Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop M
Sequence Number 2
Notes
Date Text
2008-03-03 17:30:44REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK EXCEPT:
 PG M-1.1: IT APPEARS THAT SEVERAL SG-2 LINEAR DIFFUSERS
 ARE INCORRECTLY LABELED 20 INCHES BY 1 INCH WHEN THEY
 SHOULD BE LABELED FOR 20 FEET BY 1 INCH. ALSO, THE
 RETURN GRILL FOR RTU 1C DOES NOT HAVE A SIZE OR CFM
 DESIGNATION.
  
 2. PG M-1.1 AND M-1.2: AIR BALANCES STILL DO NOT
 REFLECT THE INTRODUCTION OF OUTDOOR AIR. EXAMPLE: RTU
 1A AND RTU 1B ON EQUIPMENT SCHEDULE EACH SHOW 6400 CFM
 OF SUPPLY. THE FLOOR PLAN ON PG M-1.1 SHOWS EACH UNIT
 RETURNING 6400 CFM FROM THE SPACE. IF THESE UNITS ARE
 RETURNING 100% OF THE AIR BEING SUPPLIED, HOW WILL THEY
 BE ABLE TO INTRODUCE THE 1300 CFM OF OUTDOOR AIR THAT
 EACH UNIT CALLS FOR ON THE EQUIPMENT SCHEDULE? A
 SIMILAR CONFIGURATION AND PROBLEM OCCURS FOR RTU 2A AND
 RTU 2B. IF THE INTENTION IS FOR THE RETURN AIR FLOW TO
 BE REDUCED AS THE OUTSIDE AIR DAMPER MODULATES, WOULD
 THERE NOT BE A NEED FOR A CORRESPONDING MODULATING
 DAMPER IN THE RETURN DUCTS? ADDITIONALLY, IT IS UNCLEAR
 HOW THE GRAVITY RELIEF VENTILATORS WILL SERVE TO
 RELIEVE POSITIVE PRESSURE IN THE SPACES BEING SERVED IF
 THEY ARE TIED INTO THE RETURN AIR DUCT SYSTEM. THIS
 WOULD PUT THE GRAVITY RELIEF UNDER CONSTANT NEGATIVE
 PRESSURE. PLEASE CLARIFY.
  
 3. A-6.1: ELEVATION DRAWINGS STILL DO NOT SHOW A
 PERMANENT MEANS OF ACCESS WHICH STARTS AT GRADE LEVEL
 AS REQUIRED BY FBCM 306.5. PLEASE SHOW COMPLIANCE AND
 RESUBMIT.
  
 4. DEFERRED TO BUILDING PLAN REVIEW. PLEASE COORDINATE
 WITH ARCHITECT SHOULD BUILDING PLAN REVIEW INDICATE THE
 NEED FOR RATED ASSEMBLIES IN ANY AREAS.
  
 5. PG M-2.1: PLEASE SEE COMMENT #2 ABOVE REGARDING AIR
 BALANCE AND GRAVITY VENTILATOR DESIGN FOR RTU 3A.
 AHU-14: FLOOR PLAN SHOWS 640 CFM OF SUPPLY WHILE
 SCHEDULE ON PG M-6.0 SHOWS 450 CFM OF SUPPLY. ALSO,
 SUPPLY AND RETURN ARE BOTH SHOWN AT 640 CFM, HOW WILL
 OUTSIDE AIR BE INTRODUCED?
 AHU-13: DH-2, WHICH IS ATTACHED TO THIS AHU, DOES NOT
 APPEAR IN THE EQUIPMENT SCHEDULE ON PG M-6.0. PLEASE
 CLARIFY. SEE COMMENT ABOVE REGARDING OA INTRODUCTION.
 PLEASE CHECK ALL AIR HANDLING SYSTEMS FOR SIMILAR
 CIRCUMSTANCES ON M-2.1, M-2.2, M-3.1 AND M-3.2.
 PG M-2.2: EXHAUST GRILLS FOR EF-3 ARE MISSING
 DESIGNATIONS, SIZES AND CFM. PLEASE CORRECT.
 PG M-3.2: THERE ARE DUCTS COMING DOWN FROM ROOF IN ROOM
 322 WHICH APPEAR TO BE FROM OAU-1. THIS UNIT IS SHOWN
 ON PG M-11.0 AS A 100% OUTSIDE AIR UNIT. IT IS UNCLEAR
 AS TO WHY A 100% OUTSIDE AIR UNIT HAS A RETURN DUCT
 SYSTEM SINCE IT IS PROVIDING 100% OUTSIDE AIR. PLEASE
 CLARIFY THE DESIGN INTENT. FBC 106.1.1.
  
 6. PLEASE SEE COMMENT #2 REGARDING DESIGN OF GRAVITY
 RELIEF DAMPERS.
  
 7. OK
  
 8. OK, EXCEPT PG M-2.3: KITCHEN GREASE EXHAUST DUCT,
 VERTICAL DUCTS UNDER EF-14 AND EF-15 ARE SHOWN ON PLAN
 TO BE 16X16. EACH OF THESE FANS IS SHOWN ON EQUIPMENT
 SCHEDULE TO BE RATED AT 1912 CFM. THIS MEANS THE AIR
 VELOCITY IN THE 16X16 DUCT WOULD BE APPROXIMATELY 1074
 FEET PER MINUTE. GREASE DUCT SYSTEMS SERVING A TYPE I
 HOOD SHALL BE DESIGNED AND INSTALLED SO AS TO PROVIDE
 AN AIR VELOCITY WITHIN THE DUCT SYSTEM OF NOT LESS THAN
 1,500 FEET PER MINUTE AND NOT GREATER THAN 2,500 FEET
 PER MINUTE IN ACCORDANCE WITH FBCM 506.3.4. THE 16X16
 DUCT MAY FALL UNDER THE EXCEPTION IN THIS SECTION IF IT
 IS FOR THE PURPOSE OF TRANSITIONING TO THE SIZE OF THE
 FANS AND IT IS LESS THAN 3 FEET IN LENGTH BUT THAT CAN
 NOT BE DETERMINED FROM THESE DRAWINGS.
  
 9. OK
  
 10. OK
  
 11. M-6.0: PLEASE INCLUDE THIS NOTE ON THE OARTU
 SCHEDULE.
  
 12. OK
  
 13. OK
  
 14. OK
  
 15. OK
  
 16. OK
  
 17. WIND LOAD SUBMITTAL DATA FOR ROOFTOP EQUIPMENT WILL
 BE REVIEWED BY THE BUILDING PLAN REVIEWER.
  
 18. EQUIPMENT HEIGHT OK, PRODUCT APPROVAL SUBMITTALS
 WILL BE REVIEWED BY THE BUILDING PLAN REVIEWER.
  
 19. OK
  
 20. TO BE DETERMINED BY SUBSEQUENT BUILDING PLAN
 REVIEW.
  
 PLEASE RESPOND TO ALL REVIEW COMMENTS IN WRITING WITH
 INFORMATION ON HOW COMMENTS HAVE BEEN ADDRESSED AND
 WHERE THE REQUESTED INFORMATION CAN BE FOUND IN ORDER
 TO SPEED THE REVIEW PROCESS. ADDITIONALLY, PLEASE
 RETURN ONE SET OF OLD PLANS FOR REFERENCE. ROMOVE
 OLD/VOIDED SHEETS FROM THE PLANS BEING SUBMITTED FOR
 PERMIT PRIOR TO RESUBMITTAL.
  