2008-03-18 08:56:12****CORRECTIONS****
 ****REVISED 3/18/8***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME
 FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE
 PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL
 DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL
 SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6.
  
 4.)PROVIDE THE THRESHOLD INSPECTION PLAN.THE
 APPROVED CONTRACT WITH THE THRESHOLD INSPECTOR WILL BE
 REQUIRED IN THE PERMIT PACKAGE PRIOR TO PERMIT
 ISSUANCE.
  
 2ND REVIEW; I WAS UNABLE TO LOCATE THE COMPLIANCE
 STATEMENT AS REQUIRED BY FS553.79(7)(D).THIS IS
 REQUIRED FOR THE ARCHITECT AND ENGINEER.PLEASE ADVISE
 AS TO LOCATION OF THIS STATEMENT.
  
 NOTE THAT THE THRESHOLD INSPECTION PLAN IS TYPICALLY
 INCORPORATED INTO THE PLAN BY THE ARCHITECT IN ADDITION
 TO BEING A PART OF THE CONTRACT BETWEEN THE OWNER, THE
 INSPECTOR, AND THE CITY.
  
 5.)ADDRESSED.
  
 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD
 ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED
 (INFORMATIONAL ONLY).
  
 7.)ADDRESSED.
  
 8.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 SHEETS FS 1, 2, AND 3 WERE ADDED.HOWEVER, THEY DO NOT
 SHOW SPRINKLER HEAD LAYOUT, ONLY HAZARD CLASSIFICATION
 PER NFPA.PLEASE PROVIDE PLANS AS REQUIRED.
  
 9-24.) ADDRESSED.
  
 25.)THE GATES ARE REQUIRED TO BE ACCESSIBLE,
 FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS.PROVIDE A
 DETAIL TO SHOW COMPLIANCE.
  
 THE RESPONSE LETTER STATES THAT A10.1 SHOWS THIS
 HARDWARE GROUP AS ACCESSIBLE.SEE HARDWARE GROUP 13
 AND 14; I AM UNABLE TO DISCERN FROM THE DESCRIPTION
 THAT THIS IS ACCESSIBLE HARDWARE.PLEASE CLARIFY,
 EITHER BY REVISING THE DESCRIPTION OR INCLUDING SPEC
 SHEETS FOR THE GATE HARDWARE.
  
 26-36.) ADDRESSED.
  
 37.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 38.)ADDRESSED.
  
 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE
 ROOF PRODUCT APPROVAL.
  
 NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING
 CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION.
  
 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN
 ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS,
 WWW.FLORIDABUILDING.ORG
  
 41.)FOR THE EXCLUSIVE WOOD DOORS AND THE REPUBLIC
 DOORS, PRINT THE FLORIDA STATE PRODUCT APPROVAL,
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FROM
 THE INTERNET.
  
 NOT ADDRESSED.THE PAPERWORK PROVIDED SHOWS A DESIGN
 PRESSURE OF +-47, SEE SHEET S10, 59.2 REQUIRED.
  
 42.)FOR THE REPUBLIC DOORS, MARK WHICH PRODUCT(S) YOU
 ARE INSTALLING.
  
 2ND REVIEW, FL4304 WAS CIRCLED.PLEASE GO TO THE
 WEBSITE, WWW.FLORIDABUILDING.ORG, AND PRINT THE PRODUCT
 APPROVAL.CONFIRM THAT THE SUPPLEMENTARY DOCUMENTATION
 (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) MATCHES
 THE ONES ON THE INTERNET.NOTE THAT FL4304 (CIRCLED ON
 THE LIST OF MANUFACTURER?S PRODUCTS) HAS A DESIGN
 PRESSURE OF 114, BUT THE PAPERWORK IS FOR A DOOR WITH A
 DESIGN PRESSURE OF 60PSF.IT DOES NOT APPEAR TO BE THE
 SAME DOOR.
  
 43.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE
 LETTER STATING HOW AND WHERE EACH ITEM WAS ADDRESSED.
  
 NEW COMMENTS:
  
 44.)SHOW ALL REQUIRED DETECTABLE WARNINGS,
 FBC11-4.29.5.
  
 45.)A SECOND EXIT DOOR WAS ADDED TO THE CHAPEL.SEE
 LANDSCAPE SHEETS.THE LANDSCAPE PLANS WERE NOT REVISED
 TO REFLECT FLOOR PLAN CHANGES TO THE CHAPEL AND THE
 OFFICE AREA.IT APPEARS THAT THIS DOOR OPENS ONTO AN
 AREA WHICH IS NOT PAVED AND HAS AN IRRIGATION HEAD AT
 THIS LOCATION.SEE FBC1008.1.5, DOOR LANDING REQUIRED,
 AND FBC1003.4, FLOOR SURFACE.
  
 46.)A1.1, SEE FBC 1024.10, AISLE ACCESSWAYS.SHOW
 MINIMUM REQUIRED WIDTH.
  
 47.)PLEASE SHOW OCCUPANT LOAD SERVED BY THE DOUBLE
 GATES, ADJACENT TO CLASSROOM 331.SEE FBC1008.1.2. THE
 PATH OF EGRESS IS SHOWN AS GOING TOWARDS THE ASSEMBLY
 AREA RATHER THAN TOWARDS THE PARKING LOT. PLEASE
 EXPLAIN THE LOGIC AS IT APPEARS THAT THE EGRESS PATH
 WILL MOST LIKELY BE GOING TOWARDS THE PARKING LOT AREA.
 IT ALSO APPEARS THAT, IF USED, OCCUPANT LOAD WHICH
 THESE GATES SERVE MAY BE GREATER THAN 50.CAN THESE
 GATES SWING BOTH DIRECTIONS (180 DEGREE SWING RATHER
 THAN 90DEGREE AS SHOWN)?
  
 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS
 AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE
 REVIEW.
  
 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN
 ON A4.0, FAC9B72.
  
 50.)PLEASE CORRELATE A9 AND S10.FOR INSTANCE,
 OPENINGS 1 AND 2 ARE SHOWN AS 2X8 ON A9, 1FT8IN X
 7FT8IN ON S10.ARE THE OPENINGS THE SAME?IF NOT,
 PLEASE CORRELATE.
  
 51.)INFORMATIONAL ONLY; S10 HAS TWO SETS OF DESIGN
 PRESSURES, ZONE 4 AND ZONE 5.ALL PRODUCT APPROVALS
 WILL BE REVIEWED TO THE MOST STRINGENT.IF THIS IS NOT
 ACCEPTABLE, PLEASE REVISE SO THAT ONLY ONE NEGATIVE
 DESIGN PRESSURE IS INCLUDED FOR EACH OPENING.
  
 52.ELECTRIC SHEETS ARE MISSING FROM THE SET WHICH WAS
 REVIEWED FOR BUILDING.WHEN RESUBMITTING, PLEASE
 CONFIRM THAT EACH SET IS COMPLETE AND IDENTICAL.
  
 53.ON A1.1, THERE ARE DARK LINES ACROSS THE AREA
 WHERE THE PEW AISLES CONVERGE, ADJACENT TO THE STAGE.
 WHAT ARE THESE LINES?
  
 54.)WHEN RESUBMITTING, PLEASE CLOUD ALL CHANGES.