| 2008-03-18 08:56:12 | ****CORRECTIONS**** |
| | ****REVISED 3/18/8*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS FROM PREVIOUS LIST, NUMBERING REMAINS THE SAME |
| | FOR CONSISTENCY |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE |
| | PERMIT APPLICATION. |
| | |
| | 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN |
| | FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA |
| | (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A |
| | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB |
| | INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE |
| | PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL |
| | DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL |
| | SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6. |
| | |
| | 4.)PROVIDE THE THRESHOLD INSPECTION PLAN.THE |
| | APPROVED CONTRACT WITH THE THRESHOLD INSPECTOR WILL BE |
| | REQUIRED IN THE PERMIT PACKAGE PRIOR TO PERMIT |
| | ISSUANCE. |
| | |
| | 2ND REVIEW; I WAS UNABLE TO LOCATE THE COMPLIANCE |
| | STATEMENT AS REQUIRED BY FS553.79(7)(D).THIS IS |
| | REQUIRED FOR THE ARCHITECT AND ENGINEER.PLEASE ADVISE |
| | AS TO LOCATION OF THIS STATEMENT. |
| | |
| | NOTE THAT THE THRESHOLD INSPECTION PLAN IS TYPICALLY |
| | INCORPORATED INTO THE PLAN BY THE ARCHITECT IN ADDITION |
| | TO BEING A PART OF THE CONTRACT BETWEEN THE OWNER, THE |
| | INSPECTOR, AND THE CITY. |
| | |
| | 5.)ADDRESSED. |
| | |
| | 6.)ADDRESSED; THE PLANS WILL BE STAMPED WITH A5 FLOOD |
| | ZONE DESIGNATION, FORM BOARD SURVEY REQUIRED |
| | (INFORMATIONAL ONLY). |
| | |
| | 7.)ADDRESSED. |
| | |
| | 8.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| | FS553.79 (2). |
| | |
| | SHEETS FS 1, 2, AND 3 WERE ADDED.HOWEVER, THEY DO NOT |
| | SHOW SPRINKLER HEAD LAYOUT, ONLY HAZARD CLASSIFICATION |
| | PER NFPA.PLEASE PROVIDE PLANS AS REQUIRED. |
| | |
| | 9-24.) ADDRESSED. |
| | |
| | 25.)THE GATES ARE REQUIRED TO BE ACCESSIBLE, |
| | FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS.PROVIDE A |
| | DETAIL TO SHOW COMPLIANCE. |
| | |
| | THE RESPONSE LETTER STATES THAT A10.1 SHOWS THIS |
| | HARDWARE GROUP AS ACCESSIBLE.SEE HARDWARE GROUP 13 |
| | AND 14; I AM UNABLE TO DISCERN FROM THE DESCRIPTION |
| | THAT THIS IS ACCESSIBLE HARDWARE.PLEASE CLARIFY, |
| | EITHER BY REVISING THE DESCRIPTION OR INCLUDING SPEC |
| | SHEETS FOR THE GATE HARDWARE. |
| | |
| | 26-36.) ADDRESSED. |
| | |
| | 37.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, |
| | FBC13-103.1. |
| | |
| | 38.)ADDRESSED. |
| | |
| | 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE |
| | ROOF PRODUCT APPROVAL. |
| | |
| | NOT ADDRESSED.THIS CAN BE DONE BY THE ROOFING |
| | CONTRACTOR AT THE TIME OF ROOF PERMIT APPLICATION. |
| | |
| | 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN |
| | ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE |
| | PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A |
| | LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA. |
| | |
| | PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVALS, |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 41.)FOR THE EXCLUSIVE WOOD DOORS AND THE REPUBLIC |
| | DOORS, PRINT THE FLORIDA STATE PRODUCT APPROVAL, |
| | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FROM |
| | THE INTERNET. |
| | |
| | NOT ADDRESSED.THE PAPERWORK PROVIDED SHOWS A DESIGN |
| | PRESSURE OF +-47, SEE SHEET S10, 59.2 REQUIRED. |
| | |
| | 42.)FOR THE REPUBLIC DOORS, MARK WHICH PRODUCT(S) YOU |
| | ARE INSTALLING. |
| | |
| | 2ND REVIEW, FL4304 WAS CIRCLED.PLEASE GO TO THE |
| | WEBSITE, WWW.FLORIDABUILDING.ORG, AND PRINT THE PRODUCT |
| | APPROVAL.CONFIRM THAT THE SUPPLEMENTARY DOCUMENTATION |
| | (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) MATCHES |
| | THE ONES ON THE INTERNET.NOTE THAT FL4304 (CIRCLED ON |
| | THE LIST OF MANUFACTURER?S PRODUCTS) HAS A DESIGN |
| | PRESSURE OF 114, BUT THE PAPERWORK IS FOR A DOOR WITH A |
| | DESIGN PRESSURE OF 60PSF.IT DOES NOT APPEAR TO BE THE |
| | SAME DOOR. |
| | |
| | 43.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE |
| | LETTER STATING HOW AND WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 44.)SHOW ALL REQUIRED DETECTABLE WARNINGS, |
| | FBC11-4.29.5. |
| | |
| | 45.)A SECOND EXIT DOOR WAS ADDED TO THE CHAPEL.SEE |
| | LANDSCAPE SHEETS.THE LANDSCAPE PLANS WERE NOT REVISED |
| | TO REFLECT FLOOR PLAN CHANGES TO THE CHAPEL AND THE |
| | OFFICE AREA.IT APPEARS THAT THIS DOOR OPENS ONTO AN |
| | AREA WHICH IS NOT PAVED AND HAS AN IRRIGATION HEAD AT |
| | THIS LOCATION.SEE FBC1008.1.5, DOOR LANDING REQUIRED, |
| | AND FBC1003.4, FLOOR SURFACE. |
| | |
| | 46.)A1.1, SEE FBC 1024.10, AISLE ACCESSWAYS.SHOW |
| | MINIMUM REQUIRED WIDTH. |
| | |
| | 47.)PLEASE SHOW OCCUPANT LOAD SERVED BY THE DOUBLE |
| | GATES, ADJACENT TO CLASSROOM 331.SEE FBC1008.1.2. THE |
| | PATH OF EGRESS IS SHOWN AS GOING TOWARDS THE ASSEMBLY |
| | AREA RATHER THAN TOWARDS THE PARKING LOT. PLEASE |
| | EXPLAIN THE LOGIC AS IT APPEARS THAT THE EGRESS PATH |
| | WILL MOST LIKELY BE GOING TOWARDS THE PARKING LOT AREA. |
| | IT ALSO APPEARS THAT, IF USED, OCCUPANT LOAD WHICH |
| | THESE GATES SERVE MAY BE GREATER THAN 50.CAN THESE |
| | GATES SWING BOTH DIRECTIONS (180 DEGREE SWING RATHER |
| | THAN 90DEGREE AS SHOWN)? |
| | |
| | 48.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER |
| | OF RECORD, (SHOP DRAWING REVIEW STAMP OR LETTER), |
| | FBC*106.3.3.SHEET A9 SPECIFIES MOST OF THE COMPONENTS |
| | AND CLADDING.HOWEVER, FOR OTHER ITEMS, PLEASE |
| | REVIEW. |
| | |
| | 49.)PROVIDE PRODUCT APPROVAL FOR THE SKYLIGHTS SHOWN |
| | ON A4.0, FAC9B72. |
| | |
| | 50.)PLEASE CORRELATE A9 AND S10.FOR INSTANCE, |
| | OPENINGS 1 AND 2 ARE SHOWN AS 2X8 ON A9, 1FT8IN X |
| | 7FT8IN ON S10.ARE THE OPENINGS THE SAME?IF NOT, |
| | PLEASE CORRELATE. |
| | |
| | 51.)INFORMATIONAL ONLY; S10 HAS TWO SETS OF DESIGN |
| | PRESSURES, ZONE 4 AND ZONE 5.ALL PRODUCT APPROVALS |
| | WILL BE REVIEWED TO THE MOST STRINGENT.IF THIS IS NOT |
| | ACCEPTABLE, PLEASE REVISE SO THAT ONLY ONE NEGATIVE |
| | DESIGN PRESSURE IS INCLUDED FOR EACH OPENING. |
| | |
| | 52.ELECTRIC SHEETS ARE MISSING FROM THE SET WHICH WAS |
| | REVIEWED FOR BUILDING.WHEN RESUBMITTING, PLEASE |
| | CONFIRM THAT EACH SET IS COMPLETE AND IDENTICAL. |
| | |
| | 53.ON A1.1, THERE ARE DARK LINES ACROSS THE AREA |
| | WHERE THE PEW AISLES CONVERGE, ADJACENT TO THE STAGE. |
| | WHAT ARE THESE LINES? |
| | |
| | 54.)WHEN RESUBMITTING, PLEASE CLOUD ALL CHANGES. |