Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop B
Sequence Number 3
Notes
Date Text
2008-06-10 10:36:32****CORRECTIONS****
 ***REVISED 6/23/08***
 ***REVISED 7/22/08 (ITEM 54)**
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME
 FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE
 PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL
 DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL
 SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6.
  
 THREE COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE.ONLY TWO SETS OF THE
 SUBMITTAL PREPARED BY WOJCIESZAK & ASSOCIATES (ROOFTOP
 EQUIPMENT) WERE SUBMITTED, AND THE SUBMITTAL INCLUDED
 PHOTOCOPIES OF ENGINEERING.SEE FAC61G15-23.002,
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.SEE OTHER COMMENT REGARDING THIS
 SUBMITTAL.
  
 4.)PLEASE KEEP THE THRESHOLD INSPECTION PLAN (AND
 OTHER DOCUMENTS WHICH HAVE BEEN REVIEWED AND STAMPED)
 AS A PART OF THE PERMIT PACKAGE.THE PLAN AND THE
 PROPOSED SPECIAL INSPECTOR MUST BE APPROVED BY HAROLD
 PISKURA (SEE OTHER COMMENTS, 561-805-6711) PRIOR TO
 PERMIT ISSUANCE.
  
 5.)ADDRESSED.
  
 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD
 ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED
 (INFORMATIONAL ONLY).
  
 7-38.) ADDRESSED.
  
 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE
 ROOF PRODUCT APPROVAL.
  
 NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING
 CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION. THIS
 WILL BE A PROVISO ITEM.
  
 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN
 ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS IF
 AVAILABLE, WWW.FLORIDABUILDING.ORG
  
 41.)AN EVALUATION REPORT FOR WINDSOR REPUBLIC DOORS
 WAS SUBMITTED.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED.PLEASE SEE WWW.FLORIDABUILDING.ORG; THIS
 COMPANY HAS FIVE DIFFERENT PRODUCT APPROVALS FOR SIDE
 HINGED DOORS.IT IS LIKELY THAT THE INFORMATION
 REQUIRED IS AVAILABLE ON THIS WEBSITE.
  
 42-46.) ADDRESSED.
  
 47.) THE GATE SWING WAS REVISED, BUT DOOR 323 NOW DOES
 NOT COMPLY WITH FBC1007.2 (DOOR SWING CHANGED SINCE
 LAST REVIEW), DOOR ENCROACHMENT, AS THE DOOR NOW OPENS
 ONLY 90DEGREES (OBSTRUCTED BY THE GATE FROM OPENING
 180DEGREES).AS DISCUSSED, THIS CAN BE REDLINED WITH A
 PROVISO THAT A REVISION BE SUBMITTED CHANGING DOOR
 HINGE OR DOOR SWING.
  
 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS
 AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE
 REVIEW.
  
 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN
 ON A4.0, FAC9B72.
  
 3RD REVIEW, THE NEGATIVE DESIGN PRESSURE FOR ROOF
 COMPONENTS & CLADDING, ZONES 2 AND 3, IS -87.THE
 SKYLIGHT SPECIFIED ON A4.0 HAS A DP LIMITATION OF -80.
 THE PRODUCT APPROVAL SUBMITTED WAS A FLORIDA STATE
 PRODUCT APPROVAL; THE PRODUCT SPECIFIED ON THE PLAN
 REFERS TO A MIAMIDADE NOA.PLEASE RESOLVE THE DESIGN
 PRESSURE ISSUE AND CORRELATE PAPERWORK.
  
 50-53.) ADDRESSED.
  
 NEW COMMENTS:
  
 54.) REGARDING THE SUBMITTAL PREPARED BY WOJCIESZAK &
 ASSOCIATES:
  
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 AND ARE TO INCLUDE ALL INFORMATION REQUIRED BY
 FAC61G15-23.002, FS471 (CERTIFICATE OF AUTHORIZATION,
 PRINTED NAME AND LICENSE NUMBER OF INDIVIDUAL SEALING
 THE DOCUMENT, ETC.).THE ONLY EXCEPTION TO THIS
 REQUIREMENT IS PRODUCT APPROVALS, WHICH HAVE AN
 EXCEPTION TO THE REQUIREMENT FOR ORIGINAL DOCUMENTS
 WITHIN THE FLORIDA STATUTE.ALSO, PLEASE NOTE THE
 FOLLOWING:
  
 A. THE SUBMITTAL INCLUDES SPEC SHEETS (TOP RIGHT STATES
 JOB: SARI, LOUVER, MARK 4 AND JOB: TEMPLE ISRAEL, FAN,
 MARK SF 1 & 2) WHICH BOTH REFER TO NOA03-0422.05,
 GREENHECK SEVERE DUTY LOUVERED ENCLOSURES FLORIDA STATE
 PRODUCT APPROVAL 4825.1.PLEASE PRINT THE PRODUCT
 APPROVAL, THREE SETS.BASED ON THE NOA WHICH I VIEWED
 ONLINE, THIS PRODUCT APPEARS CODE COMPLIANT.SEE
 COMMENT 48; HAVE THE DESIGNER REVIEW THE PRODUCT PRIOR
 TO RESUBMITTAL (SHOP DRAWING REVIEW STAMP OR SIGNED AND
 SEALED LETTER).
  
 B. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE
 ENGINEERING WHICH STATES THAT H-CUE 060-200 (EXHAUST
 FAN, SPEC SHEET REFERS TO MARK EF 14 & 15), WILL
 WITHSTAND WINDS UP TO 150MPH.BASED ON THE INFORMATION
 FOUND AT
 HTTP://WWW.GREENHECK.COM/PDF/FANS/PROMOHIGHWINDFANSNOVE
 MBER2006.PDF, IT APPEARS THAT THIS PRODUCT MAY HAVE A
 MIAMIDADE NOA OR FLORIDA STATE PRODUCT APPROVAL, BUT I
 WAS UNABLE TO LOCATE.THE LETTER STATES THAT THIS
 PRODUCT IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT
 IS ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3.
 PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS
 OR APPLY FOR LOCAL PRODUCT APPROVAL IF AN EVALUATION
 REPORT (MIAMIDADE NOA OR FLORIDA STATE PRODUCT
 APPROVAL) IS NOT AVAILABLE.IT IS SUGGESTED THAT THE
 LOCATIONS BE INCLUDED ON SHEET A4.0 WHICH SHOWS ROOFTOP
 EQUIPMENT.NOTE THAT THE EDGE ZONE IS 14FEET, SEE
 SHEET S7.
  
 C. THE SUBMITTAL INCLUDES AN UNSIGNED LETTER FROM RICE
 ENGINEERING WHICH STATES THAT MODEL H-GB BELT DRIVE
 ROOF DOWNBLAST CENTRIFUGAL EXHAUST FAN, (AKA SPUN
 ALUMINUM ROOFTOP FAN, SPEC SHEET REFERS TO MARK EF 17),
 WILL WITHSTAND WINDS UP TO 150MPH.BASED ON THE
 INFORMATION FOUND AT
 HTTP://GFCPORTAL.COM/PDF/FANS/SPECIFICATIONS/CSI_%20HGB
 _%20SPEC_OCTOBER2007.RTF, IT APPEARS THAT THIS PRODUCT
 IS INCLUDED IN MIAMIDADE NOA 07-0503.07.THIS PRODUCT
 IS LIMITED TO -61 PSF.THEREFORE, THIS PRODUCT IS
 ACCEPTABLE FOR USE IN ZONE 1 BUT NOT ZONES 2 OR 3.
 PROVIDE THREE SETS OF PRODUCT APPROVALS, REVIEWED BY
 DESIGNER OF RECORD, AND CLARIFY INSTALLATION LOCATIONS.
 IT IS SUGGESTED THAT THE LOCATIONS BE INCLUDED ON SHEET
 A4.0 WHICH SHOWS ROOFTOP EQUIPMENT.NOTE THAT THE EDGE
 ZONE IS 14FEET, SEE SHEET S7.
  
