Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop E
Sequence Number 2
Notes
Date Text
2008-02-16 12:32:53*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. AS
 MENTIONED ON PREVIOUS REVIEW AS THERE WAS ALSO
 INFORMATION NOT YET SUBMITTED THERE MAY ALSO BE NEW
 COMMENTS.
 ** PLEASE SEE NOTES BELOW AS THERE IS INFORMATION NOT
 YET SUBMITTED WHICH MAY GENERATE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT POSSIBLY BE MADE AT THIS
 TIME.
  
 1) NOTE: ** IMPORTANT** WHEN CALLING THIS
 OFFICE/REVIEWER AND LEAVING VOICEMAIL PLEASE BE SURE TO
 LEAVE A RETURN PHONE NUMBER.
  
 2) NOTE: ** IMPORTANT** PLEASE SEE PREVIOUS REVIEW NOTE
 AT THE END OF REVIEW WHICH WAS ** AND LABELED AS
 IMPORTANT** WHICH SPECIFICALLY REQUESTED FOR ALL
 OLD/VOIDED SHEETS TO BE COMPLETELY REMOVED FROM SETS.
 THIS WOULD CREATE SETS WHICH DO NOT CONTAIN ANY OF THE
 OLD SHEETS AND ONLY NEW SHEETS FOR REVIEW. ANY OLD AND
 VOIDED SHEETS WOULD BE SUBMITTED ALONG WITH NEW SETS
 SEPARATELY AND ONLY NEED ONE SET OF THE OLD SHEETS.
 PLANS SUBMITTED CONTAIN ALL THE OLD AND ALL THE NEW
 SHEETS CREATING SETS WHICH ARE TWICE AS LARGE AS NEED
 BE.
 ** THIS WILL HELP THE REVIEW PROCESS AND EXPEDITE THE
 REVIEWS. THANKING YOU IN ADVANCE FOR ATTENTION TO
 THIS.
  
 3) NOTE:** THIS COMMENT WITH RESPECT TO LIFE SAFETY
 EGRESS LIGHTING WILL BE BROKEN UP INTO SUB-SECTIONS.
 PLEASE ALSO KNOW THAT SOME EXAMPLES WILL BE GIVEN BUT
 ARE NO ALL LOCATIONS IN QUESTION.
 PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WITH RESPECT TO
 MINIMUM LIGHTING LEVELS FOR ALL DESIGNATED EGRESS
 PATHS.
 PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS WHERE NO
 EMERGENCY BATTERY BACK UP LIGHT FIXTURES IS SHOWN. THE
 PREVIOUS REVIEW GAVE SOME AREAS OF EXAMPLES AND MANY
 LIGHTING FIXTURE TYPES IN SOME OF THOSE AREAS WERE
 ADJUSTED HOWEVER MANY AREAS WERE STILL NOT CHANGE OR
 THE FIXTURES WERE NOT ADJUSTED.
  
 A) PLEASE SEE THE PREVIOUS REVIEW MENTIONED TO PROVIDE
 PHOTO-METRICS FOR EGRESS PATHS HOWEVER NONE WERE
 SUBMITTED. PLEASE SEE THE AREAS OF STAIRS REQUIRE A
 LEVEL OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED
 DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. NFPA-101
 7.8.1.3, 7.9.2.2.
 THERE ARE NO SUBMITTED PHOTO-METRICS LEVELS FOR ANY
 EGRESS PATHS. PLEASE SUBMIT. PLANS NOW INCLUDE A NEW
 BATTERY BACK UNIT WAS NOW ADDED TO RISER FOR MOST OF
 THE CIRCUITS BUT NOT ALL. ONLY CIRCUITS 1L3, 23, 29,
 AND 33 ARE SHOWN YET THERE ARE OTHER CIRCUITS FOR
 OUTSIDE EGRESS LIGHTS WHICH ARE NOT SHOWN. PLEASE
 SUBMIT THE NEW SPECS/CUT SHEETS ON THIS PROPOSED UNIT.
 PLEASE INDICATE TIME IN EMERGENCY UNDER LOAD OF
 CIRCUITS.
 FAC 61G15-33.004.
  
 B) PLEASE SEE SOME EGRESS PATH HAD ALL LIGHT FIXTURES
 CHANGED TO BATTERY BACK UP FIXTURES. THIS WAS NOT THE
 REQUEST HOWEVER THIS IS NOT A CODE ISSUE. PLEASE SEE
 THERE ARE SEVERAL OTHER AREAS IN WHICH NO EMERGENCY
 LIGHTING FIXTURES WERE LOCATED.
 PLEASE SEE SOCIAL HALL, BASED ON THE FIXTURE LEGEND
 NONE OF THESE FIXTURES IN AREAS OF EGRESS ARE BATTERY
 BACK UP.
 PLEASE SEE SANCTUARY, BASED ON THE FIXTURE LEGEND NONE
 OF THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP.
 PLEASE SEE LOBBY AREAS, BASED ON FIXTURE LEGEND NONE OF
 THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP.
 PLEASE SEE CHAPEL, NONE OF THESE FIXTURES AREA BATTERY
 BACK UP BASED ON FIXTURE LEGEND AND THE OCCUPANCY LOAD
 OF THE ROOM CERTAINLY REQUIRES THIS.
 PLEASE SEE SOME HANDRAILS WHICH DO NOT SHOW ANY LIGHTS
 (NE CORNER)
 PLEASE SEE CHAPEL WHICH BASED ON LIFE SAFETY PLANS
 INDICATES EGRESS INTO COURTYARD AREA WHICH COULD NOT
 LOCATE BACK UP LIGHTING TO OUTDOOR EGRESS HALLWAYS.
 ONCE THE PHOTO-METRICS ARE SUBMITTED THE LIGHTING
 LEVELS IN THAT ARE MAY BE SUFFICIENT WITH THE BATTERY
 BACK UP OF THE *A* FIXTURES WHICH ARE ALL SHOWN AS
 BATTERY BACK UP.
 PLEASE SEE LIBRARY, NONE OF THESE FIXTURES BASED ON THE
 FIXTURE LEGEND INDICATES ANY OF THESE AS BATTERY BACK
 UP. BASED ON OCCUPANCY AND LOAD OF ROOM, THIS IS
 REQUIRED.
 PLEASE SEE EGRESS PATHS FROM BUILDING TO STAIRS, NO
 FIXTURES COULD BE LOCATED FOR ILLUMINATION OF PLATFORM
 AREAS.
 ** PLEASE SEE THERE ARE OTHER AREAS ON PLANS SHOW WHERE
 EVERY SINGLE FIXTURE WAS CHANGED TO BATTERY BACK UP.
 THIS OFFICE ONLY REQUESTED TO MEET THE LIFE SAFETY
 CODE.
 WAS THE INTENT ON PLANS FOR ALL *B* FIXTURES WHICH ARE
 IN CLASSROOMS, OFFICES, STORAGE ROOMS, CLOSETS ETC TO
 ALL BE BATTERY BACK UP?
 WAS IT INTENDED FOR ALL *A* FIXTURES TO BE BATTERY
 BACK? SOME LOCATIONS ARE CLEAR AS TO WHY THESE WOULD BE
 CHANGED HOWEVER IS IT NOT UNDERSTOOD WHY MOST AREAS
 WHICH REQUIRE BATTERY BACK UP FIXTURES DO NOT CONTAIN
 ANY AND THEN OTHER AREAS WHICH DO NOT REQUIRE ANY
 CONTAIN ALL FIXTURES AS BATTERY BACK UP. SOME OF THE
 *A* FIXTURES WERE CHANGED TO *AE* FIXTURES.
 ** THERE IS NOTHING IN THE CODE WHICH PROHIBITS
 DESIGNER TO DESIGN ALL FIXTURES IN A BUILDING BEING
 BATTERY BACK UP HOWEVER THE REQUIRED EGRESS PATHS MUST
 CONTAIN THE MINIMUM TO MEET THE 1FT CANDLE LEVEL.
  
 C) PLEASE SEE COMMENTS BELOW IN NOTE #5E WITH RESPECT
 TO OCCUPANCY SENSORS ON EGRESS LIGHTING. FBCAND LS
 CODE.
  
 AS THERE ARE STILL MANY QUESTIONS AND SOME ITEMS ARE
 MISSING CAN NOT REVIEW ALL FOR CODE COMPLIANCE AT THIS
 TIME. REVIEW CAN ONLY BE BASED ON PLANS SUBMITTED.
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL SYMBOLS ON PLANS
 WHICH ARE NOT IN LEGEND FOR SYMBOLS, ARE NOT IN FIXTURE
 LEGEND AND DO NOT CONTAIN ANY CIRCUITING ETC. IT IS
 UNCLEAR WHAT MANY OF THESE ARE.
 PLEASE SEE SANCTUARY AREA WHICH CONTAINS A D IN A
 SQUARE BOX WHICH INDICATE 1INCH CONDUIT TO ER? PLEASE
 SEE LOBBY AREA WHICH ANOTHER CIRCLE SYMBOL WITH SQUARE
 BOX WHICH INDICATES TO ER, TO WPD?
 PLEASE SEE SOCIAL AREA WHICH CONTAINS THE SAME WHICH
 STATES TO ER, WPB?
 PLEASE BE SURE ALL SYMBOLS ON PLANS ARE ON LEGEND FOR
 WHAT THESE ARE.
 PLEASE SEE LIGHTING FIXTURES ON THE ELECTRICAL PLANS
 WHICH ARE NOT THE SAME AS THE FIXTURES SHOWN ON
 ARCHITECTURAL PLANS.(EXAMPLE: EXTERIOR) PLEASE KNOW
 AS THERE ARE OTHER COMMENTS ON ELECTRICAL PLANS AND
 WILL HAVE ADJUSTMENTS ON FIXTURES ETC PLEASE BE SURE
 THE INFORMATION IS FORWARDED TO THE ARCHITECT FOR
 COORDINATION.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC
 AND CHAPTER 13.
 PLEASE SEE THE COMMENTS BELOW WILL BE IN SECTIONS AS
 PREVIOUS REVIEW AND THE INPUT DATA REPORT WILL BE NOTED
 AS IDR.
  
 A) PLEASE SEE THAT NOT ENOUGH DETAILS WERE SUBMITTED
 FOR MAIN AREAS FOR LIGHTING CONTROLS. NO DETAILS ON THE
 DEVICES, POWER PACKS, SCHEDULING OF PROPOSED, ZONES
 ETC. PLANS SHOW SOME NEW OCCUPANCY SENSOR TYPE DEVICES
 YET NOT ENOUGH INFORMATION ON THESE WAS PROVIDED. HOW
 WILL ALL AREAS BE CONTROLLED?
 FOR EXAMPLE: LOBBY AREAS, OVER RIDES, OCCUPANCY
 SENSORS, ACCENT LIGHTING, DISPLAY LIGHTING ETC. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED
 FOR EXTERIOR LIGHTING CONTROLS. PLANS SHOW A LIGHTING
 CONTACTOR AND SOME LOCATIONS NOTE THERE WILL BE A
 ASTRONOMICAL TIME CLOCK HOWEVER PLEASE SEE THE REQUIRED
 BATTERY BACK UP OF 10HRS IF PROPOSING A TC COULD NOT BE
 LOCATED.
 PLEASE SEE 13-415.1.ABC.1.4 ALSO 13-415.1.ABC.2
  
 C) PLEASE SEE THE INFORMATION ON THE IDR DOES NOT
 CORRELATE WITH PLANS. PLEASE SEE THE EXTERIOR LIGHTING
 FOR EXAMPLE WHICH STATES ALL FIXTURES AS ONLY BEING 1.
 THIS IS NOT POSSIBLE WHEN THE ARE DOZENS OF FIXTURES ON
 PLANS FOR EACH TYPE. THE IDR REQUIRES EACH FIXTURE,
 EACH TYPE, AND METHOD OF CONTROL TO COORDINATE WITH
 PLANS. AT THIS TIME AS FIXTURES ARE ONLY INDICATE AS 1
 (ONE) AT EACH LOCATION ON THE IDR,THE SPECIFIC
 FIXTURES, COUNTS ETC CAN NOT BE DETERMINED.
  
 D) PLEASE SEE THE IDR FOR ALL INTERIOR LIGHTS DOES NOT
 COORDINATE. PLEASE SEE THAT ALL LIGHTING IS REQUIRED TO
 BE FIGURED PER 13-415.2.ABC.1.1 AND .1.2
 PLEASE SEE 13-415.2, 13-400
 PLEASE KNOW AS THERE ARE FIXTURES ON THE IDR WHICH ARE
 NOT ON FIXTURE LEGEND AND FIXTURES ON THE FIXTURE
 LEGEND WHICH ARE NOT ON THE IDR.
 FOR EXAMPLE:
 500W COMPACT FLUORESCENT FIXTURES ON IDR, NOT ON
 LEGEND.
 250W ON FIXTURE LEGEND NOT ON IDR.
 PLEASE SEE FIXTURE COUNTS ON PLANS COMPARED TO FIXTURES
 IN AREAS ON THE IDR.
 ** PLEASE KNOW THERE ARE SEVERAL MORE WHICH DO NOT
 CORRELATE AND ONLY A COUPLE OF EXAMPLES ARE GIVEN.
  
