2007-11-09 18:49:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS L-1, L-2, I-1, I-2 & I-3 THE ADDRESS OF RECORD
 ON THE FLORIDA STATE DBPR WEBSITE FOR THE LANDSCAPE
 ARCHITECT DOES NOT REFLECT THE ADDRESS ON THE TITLE
 BLOCK. PLEASE UPDATE THE DPBR WEBSITE OR THE TITLE
 BLOCKS PRIOR TO RESUBMITTING FOR REVIEW. FAC
 61G1-16.004(1) & FS 481.306.
  
 2. SHT A-1.0 THE COMPLETE FIRM NAME IS REQUIRED IN THE
 TITLE BLOCK. FAC 61G1-16.004(1) & FS 481.2055.
  
 3. SHT A-1.0 BECAUSE OF MULTIPLE OCCUPANCIES,
 (BUSINESS, ASSEMBLY, MERCANTILE, & POSSIBLY EDUCATION,
 (DEPENDING ON THE AGE OF THE STUDENTS & TYPE OF CLASS
 ROOM EDUCATION), CALCULATIONS FOR MINIMUM FACILITIES IS
 REQUIRED. TABLES 1004.1.2 & 104.3.1 & SECTION 302.2.1.
 ALSO POTTY PARITY SHALL BE ADDRESSED AND REQUIRED PER
 SECTION 403.1.1.
  
 4. SHT A-1.0 SHOWS A SECONDARY KITCHEN. THE GREASE
 INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT.,
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected] OR CALVIN WILLIAMS (561) 822-2284,
 E-MAIL [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. THEY WILL ISSUE A WRITTEN DETERMINATION FOR
 THE SIZE & LOCATION OF THE GREASE INTERCEPTOR OF WHICH
 A COPY WILL BE SUBMITTED WITH THE PLANS WHEN
 RESUBMITTING FOR REVIEW.
  
 5. SHT A-2.0 WHERE SIX OR MORE STALLS ARE PROVIDED, IN
 ADDITION TO THE STALL COMPLYING WITH SECTION 11-4.17.3,
 AT LEAST ONE STALL 36 INCHES WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND PARALLEL GRAB BARS
 COMPLYING WITH FIG. 30(D)AND SECTION 11-4.26 SHALL BE
 PROVIDED. SECTION 11-4.22.4.
  
 6. SHT A-2.1 TOILET ROOMS 208 & 209. AN UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH SECTION 11-4.2.3 SHALL BE
 PROVIDED WITHIN AN ACCESSIBLE TOILET ROOM. SECTION
 11-4.22.3.
  
 7. SHT A-2.1 THE TOILET ROOM ADJACENT TO THE BRIDAL
 ROOM SHALL BE ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.22 WITH ALL SUBSECTIONS.
  
 8. SHT A-1.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE AREA OF
 EACH ROOF DRAIN, PLUS 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS, AS WELL AS ANY AREA OF A ROOF THAT
 DRAINS ONTO THE ROOF FROM ABOVE, (IF APPLICIABLE).
  
 9. SHT A-7.0 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 C. 11-4.19.5 FAUCETS
 WATER CLOSETS SHALL BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. FIGURE 28.
  
 10. SHT A-7.0 DETAIL 3, BATHROOM SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH 11-4.16, 11-4.19, 11-4.21 &
 11-4.23 WITH ALL SUBSECTIONS AND FIGURES.
  
 11. SHT A-7.0 DETAIL 5. THE TOILET ROOMS SHALL BE
 ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.17,11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS AND FIGURES. W/C'S TO BE 18" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. FIGURE 28.
  
 12. SHT A-7.0 ALL DETAILS 1 THRU 5. SHOW COMPLIANCE
 WITH SECTION 1210.2. THE WALLS WITHIN 2FT OF THE W/C'S
 AND URINALS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE UP TO 4FT ABOVE THE FLOOR.LEGEND TOILET ROOM
 ACCESSORIES W-1 INDICATES WAINSCOAT 36" HIGH BUT DETAIL
 4 SHOWS TILE TO CEILING. PLEASE CLAIRFY AND CORRELATE.
  
 13. SHT A-7.1 DETAIL 1 SHOW THE TURNING AREA IN THE
 TOILET ROOM. (NOT REQUIRED IN THE STALL). SECTION
 11-4.22.3.--SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ___FOR URINALS:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 DETAILS 1 & 2 SHOW THE FOLLOWING:
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 14. SHT A-7.1 ALL DETAILS. SHOW COMPLIANCE WITH SECTION
 1210.2. WALLS WITHIN 2FT OF WATERCLOSETS AND URINALS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE.
  
 15. SHT A-7.1 DETAILS 2 & 5 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 16. SHT A-7.1 DETAIL 6 TOILET ROOM SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS AND FIGURES.
  
 17. SHT A-7.2 DETAILS 4 & 5 LOUNGE SINK SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH
 ALL SUBSECTIONS.
  
 18. SHTS S-1 THRU S-10 THE PRINTED NAME AND LICENSE
 NUMBER SHALL BE LEGIBLY PRINTED IN THE TITLE BLOCKS OF
 ALL SHEETS. FAC 61G15-23.002(2) & FS 471.025.
  
 19. SHT P1.0 SHOWS CONDENSATE TO DISCHARGE 6" ABOVE THE
 SIDEWALK. THIS IS NOT APPROVED. CONDENSATE SHALL
 CONNECT TO A DRYWELL, STORM CATCH BASIN, PLANTED AREA
 OR CONNECT TO A STORM DRAINAGE LINE OUTSIDE THE
 BUILDING. IF CONNECTING TO A STORM LINE, A RELIEF VENT,
 (GOOSENECK), SHALL BE REQUIRED AS THE CONDENSATE EXITS
 THE BUILDING. CONDENSATE DRAINAGE CAN NOT CREATE A
 HAZARD OR NUISANCE. SECTION 314.2.1.
  
 20. SHT P-1.0 STORM DRAINAGE IS SHOWN TO CONNECT TO
 STORMWATER DRAINAGE SYSTEM. "REFER TO CIVIL PLANS FOR
 CONT". PLESE CLARIFYAS THE STORMWATER DRAINAGE SYSTEM
 IS NOT SHOWN ON THE CIVIL PLANS. SECTION 106.1.1.
  
 21. SHT P-1.0 SHOW THE HOT AND COLD WATER PIPING ON THE
 FLOOR PLAN. SECTION 106.3.5.1.3(3)(10).
  
 22. SUBMIT A WATER ISOMETRIC WATER RISER DIAGRAM FROM
 METER, THRU RPZV BACKFLOW, TO THE MOST REMOTE FIXTURE
 SHOWING ALL PIPE SIZES, VALVES, OFFSETS, & WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. SECTION
 106.3.5.1.3(3)(10)(13).
  
 23. SHT P-2.0 SHOW THE HOT & COLD WATER PIPING ON THE
 FLOOR PLAN. SECTION 106.3.5.1.3(3)(10).
  
 24. SHT P-3.0 BACKFLOW PROTECTION IS REQUIRED ON THE
 WATER LINES TO THE WATER FOUNTAINS. A VACUUM BREAKER AT
 THE HIGHEST POINT OF THE SUPPLY LINE TO THE FOUNTAINS
 WILL BE SUFFICIENT. SECTION 608.
  
 25. SHT P-3.0 CONDENSATE LINES SHOW BACKWATER VALVES.
 PER SECTION 715.1 FIXTURES ABOVE THE ELEVATION OF THE
 MANHOLE SHALL NOT DISCHARGE THRU A BACKWATER VALVE.
 WHERE THE POSSIBILITY OF A BACKUP MAY OCCUR, A RELIEF
 VENT, (GOOSENECK) , SHALL BE INSTALLED AS THE
 CONDENSATE EXITS THE BUILDING.
  
