| Date |
Text |
| 2008-04-04 08:07:05 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED TO SECURE A PERMIT. |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO |
| | THE MOST REMOTE APPLIANCE. |
| | ****RESPONSE NOTED, BUT THE LENGTHS OF PIPE FROM THE |
| | METER TO AND INCLUDING THE FIRST DROP, THE FIRST RISE |
| | AND SECTION OVER TO THE FIRST RISER, (12FT). ALSO THE |
| | DROP OUT OF THE CEILING IS ONLY SHOWN AS 2FT. PLEASE |
| | CLARIFY AND SHOW ALL CUT SECTION LENGHTS. |
| | |
| | B. OK |
| | C. OK |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM |
| | THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON |
| | THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES |
| | 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING |
| | ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC |
| | SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE |
| | CLARIFY. |
| | ****RESPONSE NOTED, BUT ADDITION OF CUT SECTION LENGHTS |
| | SHOWN TOTALS 127FT, THIS IS WITH THE SECTIONS FROM THE |
| | METER TO AND INCLUDING THE FIRST DROP, AS WELL AS THE |
| | FIRST RISE FROM THE PE PIPE AND SECTION TO THE FIRST |
| | RISER (12FT) NOT ADDED. A CLARIFICATION FOR THE DROP |
| | DOWNSTREAM OF THE SOLINOID VALVE, (2FT),WILL BE |
| | REQUIRED TO BE VERIFIED. |
| | |
| | E. OK |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE LOCATION OF THE INFORMATION |
| | ON THE ARCHITECTURAL SHEETS IS NOT INDICATED. ALSO THE |
| | LISTING INFORMATION AS WELL AS THE BTU LOAD OF EACH GAS |
| | APPLIANCE IS REQUIRED. WILL THIS INFORMATION BE |
| | AVAILABLE ON THE ARCHITECTURAL SHEETS? IF NOT SUBMIT |
| | MANUF. SPECIFICATION SHEETS TO VERIFY LISTING & BTU |
| | LOAD. |
| | |
| | G. N/A |
| | H. N/A |
| | |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE IS |
| | NOT INDICATED, NOR IS THE UNION. ALSO NO INDICATION |
| | THAT THE VALVES/UNION ARE BELOW THE CEILING. |
| | |
| | J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE |
| | REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT |
| | THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE |
| | REGULATOR. |
| | ****RESPONSE NOTED, PLEASE SUBMIT PRIOR TO INSTALLATION |
| | TO PREVENT REMOVAL/REPLACEMENT IN CASE REGULATOR IS NOT |
| | APPROVED. |
| | |
| | K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4. |
| | --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE |
| | SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM. |
| | ****RESPONSE NOTED, BUT THE UNION IS NOT INDICATED. |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SHT P-11.1 THE UNIT NUMBERS FROM THE GAS APPLIANCE |
| | SCHEDULE DO NOT REFLECT THE NUMBERS INDICATED ON THE |
| | GAS ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 106.1.1 & TABLE 402.4(2). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |