Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop P
Sequence Number 2
Notes
Date Text
2008-03-15 09:25:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
  
 19. SHT P1.0 SHOWS CONDENSATE TO DISCHARGE 6" ABOVE THE
 SIDEWALK. THIS IS NOT APPROVED. CONDENSATE SHALL
 CONNECT TO A DRYWELL, STORM CATCH BASIN, PLANTED AREA
 OR CONNECT TO A STORM DRAINAGE LINE OUTSIDE THE
 BUILDING. IF CONNECTING TO A STORM LINE, A RELIEF VENT,
 (GOOSENECK), SHALL BE REQUIRED AS THE CONDENSATE EXITS
 THE BUILDING. CONDENSATE DRAINAGE CAN NOT CREATE A
 HAZARD OR NUISANCE. SECTION 314.2.1.
 ****RESPONSE NOTED, BUT THE RELIEF VENT, (GOOSENECK),
 IS NOT INDICATED ON THE PLANS. THE RELIEF VENT WILL
 KEEP ANY STORM/CONDENSATE FROM ENTERING THE BUILDING
 AND MAKES THE REQUIREMENT FOR A BACKWATER VALVE MOOT.
  
 20. OK
 21. OK
  
 22. SUBMIT A WATER ISOMETRIC WATER RISER DIAGRAM FROM
 METER, THRU RPZV BACKFLOW, TO THE MOST REMOTE FIXTURE
 SHOWING ALL PIPE SIZES, VALVES, OFFSETS, & WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. SECTION
 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT SHEET P-12 STATES "CONT. ON SHT
 P-13.0, BUT NO WATER ISOMETRIC WAS FOUND ON SHE P-13.0.
 PLEASE CLARIFY.
  
 23. OK
 24. OK
  
 25. SHT P-3.0 CONDENSATE LINES SHOW BACKWATER VALVES.
 PER SECTION 715.1 FIXTURES ABOVE THE ELEVATION OF THE
 MANHOLE SHALL NOT DISCHARGE THRU A BACKWATER VALVE.
 WHERE THE POSSIBILITY OF A BACKUP MAY OCCUR, A RELIEF
 VENT, (GOOSENECK) , SHALL BE INSTALLED AS THE
 CONDENSATE EXITS THE BUILDING.
 ****RESPONSE NOTED, BUT THE RELIEF VENT WILL KEEP ANY
 STORM/CONDENSATE FROM ENTERING THE BUILDING AND MAKES
 THE REQUIREMENT FOR A BACKWATER VALVE MOOT.
  
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
  
 31. SUBMIT STORM ISOMETRIC RISER DIAGRAMS FOR ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS THAT REFLECT THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, OFFSETS AND INDICATE SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF DRAIN. SECTION
 106.3.5.1.3(7)(13).--SHOW CLEANOUTS REQUIRED BY
 SECTION 1101.8.
 ****RESPONSE NOTED, BUT ISOMETRIC RISER DIAGRAMS FOR
 RISERS 12 THRU 22 HAVE NOT BEEN SUBMITTED. PLEASE SHOW
 ALL PIPE SIZES AND INDICATE THE SQUARE FOOTAGE IN THE
 RISER DIAGRAM AS IT ACCUMULATES IN THE SYSTEM ON THE
 NEW RISERS AS WELL AS THOSE RISERS SUBMITTED
 PREVIOUSLY.
  
 32. SUBMIT CONDENSATE ISOMETRIC RISER DIAGRAMS FOR ALL
 CONDENSATE RISERS THAT REFLECT THE FLOOR PLAN. SHOW
 PIPE SIZES. OFFSETS AND INDICATE MATERIAL FOR SYSTEM.
 NO PVC IN PLENUMS.
 ****RESPONSE NOTED, BUT CONDENSATE RISERS WERE NOT
 FOUND.
  
 33. OK
 34. OK
 35. OK
 36. OK
 37. OK
  
 38. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED TO SECURE A PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
 ****RESPONSE NOTED, BUT THE LENGTHS OF PIPE FROM THE
 METER TO AND INCLUDING THE FIRST DROP, THE FIRST RISE
 AND SECTION OVER TO THE FIRST RISER, (12FT). ALSO THE
 DROP OUT OF THE CEILING IS ONLY SHOWN AS 2FT. PLEASE
 CLARIFY AND SHOW ALL CUT SECTION LENGHTS.
  
 B. OK
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM
 THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON
 THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES
 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING
 ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC
 SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE
 CLARIFY.
 ****RESPONSE NOTED, BUT ADDITION OF CUT SECTION LENGHTS
 SHOWN TOTALS 127FT, THIS IS WITH THE SECTIONS FROM THE
 METER TO AND INCLUDING THE FIRST DROP, AS WELL AS THE
 FIRST RISE FROM THE PE PIPE AND SECTION TO THE FIRST
 RISER (12FT) NOT ADDED. A CLARIFICATION FOR THE DROP
 DOWNSTREAM OF THE SOLINOID VALVE, (2FT),WILL BE
 REQUIRED TO BE VERIFIED.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE LOCATION OF THE INFORMATION
 ON THE ARCHITECTURAL SHEETS IS NOT INDICATED. ALSO THE
 LISTING INFORMATION AS WELL AS THE BTU LOAD OF EACH GAS
 APPLIANCE IS REQUIRED. WILL THIS INFORMATION BE
 AVAILABLE ON THE ARCHITECTURAL SHEETS? IF NOT SUBMIT
 MANUF. SPECIFICATION SHEETS TO VERIFY LISTING & BTU
 LOAD.
  
 G. N/A
 H. N/A
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE IS
 NOT INDICATED, NOR IS THE UNION. ALSO NO INDICATION
 THAT THE VALVES/UNION ARE BELOW THE CEILING.
  
 J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE
 REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT
 THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE
 REGULATOR.
 ****RESPONSE NOTED, PLEASE SUBMIT PRIOR TO INSTALLATION
 TO PREVENT REMOVAL/REPLACEMENT IN CASE REGULATOR IS NOT
 APPROVED.
  
 K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4.
 --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE
 SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE UNION IS NOT INDICATED.
  
 **********NEW COMMENT**********
  
 1B. SHT P-11.1 THE UNIT NUMBERS FROM THE GAS APPLIANCE
 SCHEDULE DO NOT REFLECT THE NUMBERS INDICATED ON THE
 GAS ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1 & TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]