| Date |
Text |
| 2007-11-09 18:49:38 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS L-1, L-2, I-1, I-2 & I-3 THE ADDRESS OF RECORD |
| | ON THE FLORIDA STATE DBPR WEBSITE FOR THE LANDSCAPE |
| | ARCHITECT DOES NOT REFLECT THE ADDRESS ON THE TITLE |
| | BLOCK. PLEASE UPDATE THE DPBR WEBSITE OR THE TITLE |
| | BLOCKS PRIOR TO RESUBMITTING FOR REVIEW. FAC |
| | 61G1-16.004(1) & FS 481.306. |
| | |
| | 2. SHT A-1.0 THE COMPLETE FIRM NAME IS REQUIRED IN THE |
| | TITLE BLOCK. FAC 61G1-16.004(1) & FS 481.2055. |
| | |
| | 3. SHT A-1.0 BECAUSE OF MULTIPLE OCCUPANCIES, |
| | (BUSINESS, ASSEMBLY, MERCANTILE, & POSSIBLY EDUCATION, |
| | (DEPENDING ON THE AGE OF THE STUDENTS & TYPE OF CLASS |
| | ROOM EDUCATION), CALCULATIONS FOR MINIMUM FACILITIES IS |
| | REQUIRED. TABLES 1004.1.2 & 104.3.1 & SECTION 302.2.1. |
| | ALSO POTTY PARITY SHALL BE ADDRESSED AND REQUIRED PER |
| | SECTION 403.1.1. |
| | |
| | 4. SHT A-1.0 SHOWS A SECONDARY KITCHEN. THE GREASE |
| | INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT., |
| | INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE. |
| | PLEASE CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL |
| | [email protected] OR CALVIN WILLIAMS (561) 822-2284, |
| | E-MAIL [email protected]. THEIR FAX NUMBER IS (561) |
| | 822-2287. THEY WILL ISSUE A WRITTEN DETERMINATION FOR |
| | THE SIZE & LOCATION OF THE GREASE INTERCEPTOR OF WHICH |
| | A COPY WILL BE SUBMITTED WITH THE PLANS WHEN |
| | RESUBMITTING FOR REVIEW. |
| | |
| | 5. SHT A-2.0 WHERE SIX OR MORE STALLS ARE PROVIDED, IN |
| | ADDITION TO THE STALL COMPLYING WITH SECTION 11-4.17.3, |
| | AT LEAST ONE STALL 36 INCHES WIDE WITH AN OUTWARD |
| | SWINGING, SELF-CLOSING DOOR AND PARALLEL GRAB BARS |
| | COMPLYING WITH FIG. 30(D)AND SECTION 11-4.26 SHALL BE |
| | PROVIDED. SECTION 11-4.22.4. |
| | |
| | 6. SHT A-2.1 TOILET ROOMS 208 & 209. AN UNOBSTRUCTED |
| | TURNING SPACE COMPLYING WITH SECTION 11-4.2.3 SHALL BE |
| | PROVIDED WITHIN AN ACCESSIBLE TOILET ROOM. SECTION |
| | 11-4.22.3. |
| | |
| | 7. SHT A-2.1 THE TOILET ROOM ADJACENT TO THE BRIDAL |
| | ROOM SHALL BE ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH |
| | SECTION 11-4.22 WITH ALL SUBSECTIONS. |
| | |
| | 8. SHT A-1.0 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE AREA OF |
| | EACH ROOF DRAIN, PLUS 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS, AS WELL AS ANY AREA OF A ROOF THAT |
| | DRAINS ONTO THE ROOF FROM ABOVE, (IF APPLICIABLE). |
| | |
| | 9. SHT A-7.0 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | ___FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | C. 11-4.19.5 FAUCETS |
| | WATER CLOSETS SHALL BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE. FIGURE 28. |
| | |
| | 10. SHT A-7.0 DETAIL 3, BATHROOM SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH 11-4.16, 11-4.19, 11-4.21 & |
| | 11-4.23 WITH ALL SUBSECTIONS AND FIGURES. |
| | |
| | 11. SHT A-7.0 DETAIL 5. THE TOILET ROOMS SHALL BE |
| | ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.17,11-4.19 & 11-4.22 WITH ALL |
| | SUBSECTIONS AND FIGURES. W/C'S TO BE 18" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE. FIGURE 28. |
| | |
| | 12. SHT A-7.0 ALL DETAILS 1 THRU 5. SHOW COMPLIANCE |
| | WITH SECTION 1210.2. THE WALLS WITHIN 2FT OF THE W/C'S |
| | AND URINALS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE UP TO 4FT ABOVE THE FLOOR.LEGEND TOILET ROOM |
| | ACCESSORIES W-1 INDICATES WAINSCOAT 36" HIGH BUT DETAIL |
| | 4 SHOWS TILE TO CEILING. PLEASE CLAIRFY AND CORRELATE. |
| | |
| | 13. SHT A-7.1 DETAIL 1 SHOW THE TURNING AREA IN THE |
| | TOILET ROOM. (NOT REQUIRED IN THE STALL). SECTION |
| | 11-4.22.3.--SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | ___FOR URINALS: |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | DETAILS 1 & 2 SHOW THE FOLLOWING: |
| | ___FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS |
| | |
| | 14. SHT A-7.1 ALL DETAILS. SHOW COMPLIANCE WITH SECTION |
| | 1210.2. WALLS WITHIN 2FT OF WATERCLOSETS AND URINALS |
| | SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. |
| | |
| | 15. SHT A-7.1 DETAILS 2 & 5 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS |
| | |
| | 16. SHT A-7.1 DETAIL 6 TOILET ROOM SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & |
| | 11-4.22 WITH ALL SUBSECTIONS AND FIGURES. |
| | |
| | 17. SHT A-7.2 DETAILS 4 & 5 LOUNGE SINK SHALL BE |
| | ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH |
| | ALL SUBSECTIONS. |
| | |
| | 18. SHTS S-1 THRU S-10 THE PRINTED NAME AND LICENSE |
| | NUMBER SHALL BE LEGIBLY PRINTED IN THE TITLE BLOCKS OF |
| | ALL SHEETS. FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | 19. SHT P1.0 SHOWS CONDENSATE TO DISCHARGE 6" ABOVE THE |
| | SIDEWALK. THIS IS NOT APPROVED. CONDENSATE SHALL |
| | CONNECT TO A DRYWELL, STORM CATCH BASIN, PLANTED AREA |
| | OR CONNECT TO A STORM DRAINAGE LINE OUTSIDE THE |
| | BUILDING. IF CONNECTING TO A STORM LINE, A RELIEF VENT, |
| | (GOOSENECK), SHALL BE REQUIRED AS THE CONDENSATE EXITS |
| | THE BUILDING. CONDENSATE DRAINAGE CAN NOT CREATE A |
| | HAZARD OR NUISANCE. SECTION 314.2.1. |
| | |
| | 20. SHT P-1.0 STORM DRAINAGE IS SHOWN TO CONNECT TO |
| | STORMWATER DRAINAGE SYSTEM. "REFER TO CIVIL PLANS FOR |
| | CONT". PLESE CLARIFYAS THE STORMWATER DRAINAGE SYSTEM |
| | IS NOT SHOWN ON THE CIVIL PLANS. SECTION 106.1.1. |
| | |
| | 21. SHT P-1.0 SHOW THE HOT AND COLD WATER PIPING ON THE |
| | FLOOR PLAN. SECTION 106.3.5.1.3(3)(10). |
| | |
| | 22. SUBMIT A WATER ISOMETRIC WATER RISER DIAGRAM FROM |
| | METER, THRU RPZV BACKFLOW, TO THE MOST REMOTE FIXTURE |
| | SHOWING ALL PIPE SIZES, VALVES, OFFSETS, & WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9. WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. SECTION |
| | 106.3.5.1.3(3)(10)(13). |
| | |
| | 23. SHT P-2.0 SHOW THE HOT & COLD WATER PIPING ON THE |
| | FLOOR PLAN. SECTION 106.3.5.1.3(3)(10). |
| | |
| | 24. SHT P-3.0 BACKFLOW PROTECTION IS REQUIRED ON THE |
| | WATER LINES TO THE WATER FOUNTAINS. A VACUUM BREAKER AT |
| | THE HIGHEST POINT OF THE SUPPLY LINE TO THE FOUNTAINS |
| | WILL BE SUFFICIENT. SECTION 608. |
| | |
| | 25. SHT P-3.0 CONDENSATE LINES SHOW BACKWATER VALVES. |
| | PER SECTION 715.1 FIXTURES ABOVE THE ELEVATION OF THE |
| | MANHOLE SHALL NOT DISCHARGE THRU A BACKWATER VALVE. |
| | WHERE THE POSSIBILITY OF A BACKUP MAY OCCUR, A RELIEF |
| | VENT, (GOOSENECK) , SHALL BE INSTALLED AS THE |
| | CONDENSATE EXITS THE BUILDING. |
| | |
| | 26. SHT P-3.0 NOTE AT THE WATER HEATER INDICATES THE P |
| | & T RELIEF VALVE AND EM PAN DRAIN LINE TO BE ROUTED TO |
| | A FLOOR DRAIN VIA INDIRECT WASTE. FLOOR DRAINS ARE NOT |
| | APPROVED INDIRECT WASTE RECEPTORS. SECTION 802.3. SINCE |
| | AN EMERGENCY PAN IS NOT REQUIRED ON THE FIRST FLOOR PER |
| | SECTION 504.7 AND THE P & T CAN DISCHARGE ONTO THE |
| | FLOOR,THEY ARE NOT REQUIRED TO BE PIPED TO AN |
| | INDIRECT WASTE RECEPTOR SO A FLOOR DRAIN WILL BE OK IN |
| | THE ROOM BUT NOT AS AN INDIRECT WASTE RECEPTOR. |
| | |
| | 27. SUBMIT A DETAIL FOR THE WATER HEATER. SHOW |
| | COMPLIANCE WITH SECTIONS 503.1, (SHUT OFF VALVE), |
| | SECTION 504.2, (IF BOTTOM FED W/H), 504.4, (RELIEF |
| | VALVE), 504.6.1, (DISCHARGE), 504.6.2, (MATERIALS) AND |
| | SECTION 607.3.2 (THERMAL EXPANSION CONTROL) |
| | |
| | 28. SHT P-4.0 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. (SEE COMMENT # 8). A CHECK ON |
| | TWO ROOF AREAS, ROOF DRAINS #7 & #10 DO NOT SEEM TO |
| | INCLUDE ALL SQUARE FOOTAGE FOR THE ROOF AREAS AND/OR |
| | VERTICAL CONTRIBUTION. EXAMPLE ROOF DRAIN#7 AREA IS |
| | SHOWN AS 1,304SF, BUT A CHECK OF THE AREA INDICATES |
| | 1,666SF AND THE ROOF DRAIN #10 AREA IS SHOWN AS 1,962SF |
| | BUT A CHECK OF THE AREA INDICATES 2,322SF. PLEASE |
| | SUBMIT THE CALCULATIONS SHOWING INFORMATION REQUESTED |
| | IN COMMENT #8. SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. |
| | |
| | 29. SHT P-5.0 SHOW THE GAS LINE UP TO THE MATCH LINE ON |
| | THE FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 30. SHT P-5.0 THE DISHWASHER, (P-49), SHALL DISCHARGE |
| | INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM PER |
| | ARTICLE III SECTION 90-124(7)(B). PLEASE CONNECT |
| | DISHWASHER TO SANITARY. |
| | |
| | 31. SUBMIT STORM ISOMETRIC RISER DIAGRAMS FOR ALL ROOF |
| | DRAINS AND SECONDARY ROOF DRAINS THAT REFLECT THE FLOOR |
| | PLAN. SHOW ALL PIPE SIZES, OFFSETS AND INDICATE SQUARE |
| | FOOTAGE BEING DRAINED BY EACH ROOF DRAIN. SECTION |
| | 106.3.5.1.3(7)(13).--SHOW CLEANOUTS REQUIRED BY |
| | SECTION 1101.8. |
| | |
| | 32. SUBMIT CONDENSATE ISOMETRIC RISER DIAGRAMS FOR ALL |
| | CONDENSATE RISERS THAT REFLECT THE FLOOR PLAN. SHOW |
| | PIPE SIZES. OFFSETS AND INDICATE MATERIAL FOR SYSTEM. |
| | NO PVC IN PLENUMS. |
| | |
| | 33. SHT P-6.0 PLUMBING GENERAL SPECIFICATIONS 1509(G) |
| | AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE AIR |
| | CHAMBERS FROM REFLENCE. SECTION 604.9 AND PDI-WH 201. |
| | |
| | 34. SUBMIT A WATER ISOMETRIC RISER DIAGRAM THAT |
| | REFLECTS THE FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES, |
| | (FULL OPEN & SHUT OFF), SECTIONS 606.1 & 606.2, |
| | OFFSETS, AND WATER HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.6, (DISHWASHER, WASH MACHINE, ICE MAKER ETC). WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN |
| | AN "EFFECTIVE RANGE" NOT IN THE CEILING PER PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | 35. SHT P-7.0 KITCHEN EQUIPMENT PLUMBING SCHEDULE ITEM |
| | P-58 INDICATES 1-1/2" SANITARY WASTE. A MINIMUM 2" |
| | P-TRAP IS REQUIRE PER TABLE 709.1. NOTE INDICATES FS-2 |
| | AT THE WASH MACHINE, BUT SHOWS DIRECT CONNECTION TO THE |
| | SANITARY SYSTEM. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 36. SHT P-10.0 THE VENTING FOR TOILET ROOMS 316 & 317 |
| | DO NOT SHOW VENT THRU ROOF AS REQUIRED IN SECTION |
| | 903.3. PLEASE CLARIFY. |
| | |
| | 37. SHT P-11.0 SANITARY RISER DIAGRAM THE DISH WASHER |
| | SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT THE |
| | GREASE SYSTEM. ARTICLE III SECTION 90-124(7)(B). PLEASE |
| | CONNECT DISHWASHER TO SANITARY. |
| | |
| | 38. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED TO SECURE A PERMIT. |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO |
| | THE MOST REMOTE APPLIANCE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). GAS APPLIANCE SCHEDULE |
| | NOTE #4 INDICATES TABLE 402.4(24) WHICH IS LP GAS. |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM |
| | THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON |
| | THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES |
| | 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING |
| | ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC |
| | SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE |
| | CLARIFY. |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. -- FOR W/H. |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | G. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | H. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE |
| | REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT |
| | THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE |
| | REGULATOR. |
| | |
| | K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4. |
| | --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE |
| | SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |