| 2008-02-16 12:32:53 | *** DENIED 2ND REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. AS |
| | MENTIONED ON PREVIOUS REVIEW AS THERE WAS ALSO |
| | INFORMATION NOT YET SUBMITTED THERE MAY ALSO BE NEW |
| | COMMENTS. |
| | ** PLEASE SEE NOTES BELOW AS THERE IS INFORMATION NOT |
| | YET SUBMITTED WHICH MAY GENERATE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH CAN NOT POSSIBLY BE MADE AT THIS |
| | TIME. |
| | |
| | 1) NOTE: ** IMPORTANT** WHEN CALLING THIS |
| | OFFICE/REVIEWER AND LEAVING VOICEMAIL PLEASE BE SURE TO |
| | LEAVE A RETURN PHONE NUMBER. |
| | |
| | 2) NOTE: ** IMPORTANT** PLEASE SEE PREVIOUS REVIEW NOTE |
| | AT THE END OF REVIEW WHICH WAS ** AND LABELED AS |
| | IMPORTANT** WHICH SPECIFICALLY REQUESTED FOR ALL |
| | OLD/VOIDED SHEETS TO BE COMPLETELY REMOVED FROM SETS. |
| | THIS WOULD CREATE SETS WHICH DO NOT CONTAIN ANY OF THE |
| | OLD SHEETS AND ONLY NEW SHEETS FOR REVIEW. ANY OLD AND |
| | VOIDED SHEETS WOULD BE SUBMITTED ALONG WITH NEW SETS |
| | SEPARATELY AND ONLY NEED ONE SET OF THE OLD SHEETS. |
| | PLANS SUBMITTED CONTAIN ALL THE OLD AND ALL THE NEW |
| | SHEETS CREATING SETS WHICH ARE TWICE AS LARGE AS NEED |
| | BE. |
| | ** THIS WILL HELP THE REVIEW PROCESS AND EXPEDITE THE |
| | REVIEWS. THANKING YOU IN ADVANCE FOR ATTENTION TO |
| | THIS. |
| | |
| | 3) NOTE:** THIS COMMENT WITH RESPECT TO LIFE SAFETY |
| | EGRESS LIGHTING WILL BE BROKEN UP INTO SUB-SECTIONS. |
| | PLEASE ALSO KNOW THAT SOME EXAMPLES WILL BE GIVEN BUT |
| | ARE NO ALL LOCATIONS IN QUESTION. |
| | PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WITH RESPECT TO |
| | MINIMUM LIGHTING LEVELS FOR ALL DESIGNATED EGRESS |
| | PATHS. |
| | PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS WHERE NO |
| | EMERGENCY BATTERY BACK UP LIGHT FIXTURES IS SHOWN. THE |
| | PREVIOUS REVIEW GAVE SOME AREAS OF EXAMPLES AND MANY |
| | LIGHTING FIXTURE TYPES IN SOME OF THOSE AREAS WERE |
| | ADJUSTED HOWEVER MANY AREAS WERE STILL NOT CHANGE OR |
| | THE FIXTURES WERE NOT ADJUSTED. |
| | |
| | A) PLEASE SEE THE PREVIOUS REVIEW MENTIONED TO PROVIDE |
| | PHOTO-METRICS FOR EGRESS PATHS HOWEVER NONE WERE |
| | SUBMITTED. PLEASE SEE THE AREAS OF STAIRS REQUIRE A |
| | LEVEL OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED |
| | DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. NFPA-101 |
| | 7.8.1.3, 7.9.2.2. |
| | THERE ARE NO SUBMITTED PHOTO-METRICS LEVELS FOR ANY |
| | EGRESS PATHS. PLEASE SUBMIT. PLANS NOW INCLUDE A NEW |
| | BATTERY BACK UNIT WAS NOW ADDED TO RISER FOR MOST OF |
| | THE CIRCUITS BUT NOT ALL. ONLY CIRCUITS 1L3, 23, 29, |
| | AND 33 ARE SHOWN YET THERE ARE OTHER CIRCUITS FOR |
| | OUTSIDE EGRESS LIGHTS WHICH ARE NOT SHOWN. PLEASE |
| | SUBMIT THE NEW SPECS/CUT SHEETS ON THIS PROPOSED UNIT. |
| | PLEASE INDICATE TIME IN EMERGENCY UNDER LOAD OF |
| | CIRCUITS. |
| | FAC 61G15-33.004. |
| | |
| | B) PLEASE SEE SOME EGRESS PATH HAD ALL LIGHT FIXTURES |
| | CHANGED TO BATTERY BACK UP FIXTURES. THIS WAS NOT THE |
| | REQUEST HOWEVER THIS IS NOT A CODE ISSUE. PLEASE SEE |
| | THERE ARE SEVERAL OTHER AREAS IN WHICH NO EMERGENCY |
| | LIGHTING FIXTURES WERE LOCATED. |
| | PLEASE SEE SOCIAL HALL, BASED ON THE FIXTURE LEGEND |
| | NONE OF THESE FIXTURES IN AREAS OF EGRESS ARE BATTERY |
| | BACK UP. |
| | PLEASE SEE SANCTUARY, BASED ON THE FIXTURE LEGEND NONE |
| | OF THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP. |
| | PLEASE SEE LOBBY AREAS, BASED ON FIXTURE LEGEND NONE OF |
| | THESE FIXTURES IN EGRESS AREAS ARE BATTERY BACK UP. |
| | PLEASE SEE CHAPEL, NONE OF THESE FIXTURES AREA BATTERY |
| | BACK UP BASED ON FIXTURE LEGEND AND THE OCCUPANCY LOAD |
| | OF THE ROOM CERTAINLY REQUIRES THIS. |
| | PLEASE SEE SOME HANDRAILS WHICH DO NOT SHOW ANY LIGHTS |
| | (NE CORNER) |
| | PLEASE SEE CHAPEL WHICH BASED ON LIFE SAFETY PLANS |
| | INDICATES EGRESS INTO COURTYARD AREA WHICH COULD NOT |
| | LOCATE BACK UP LIGHTING TO OUTDOOR EGRESS HALLWAYS. |
| | ONCE THE PHOTO-METRICS ARE SUBMITTED THE LIGHTING |
| | LEVELS IN THAT ARE MAY BE SUFFICIENT WITH THE BATTERY |
| | BACK UP OF THE *A* FIXTURES WHICH ARE ALL SHOWN AS |
| | BATTERY BACK UP. |
| | PLEASE SEE LIBRARY, NONE OF THESE FIXTURES BASED ON THE |
| | FIXTURE LEGEND INDICATES ANY OF THESE AS BATTERY BACK |
| | UP. BASED ON OCCUPANCY AND LOAD OF ROOM, THIS IS |
| | REQUIRED. |
| | PLEASE SEE EGRESS PATHS FROM BUILDING TO STAIRS, NO |
| | FIXTURES COULD BE LOCATED FOR ILLUMINATION OF PLATFORM |
| | AREAS. |
| | ** PLEASE SEE THERE ARE OTHER AREAS ON PLANS SHOW WHERE |
| | EVERY SINGLE FIXTURE WAS CHANGED TO BATTERY BACK UP. |
| | THIS OFFICE ONLY REQUESTED TO MEET THE LIFE SAFETY |
| | CODE. |
| | WAS THE INTENT ON PLANS FOR ALL *B* FIXTURES WHICH ARE |
| | IN CLASSROOMS, OFFICES, STORAGE ROOMS, CLOSETS ETC TO |
| | ALL BE BATTERY BACK UP? |
| | WAS IT INTENDED FOR ALL *A* FIXTURES TO BE BATTERY |
| | BACK? SOME LOCATIONS ARE CLEAR AS TO WHY THESE WOULD BE |
| | CHANGED HOWEVER IS IT NOT UNDERSTOOD WHY MOST AREAS |
| | WHICH REQUIRE BATTERY BACK UP FIXTURES DO NOT CONTAIN |
| | ANY AND THEN OTHER AREAS WHICH DO NOT REQUIRE ANY |
| | CONTAIN ALL FIXTURES AS BATTERY BACK UP. SOME OF THE |
| | *A* FIXTURES WERE CHANGED TO *AE* FIXTURES. |
| | ** THERE IS NOTHING IN THE CODE WHICH PROHIBITS |
| | DESIGNER TO DESIGN ALL FIXTURES IN A BUILDING BEING |
| | BATTERY BACK UP HOWEVER THE REQUIRED EGRESS PATHS MUST |
| | CONTAIN THE MINIMUM TO MEET THE 1FT CANDLE LEVEL. |
| | |
| | C) PLEASE SEE COMMENTS BELOW IN NOTE #5E WITH RESPECT |
| | TO OCCUPANCY SENSORS ON EGRESS LIGHTING. FBCAND LS |
| | CODE. |
| | |
| | AS THERE ARE STILL MANY QUESTIONS AND SOME ITEMS ARE |
| | MISSING CAN NOT REVIEW ALL FOR CODE COMPLIANCE AT THIS |
| | TIME. REVIEW CAN ONLY BE BASED ON PLANS SUBMITTED. |
| | |
| | 4) NOTE: PLEASE SEE THERE ARE SEVERAL SYMBOLS ON PLANS |
| | WHICH ARE NOT IN LEGEND FOR SYMBOLS, ARE NOT IN FIXTURE |
| | LEGEND AND DO NOT CONTAIN ANY CIRCUITING ETC. IT IS |
| | UNCLEAR WHAT MANY OF THESE ARE. |
| | PLEASE SEE SANCTUARY AREA WHICH CONTAINS A D IN A |
| | SQUARE BOX WHICH INDICATE 1INCH CONDUIT TO ER? PLEASE |
| | SEE LOBBY AREA WHICH ANOTHER CIRCLE SYMBOL WITH SQUARE |
| | BOX WHICH INDICATES TO ER, TO WPD? |
| | PLEASE SEE SOCIAL AREA WHICH CONTAINS THE SAME WHICH |
| | STATES TO ER, WPB? |
| | PLEASE BE SURE ALL SYMBOLS ON PLANS ARE ON LEGEND FOR |
| | WHAT THESE ARE. |
| | PLEASE SEE LIGHTING FIXTURES ON THE ELECTRICAL PLANS |
| | WHICH ARE NOT THE SAME AS THE FIXTURES SHOWN ON |
| | ARCHITECTURAL PLANS.(EXAMPLE: EXTERIOR) PLEASE KNOW |
| | AS THERE ARE OTHER COMMENTS ON ELECTRICAL PLANS AND |
| | WILL HAVE ADJUSTMENTS ON FIXTURES ETC PLEASE BE SURE |
| | THE INFORMATION IS FORWARDED TO THE ARCHITECT FOR |
| | COORDINATION. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO FBC |
| | AND CHAPTER 13. |
| | PLEASE SEE THE COMMENTS BELOW WILL BE IN SECTIONS AS |
| | PREVIOUS REVIEW AND THE INPUT DATA REPORT WILL BE NOTED |
| | AS IDR. |
| | |
| | A) PLEASE SEE THAT NOT ENOUGH DETAILS WERE SUBMITTED |
| | FOR MAIN AREAS FOR LIGHTING CONTROLS. NO DETAILS ON THE |
| | DEVICES, POWER PACKS, SCHEDULING OF PROPOSED, ZONES |
| | ETC. PLANS SHOW SOME NEW OCCUPANCY SENSOR TYPE DEVICES |
| | YET NOT ENOUGH INFORMATION ON THESE WAS PROVIDED. HOW |
| | WILL ALL AREAS BE CONTROLLED? |
| | FOR EXAMPLE: LOBBY AREAS, OVER RIDES, OCCUPANCY |
| | SENSORS, ACCENT LIGHTING, DISPLAY LIGHTING ETC. PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | B) PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED |
| | FOR EXTERIOR LIGHTING CONTROLS. PLANS SHOW A LIGHTING |
| | CONTACTOR AND SOME LOCATIONS NOTE THERE WILL BE A |
| | ASTRONOMICAL TIME CLOCK HOWEVER PLEASE SEE THE REQUIRED |
| | BATTERY BACK UP OF 10HRS IF PROPOSING A TC COULD NOT BE |
| | LOCATED. |
| | PLEASE SEE 13-415.1.ABC.1.4 ALSO 13-415.1.ABC.2 |
| | |
| | C) PLEASE SEE THE INFORMATION ON THE IDR DOES NOT |
| | CORRELATE WITH PLANS. PLEASE SEE THE EXTERIOR LIGHTING |
| | FOR EXAMPLE WHICH STATES ALL FIXTURES AS ONLY BEING 1. |
| | THIS IS NOT POSSIBLE WHEN THE ARE DOZENS OF FIXTURES ON |
| | PLANS FOR EACH TYPE. THE IDR REQUIRES EACH FIXTURE, |
| | EACH TYPE, AND METHOD OF CONTROL TO COORDINATE WITH |
| | PLANS. AT THIS TIME AS FIXTURES ARE ONLY INDICATE AS 1 |
| | (ONE) AT EACH LOCATION ON THE IDR,THE SPECIFIC |
| | FIXTURES, COUNTS ETC CAN NOT BE DETERMINED. |
| | |
| | D) PLEASE SEE THE IDR FOR ALL INTERIOR LIGHTS DOES NOT |
| | COORDINATE. PLEASE SEE THAT ALL LIGHTING IS REQUIRED TO |
| | BE FIGURED PER 13-415.2.ABC.1.1 AND .1.2 |
| | PLEASE SEE 13-415.2, 13-400 |
| | PLEASE KNOW AS THERE ARE FIXTURES ON THE IDR WHICH ARE |
| | NOT ON FIXTURE LEGEND AND FIXTURES ON THE FIXTURE |
| | LEGEND WHICH ARE NOT ON THE IDR. |
| | FOR EXAMPLE: |
| | 500W COMPACT FLUORESCENT FIXTURES ON IDR, NOT ON |
| | LEGEND. |
| | 250W ON FIXTURE LEGEND NOT ON IDR. |
| | PLEASE SEE FIXTURE COUNTS ON PLANS COMPARED TO FIXTURES |
| | IN AREAS ON THE IDR. |
| | ** PLEASE KNOW THERE ARE SEVERAL MORE WHICH DO NOT |
| | CORRELATE AND ONLY A COUPLE OF EXAMPLES ARE GIVEN. |
| | |
| | E) PLEASE SEE CORRIDOR 335 WHICH INDICATES ONE WALL |
| | DEVICE AT EACH END OF THIS LONG EGRESS PATH. PLEASE SEE |
| | FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 WITH RESPECT TO |
| | AUTOMATED DEVICES IN EGRESS PATHS. THIS IS PERMITTED BY |
| | BOTH CODES HOWEVER THE COVERAGE OF SUCH UNITS SHALL BE |
| | SUFFICIENT FOR ENTIRE LENGTH, THE DEVICES ARE REQUIRED |
| | TO BE 15MINS OF TIME AND PLANS SHOW 10MINS. |
| | PLEASE ALSO SEE THE DEVICES SHALL ALSO BE FAIL-SAFE ON |
| | DEVICES. THIS WOULD ALSO BE FOR OTHER AREAS WHERE |
| | OCCUPANCY SENSORS ARE BEING USED FOR EGRESS LIGHTING. |
| | |
| | F) PLEASE INCLUDE NOTES ON PLANS ARE REQUIRED PER |
| | 13-413.1.ABC.2, .2.1 AND .2.2 |
| | |
| | G) PLEASE BE SURE THE OWNER AGENT HAS FILLED OUT |
| | SECTION ON CERTIFICATION SHEET AND SIGNED WHEN NEW |
| | CALCULATIONS ARE SUBMITTED. |
| | 13-103.1.1.1 |
| | |
| | 6) NOTE: PLEASE BE SURE ALL EMERGENCY AND EXIT LIGHTS |
| | ARE CIRCUITED PER 700.12F. AS MOST FIXTURES IN MANY |
| | AREAS ARE ALL BATTERY BACK UP THIS IS OK, HOWEVER THIS |
| | NOTE REMAINS BASE DON THE FACT THERE ARE OTHER AREAS |
| | WHERE THERE ARE NO BATTERY BACK UP FIXTURES. |
| | |
| | 7) NOTE: PLEASE SEE FAC 61G15-33.004 WHICH REQUIRES ALL |
| | LIGHTING AND ILLUMINATION DESIGN TO BE PART OF THE |
| | RESPONSIBILITY OF THE DESIGN PROFESSIONAL. IF THERE ARE |
| | OTHER SHEETS WHICH WILL BE PART OF THE LIGHTING BEING |
| | SUBMITTED FOR SCOPE OF WORK REQUIRED BY A DESIGN |
| | PROFESSIONAL PLEASE BE SURE ALL SHEETS CONTAINS THE |
| | INFORMATION FROM THAT DESIGN PROFESSIONAL AND ARE |
| | SIGNED, DATED AND SEALED ACCORDINGLY. |
| | PLEASE SEE LIGHTING PLANS SUBMITTED BY LD INC. |
| | THE PREVIOUS REVIEW REQUESTED PHOTO-METRICS TO BE |
| | SUBMITTED FOR ALL EXTERIOR LIGHTING AREAS. HOWEVER |
| | PLEASE SEE PLANS WHICH SHOWS AREAS WITH 0.0 (NO) LEVELS |
| | OF LIGHTING. HOW IS THIS POSSIBLE WHEN THERE ARE DOZENS |
| | OF EXTERIOR LIGHTS ON PLANS? |
| | PLEASE COORDINATE ALL. |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | |
| | 8) NOTE: PLEASE SEE THE PREVIOUS REVIEW MENTIONED THE |
| | CONCERN OF THE MAIN ELECTRICAL EQUIPMENT AND OTHER |
| | ELECTRICAL PANELS IN A REQUIRED EGRESS HALLWAY. REVIEW |
| | COMMENT MENTIONED TO SEE POSSIBLE BUILDING AND FIRE |
| | REVIEW COMMENTS. |
| | THE RESPONSE MENTIONS NO CODES WERE LOCATED WHICH |
| | PREVENTED THIS. AT THIS TIME INFORMATION AND SCENARIOS |
| | WILL BE TURNED OVER TO THE BUILDING REVIEWER AND |
| | BUILDING OFFICIAL FOR CLARIFICATION ON WHETHER OR NOT |
| | THIS IS PERMITTED AND MOST OF ALL IF THIS IS SAFE FOR |
| | THE OCCUPANTS IN AN EMERGENCY SITUATION. THIS REVIEWER |
| | CAN NOT SEE HOW THIS IS NOT A HAZARD AND NEEDS |
| | DETERMINATION ON THIS SCENARIO. |
| | THE 1600AMP MDP PROTRUDES INTO A REQUIRED EGRESS HALL |
| | WAY. |
| | FBC 1001.3, 1001.4 |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 WHICH |
| | MENTIONED TO CLARIFY THE MDP1 AS SHOWN ON RISER AND |
| | SCHEDULE. |
| | PLEASE SEE THE RISER STILL CONTAINS NOTE WHICH STATES |
| | *MAIN DISCONNECT PANEL*. THIS PANEL BY THE SCHEDULE IS |
| | SHOWN AS A MAIN LUG ONLY SWITCHBOARD. |
| | PLEASE SEE THE CIRCUITING ON THIS PANEL WAS ALSO NOT |
| | UPDATED. FOR EXAMPLE: AS NOTED PREVIOUSLY: EXAMPLE; 1) |
| | PANEL 1L1 |
| | 3) |
| | 5) |
| | 7) PANEL 1L2 |
| | 9) |
| | 11) |
| | THIS IS AN EXAMPLE ONLY AS THIS IS STILL THREE PHASE |
| | EQUIPMENT. |
| | 408.4, FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL |
| | INFORMATION AND COORDINATION. |
| | |
| | 10) NOTE: PLEASE COORDINATE RISER AND PANELS. PLEASE |
| | SEE KITCHEN PANELS 1K1 AND 1K2 WHICH ARE BOTH SHOWN AS |
| | 400AMP ON RISER AND BEING FED FROM THE MAIN |
| | DISTRIBUTION BOARD WITH A 400AMP BREAKER. YET PLEASE |
| | SEE EACH OF THESE PANELS ARE SHOWN AS 200AMP MLO ON |
| | THEIR SCHEDULES WITH ONLY A SINGLE FEED OF 3/0 |
| | CONDUCTORS. |
| | PLEASE COORDINATE AND ADJUST. |
| | PLEASE ALSO SEE THE POWER PLANS DO NOT SHOW THE |
| | LOCATION OF THESE PANELS. SHEET E-5.0 MENTIONS TO SEE |
| | SHEET E-11.0 FOR THE ENLARGED KITCHEN PLANS. IT WAS |
| | BEING ASSUMED THESE PANEL WERE IN THE KITCHEN HOWEVER |
| | COULD NOT LOCATE THESE ANYWHERE ON PLANS. |
| | SHEET E-6.0 ALSO DOES NOT SHOW THESE K PANELS. 240.24, |
| | 110.26, 408.17, 240.4, 310.16, ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | |
| | 11) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO AIC |
| | RATINGS FOR ALL PANELS, BREAKER AND SERVICE EQUIPMENT. |
| | THE MAIN SWITCH BOARD DOES NOW INDICATE THE BRANCH |
| | CIRCUIT RATINGS AS 65K RATED AND MAIN AT 100K. HOWEVER |
| | PLEASE SEE OTHER PANELS WHICH SHOW ONE AIC RATING FOR |
| | BOARD AND BREAKERS STILL. |
| | PLEASE VERIFY FOR EXAMPLE ALL PANELS SHOWING A 65K |
| | RATING FOR PANELS AND BRANCH BREAKERS THIS IS WITH THE |
| | EXCEPTION OF PANEL 1K1 WHICH SHOWS A 10K RATING. 110.9, |
| | 110.3 |
| | FBC106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 12) NOTE: PLEASE KNOW THE SIGNED AND SEALED STRUCTURAL |
| | WIND LOAD CALCULATIONS SHOWING THE EPA (EFFECTIVE |
| | PROJECTED AREAS) OF LIGHT FIXTURES ON POLES WILL BE |
| | REVIEWED BY THE BUILDING REVIEWER. |
| | |
| | 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | PLEASE BE SURE TO GO OVER ALL COMMENTS AND ONCE AGAIN |
| | PLEASE CALL. PLEASE LEAVE PHONE NUMBER WHEN LEAVING A |
| | MESSAGE. |
| | ** PLEASE ALSO KNOW THAT AT THIS TIME ONE SET OF |
| | ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE BEING |
| | RETAINED BY THIS OFFICE. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| 2008-02-16 07:59:23 | 2008-02-16 07:059:23 |
| | |
| | IN REVIEW |
| 2008-02-15 19:34:00 | |
| | 2008-02-15 15:35:24 |
| | REVIEW COMMENCED |
| | |
| | 2008-02-15 19:34:00 |
| | REVIEW STOPPED. WILL CONTINUE ON 2/16, NOTES WILL |
| | FOLLOW AND PLANS WILL BE IN A *FAILED STATUS* |
| | |
| | |
| 2008-02-14 19:24:52 | 2008-02-14 19:24:52 |
| | |
| | IN ELEC FOR REVIEW |