 E) PLEASE SEE CORRIDOR 335 WHICH INDICATES ONE WALL
 DEVICE AT EACH END OF THIS LONG EGRESS PATH. PLEASE SEE
 FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 WITH RESPECT TO
 AUTOMATED DEVICES IN EGRESS PATHS. THIS IS PERMITTED BY
 BOTH CODES HOWEVER THE COVERAGE OF SUCH UNITS SHALL BE
 SUFFICIENT FOR ENTIRE LENGTH, THE DEVICES ARE REQUIRED
 TO BE 15MINS OF TIME AND PLANS SHOW 10MINS.
 PLEASE ALSO SEE THE DEVICES SHALL ALSO BE FAIL-SAFE ON
 DEVICES. THIS WOULD ALSO BE FOR OTHER AREAS WHERE
 OCCUPANCY SENSORS ARE BEING USED FOR EGRESS LIGHTING.
  
 F) PLEASE INCLUDE NOTES ON PLANS ARE REQUIRED PER
 13-413.1.ABC.2, .2.1 AND .2.2
  
 G) PLEASE BE SURE THE OWNER AGENT HAS FILLED OUT
 SECTION ON CERTIFICATION SHEET AND SIGNED WHEN NEW
 CALCULATIONS ARE SUBMITTED.
 13-103.1.1.1
  
 6) NOTE: PLEASE BE SURE ALL EMERGENCY AND EXIT LIGHTS
 ARE CIRCUITED PER 700.12F. AS MOST FIXTURES IN MANY
 AREAS ARE ALL BATTERY BACK UP THIS IS OK, HOWEVER THIS
 NOTE REMAINS BASE DON THE FACT THERE ARE OTHER AREAS
 WHERE THERE ARE NO BATTERY BACK UP FIXTURES.
  
 7) NOTE: PLEASE SEE FAC 61G15-33.004 WHICH REQUIRES ALL
 LIGHTING AND ILLUMINATION DESIGN TO BE PART OF THE
 RESPONSIBILITY OF THE DESIGN PROFESSIONAL. IF THERE ARE
 OTHER SHEETS WHICH WILL BE PART OF THE LIGHTING BEING
 SUBMITTED FOR SCOPE OF WORK REQUIRED BY A DESIGN
 PROFESSIONAL PLEASE BE SURE ALL SHEETS CONTAINS THE
 INFORMATION FROM THAT DESIGN PROFESSIONAL AND ARE
 SIGNED, DATED AND SEALED ACCORDINGLY.
 PLEASE SEE LIGHTING PLANS SUBMITTED BY LD INC.
 THE PREVIOUS REVIEW REQUESTED PHOTO-METRICS TO BE
 SUBMITTED FOR ALL EXTERIOR LIGHTING AREAS. HOWEVER
 PLEASE SEE PLANS WHICH SHOWS AREAS WITH 0.0 (NO) LEVELS
 OF LIGHTING. HOW IS THIS POSSIBLE WHEN THERE ARE DOZENS
 OF EXTERIOR LIGHTS ON PLANS?
 PLEASE COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
  
 8) NOTE: PLEASE SEE THE PREVIOUS REVIEW MENTIONED THE
 CONCERN OF THE MAIN ELECTRICAL EQUIPMENT AND OTHER
 ELECTRICAL PANELS IN A REQUIRED EGRESS HALLWAY. REVIEW
 COMMENT MENTIONED TO SEE POSSIBLE BUILDING AND FIRE
 REVIEW COMMENTS.
 THE RESPONSE MENTIONS NO CODES WERE LOCATED WHICH
 PREVENTED THIS. AT THIS TIME INFORMATION AND SCENARIOS
 WILL BE TURNED OVER TO THE BUILDING REVIEWER AND
 BUILDING OFFICIAL FOR CLARIFICATION ON WHETHER OR NOT
 THIS IS PERMITTED AND MOST OF ALL IF THIS IS SAFE FOR
 THE OCCUPANTS IN AN EMERGENCY SITUATION. THIS REVIEWER
 CAN NOT SEE HOW THIS IS NOT A HAZARD AND NEEDS
 DETERMINATION ON THIS SCENARIO.
 THE 1600AMP MDP PROTRUDES INTO A REQUIRED EGRESS HALL
 WAY.
 FBC 1001.3, 1001.4
  
 9) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 WHICH
 MENTIONED TO CLARIFY THE MDP1 AS SHOWN ON RISER AND
 SCHEDULE.
 PLEASE SEE THE RISER STILL CONTAINS NOTE WHICH STATES
 *MAIN DISCONNECT PANEL*. THIS PANEL BY THE SCHEDULE IS
 SHOWN AS A MAIN LUG ONLY SWITCHBOARD.
 PLEASE SEE THE CIRCUITING ON THIS PANEL WAS ALSO NOT
 UPDATED. FOR EXAMPLE: AS NOTED PREVIOUSLY: EXAMPLE; 1)
 PANEL 1L1
 3)
 5)
 7) PANEL 1L2
 9)
 11)
 THIS IS AN EXAMPLE ONLY AS THIS IS STILL THREE PHASE
 EQUIPMENT.
 408.4, FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL
 INFORMATION AND COORDINATION.
  
 10) NOTE: PLEASE COORDINATE RISER AND PANELS. PLEASE
 SEE KITCHEN PANELS 1K1 AND 1K2 WHICH ARE BOTH SHOWN AS
 400AMP ON RISER AND BEING FED FROM THE MAIN
 DISTRIBUTION BOARD WITH A 400AMP BREAKER. YET PLEASE
 SEE EACH OF THESE PANELS ARE SHOWN AS 200AMP MLO ON
 THEIR SCHEDULES WITH ONLY A SINGLE FEED OF 3/0
 CONDUCTORS.
 PLEASE COORDINATE AND ADJUST.
 PLEASE ALSO SEE THE POWER PLANS DO NOT SHOW THE
 LOCATION OF THESE PANELS. SHEET E-5.0 MENTIONS TO SEE
 SHEET E-11.0 FOR THE ENLARGED KITCHEN PLANS. IT WAS
 BEING ASSUMED THESE PANEL WERE IN THE KITCHEN HOWEVER
 COULD NOT LOCATE THESE ANYWHERE ON PLANS.
 SHEET E-6.0 ALSO DOES NOT SHOW THESE K PANELS. 240.24,
 110.26, 408.17, 240.4, 310.16, ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO AIC
 RATINGS FOR ALL PANELS, BREAKER AND SERVICE EQUIPMENT.
 THE MAIN SWITCH BOARD DOES NOW INDICATE THE BRANCH
 CIRCUIT RATINGS AS 65K RATED AND MAIN AT 100K. HOWEVER
 PLEASE SEE OTHER PANELS WHICH SHOW ONE AIC RATING FOR
 BOARD AND BREAKERS STILL.
 PLEASE VERIFY FOR EXAMPLE ALL PANELS SHOWING A 65K
 RATING FOR PANELS AND BRANCH BREAKERS THIS IS WITH THE
 EXCEPTION OF PANEL 1K1 WHICH SHOWS A 10K RATING. 110.9,
 110.3
 FBC106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 12) NOTE: PLEASE KNOW THE SIGNED AND SEALED STRUCTURAL
 WIND LOAD CALCULATIONS SHOWING THE EPA (EFFECTIVE
 PROJECTED AREAS) OF LIGHT FIXTURES ON POLES WILL BE
 REVIEWED BY THE BUILDING REVIEWER.
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 PLEASE BE SURE TO GO OVER ALL COMMENTS AND ONCE AGAIN
 PLEASE CALL. PLEASE LEAVE PHONE NUMBER WHEN LEAVING A
 MESSAGE.
 ** PLEASE ALSO KNOW THAT AT THIS TIME ONE SET OF
 ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE BEING
 RETAINED BY THIS OFFICE.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2008-02-16 07:59:232008-02-16 07:059:23
  
 IN REVIEW
2008-02-15 19:34:00 
 2008-02-15 15:35:24
 REVIEW COMMENCED
  
 2008-02-15 19:34:00
 REVIEW STOPPED. WILL CONTINUE ON 2/16, NOTES WILL
 FOLLOW AND PLANS WILL BE IN A *FAILED STATUS*
  
  
2008-02-14 19:24:522008-02-14 19:24:52
  
 IN ELEC FOR REVIEW


Account Summary | Usage Policy | Privacy Policy