IS SUGGESTED THAT THE |
| | LOCATIONS BE INCLUDED ON SHEET A4.0 WHICH SHOWS ROOFTOP |
| | EQUIPMENT.NOTE THAT THE EDGE ZONE IS 14FEET, SEE |
| | SHEET S7. |
| | |
| | C. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE |
| | ENGINEERING WHICH STATES THAT MODEL H-GB BELT DRIVE |
| | ROOF DOWNBLAST CENTRIFUGAL EXHAUST FAN, (AKA SPUN |
| | ALUMINUM ROOFTOP FAN, SPEC SHEET REFERS TO MARK EF 17), |
| | WILL WITHSTAND WINDS UP TO 150MPH.BASED ON THE |
| | INFORMATION FOUND AT |
| | HTTP://GFCPORTAL.COM/PDF/FANS/SPECIFICATIONS/CSI_%20HGB |
| | _%20SPEC_OCTOBER2007.RTF, IT APPEARS THAT THIS PRODUCT |
| | IS INCLUDED IN MIAMIDADE NOA 07-0503.07.THIS PRODUCT |
| | IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT IS |
| | ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3. |
| | PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY |
| | DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS. |
| | IT IS SUGGESTED THAT THE LOCATIONS BE INCLUDED ON SHEET |
| | A4.0 WHICH SHOWS ROOFTOP EQUIPMENT.NOTE THAT THE EDGE |
| | ZONE IS 14FEET, SEE SHEET S7. |
| | |
| | D. THE REPORTS FOR THE TRANE COMPANY ENTITLED SOUTH |
| | FLORIDA HURRICANE WIND LOAD LOAD ANALYSIS & |
| | CALCULATIONS PREPARED BY STAMOS & ASSOCIATES INC. ARE |
| | REQUIRED TO BE ORIGINAL AND TO INCLUDE ALL INFORMATION |
| | REQUIRED BY FAC61G15-23.002.CALCULATIONS ARE TO BE |
| | EITHER SIGNED, SEALED AND DATED ON EACH SHEET OR |
| | INCLUDE AN INDEX SHEET AS WELL AS ALL INFORMATION |
| | REQUIRED BY FAC61G15-23.002.THE ENGINEERING IS DATED |
| | 10/21/93; THE ASCE STANDARD FOR WIND HAS BEEN REVISED |
| | THREE TIMES SINCE THAT DATE; THE CALCULATIONS WERE DONE |
| | IN ACCORDANCE WITH SFBC (A CODE NO LONGER IN EFFECT) |
| | AND SHOULD BE DONE IN ACCORDANCE WITH FBC/ASCE; PLEASE |
| | UPDATE ENGINEERING.THE CALCULATIONS SUBMITTED REFER |
| | TO SFBC AND APPLICABLE SFBC CODE REFERENCES; PLEASE |
| | REVISE TO REFLECT THE CURRENT CODE.THE CALCULATIONS |
| | USE P=37PSF FROM SFBC TABLE 2309.2; PLEASE USE |
| | PRESSURES AS PER FBC2004 SECTION 1609 OR ASCE7-02. |
| | DESIGN PRESSURES MUST BE CONSISTENT WITH PRESSURES |
| | DECLARED BY THE STRUCTURAL ENGINEER.PLEASE SPECIFY |
| | MINIMUM DISTANCE OF ROOFTOP UNIT TO EDGE OF ROOF |
| | (LOCATION IN ZONE 1 OR ZONE 2); IT IS NOT CLEAR WHY |
| | 37PSF HAS BEEN USED OR IF ROOFTOP EQUIPMENT LOCATION |
| | WILL AFFECT DESIGN.THE CALCULATIONS STATE ON SHEET 3 |
| | THAT REAR PANEL INFORMATION IS NOT AVAILABLE; PLEASE |
| | REVISE CALCULATIONS TO INCLUDE ALL APPLICABLE |
| | INFORMATION. THE CALCULATIONS STATE THAT SOME OF THE |
| | SCREW FASTENER PATTERN CALCULATIONS WERE OMITTED DUE TO |
| | ADEQUATE FASTENERS ILLUSTRATED, PLEASE REVISE TO |
| | INCLUDE ALL APPLICABLE INFORMATION.THE DESIGN WAS FOR |
| | 120MPH, MOST LIKELY SUSTAINED RATHER THAN 3SECOND GUST; |
| | PLEASE CLARIFY DESIGN CRITERIA. |
| | |
| | E. A LETTER PREPARED BY KIRBY BICKNELL, PE AND REVIEWED |
| | BY JOHN D. BUEROSSEE, PE REGARDING THE EXTREME |
| | CONDITION MOUNTING KIT WAS SUBMITTED.DOCUMENTS |
| | PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD |
| | ARE TO BE SIGNED, SEALED, DATED ORIGINALS.PROVIDE THE |
| | SPEC SHEETS FOR THIS PRODUCT ALONG WITH ORIGINAL |
| | ENGINEERING IF A PRODUCT APPROVAL IS NOT AVAILABLE. |
| | |
| | F. ENGINEERING PREPARED BY BROMLEY COOK FOR PRECISION |
| | ALUMINUM PRODUCTS WAS PROVIDED.THIS PRODUCT REQUIRES |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL, FAC9B72. |
| | PLEASE VERIFY; A MIAMIDADE NOA MAY BE AVAILABLE. |
| | |
| | ** MECHANICAL EQUIPMENT ENGINEERING FOR WIND CAN BE A |
| | PROVISO ITEM.ALL ITEMS 54A THROUGH F TO BE ADDRESSED |
| | THROUGH PLAN REVIEW AS A REVISION PRIOR TO |
| | INSTALLATION. ** (REVISED 7/22/8 |
| | |
| | 54.)PAYMENT OF IMPACT FEES AND APPROVAL OF THE |
| | SPECIAL INSPECTOR BY HAROLD PISKURA ARE REQUIRED PRIOR |
| | TO PERMIT ISSUANCE.ALL OTHER ISSUES IN THIS LIST CAN |
| | BE PROVISO ITEMS (SUBMITTED PRIOR TO INSTALLATION, |
| | AFTER PERMIT ISSUANCE). |
| | |
| | ***NEW COMMENTS 6/23/8*** |
| | |
| | 55.)SHEETS A3.0, A3.1, AND A3.2 WERE REMOVED FROM ONE |
| | SET AND RETAINED BY ANOTHER REVIEWER.PLEASE PRINT |
| | ANOTHER SET OF THESE SHEETS AND INSERT INTO THE SET |
| | FROM WHICH THEY HAVE BEEN REMOVED. |
| | |
| | 56.)THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT |
| | THE REFLECTED CEILING PLAN IS TO BE REVISED TO |
| | CORRELATE WITH THE ELECTRICAL DRAWINGS PRIOR TO |
| | INSTALLATION. |