 D. THE REPORTS FOR THE TRANE COMPANY ENTITLED SOUTH
 FLORIDA HURRICANE WIND LOAD LOAD ANALYSIS &
 CALCULATIONS PREPARED BY STAMOS & ASSOCIATES INC. ARE
 REQUIRED TO BE ORIGINAL AND TO INCLUDE ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.CALCULATIONS ARE TO BE
 EITHER SIGNED, SEALED AND DATED ON EACH SHEET OR
 INCLUDE AN INDEX SHEET AS WELL AS ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.THE ENGINEERING IS DATED
 10/21/93; THE ASCE STANDARD FOR WIND HAS BEEN REVISED
 THREE TIMES SINCE THAT DATE; THE CALCULATIONS WERE DONE
 IN ACCORDANCE WITH SFBC (A CODE NO LONGER IN EFFECT)
 AND SHOULD BE DONE IN ACCORDANCE WITH FBC/ASCE; PLEASE
 UPDATE ENGINEERING.THE CALCULATIONS SUBMITTED REFER
 TO SFBC AND APPLICABLE SFBC CODE REFERENCES; PLEASE
 REVISE TO REFLECT THE CURRENT CODE.THE CALCULATIONS
 USE P=37PSF FROM SFBC TABLE 2309.2; PLEASE USE
 PRESSURES AS PER FBC2004 SECTION 1609 OR ASCE7-02.
 DESIGN PRESSURES MUST BE CONSISTENT WITH PRESSURES
 DECLARED BY THE STRUCTURAL ENGINEER.PLEASE SPECIFY
 MINIMUM DISTANCE OF ROOFTOP UNIT TO EDGE OF ROOF
 (LOCATION IN ZONE 1 OR ZONE 2); IT IS NOT CLEAR WHY
 37PSF HAS BEEN USED OR IF ROOFTOP EQUIPMENT LOCATION
 WILL AFFECT DESIGN.THE CALCULATIONS STATE ON SHEET 3
 THAT REAR PANEL INFORMATION IS NOT AVAILABLE; PLEASE
 REVISE CALCULATIONS TO INCLUDE ALL APPLICABLE
 INFORMATION. THE CALCULATIONS STATE THAT SOME OF THE
 SCREW FASTENER PATTERN CALCULATIONS WERE OMITTED DUE TO
 ADEQUATE FASTENERS ILLUSTRATED, PLEASE REVISE TO
 INCLUDE ALL APPLICABLE INFORMATION.THE DESIGN WAS FOR
 120MPH, MOST LIKELY SUSTAINED RATHER THAN 3SECOND GUST;
 PLEASE CLARIFY DESIGN CRITERIA.
  
 E. A LETTER PREPARED BY KIRBY BICKNELL, PE AND REVIEWED
 BY JOHN D. BUEROSSEE, PE REGARDING THE EXTREME
 CONDITION MOUNTING KIT WAS SUBMITTED.DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED, DATED ORIGINALS.PROVIDE THE
 SPEC SHEETS FOR THIS PRODUCT ALONG WITH ORIGINAL
 ENGINEERING IF A PRODUCT APPROVAL IS NOT AVAILABLE.
  
 F. ENGINEERING PREPARED BY BROMLEY COOK FOR PRECISION
 ALUMINUM PRODUCTS WAS PROVIDED.THIS PRODUCT REQUIRES
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL, FAC9B72.
 PLEASE VERIFY; A MIAMIDADE NOA MAY BE AVAILABLE.
  
 ** MECHANICAL EQUIPMENT ENGINEERING FOR WIND CAN BE A
 PROVISO ITEM.ALL ITEMS 54A THROUGH F TO BE ADDRESSED
 THROUGH PLAN REVIEW AS A REVISION PRIOR TO
 INSTALLATION. ** (REVISED 7/22/8
  
 54.)PAYMENT OF IMPACT FEES AND APPROVAL OF THE
 SPECIAL INSPECTOR BY HAROLD PISKURA ARE REQUIRED PRIOR
 TO PERMIT ISSUANCE.ALL OTHER ISSUES IN THIS LIST CAN
 BE PROVISO ITEMS (SUBMITTED PRIOR TO INSTALLATION,
 AFTER PERMIT ISSUANCE).
  
 ***NEW COMMENTS 6/23/8***
  
 55.)SHEETS A3.0, A3.1, AND A3.2 WERE REMOVED FROM ONE
 SET AND RETAINED BY ANOTHER REVIEWER.PLEASE PRINT
 ANOTHER SET OF THESE SHEETS AND INSERT INTO THE SET
 FROM WHICH THEY HAVE BEEN REMOVED.
  
 56.)THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT
 THE REFLECTED CEILING PLAN IS TO BE REVISED TO
 CORRELATE WITH THE ELECTRICAL DRAWINGS PRIOR TO
 INSTALLATION.