 26. SHT P-3.0 NOTE AT THE WATER HEATER INDICATES THE P
 & T RELIEF VALVE AND EM PAN DRAIN LINE TO BE ROUTED TO
 A FLOOR DRAIN VIA INDIRECT WASTE. FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. SECTION 802.3. SINCE
 AN EMERGENCY PAN IS NOT REQUIRED ON THE FIRST FLOOR PER
 SECTION 504.7 AND THE P & T CAN DISCHARGE ONTO THE
 FLOOR,THEY ARE NOT REQUIRED TO BE PIPED TO AN
 INDIRECT WASTE RECEPTOR SO A FLOOR DRAIN WILL BE OK IN
 THE ROOM BUT NOT AS AN INDIRECT WASTE RECEPTOR.
  
 27. SUBMIT A DETAIL FOR THE WATER HEATER. SHOW
 COMPLIANCE WITH SECTIONS 503.1, (SHUT OFF VALVE),
 SECTION 504.2, (IF BOTTOM FED W/H), 504.4, (RELIEF
 VALVE), 504.6.1, (DISCHARGE), 504.6.2, (MATERIALS) AND
 SECTION 607.3.2 (THERMAL EXPANSION CONTROL)
  
 28. SHT P-4.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. (SEE COMMENT # 8). A CHECK ON
 TWO ROOF AREAS, ROOF DRAINS #7 & #10 DO NOT SEEM TO
 INCLUDE ALL SQUARE FOOTAGE FOR THE ROOF AREAS AND/OR
 VERTICAL CONTRIBUTION. EXAMPLE ROOF DRAIN#7 AREA IS
 SHOWN AS 1,304SF, BUT A CHECK OF THE AREA INDICATES
 1,666SF AND THE ROOF DRAIN #10 AREA IS SHOWN AS 1,962SF
 BUT A CHECK OF THE AREA INDICATES 2,322SF. PLEASE
 SUBMIT THE CALCULATIONS SHOWING INFORMATION REQUESTED
 IN COMMENT #8. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES.
  
 29. SHT P-5.0 SHOW THE GAS LINE UP TO THE MATCH LINE ON
 THE FLOOR PLAN. SECTION 106.1.1.
  
 30. SHT P-5.0 THE DISHWASHER, (P-49), SHALL DISCHARGE
 INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM PER
 ARTICLE III SECTION 90-124(7)(B). PLEASE CONNECT
 DISHWASHER TO SANITARY.
  
 31. SUBMIT STORM ISOMETRIC RISER DIAGRAMS FOR ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS THAT REFLECT THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, OFFSETS AND INDICATE SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF DRAIN. SECTION
 106.3.5.1.3(7)(13).--SHOW CLEANOUTS REQUIRED BY
 SECTION 1101.8.
  
 32. SUBMIT CONDENSATE ISOMETRIC RISER DIAGRAMS FOR ALL
 CONDENSATE RISERS THAT REFLECT THE FLOOR PLAN. SHOW
 PIPE SIZES. OFFSETS AND INDICATE MATERIAL FOR SYSTEM.
 NO PVC IN PLENUMS.
  
 33. SHT P-6.0 PLUMBING GENERAL SPECIFICATIONS 1509(G)
 AIR CHAMBERS ARE NOT APPROVED. PLEASE DELETE AIR
 CHAMBERS FROM REFLENCE. SECTION 604.9 AND PDI-WH 201.
  
 34. SUBMIT A WATER ISOMETRIC RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES,
 (FULL OPEN & SHUT OFF), SECTIONS 606.1 & 606.2,
 OFFSETS, AND WATER HAMMER ARRESTORS REQUIRED BY SECTION
 604.6, (DISHWASHER, WASH MACHINE, ICE MAKER ETC). WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING PER PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 35. SHT P-7.0 KITCHEN EQUIPMENT PLUMBING SCHEDULE ITEM
 P-58 INDICATES 1-1/2" SANITARY WASTE. A MINIMUM 2"
 P-TRAP IS REQUIRE PER TABLE 709.1. NOTE INDICATES FS-2
 AT THE WASH MACHINE, BUT SHOWS DIRECT CONNECTION TO THE
 SANITARY SYSTEM. PLEASE CLARIFY. SECTION 106.1.1.
  
 36. SHT P-10.0 THE VENTING FOR TOILET ROOMS 316 & 317
 DO NOT SHOW VENT THRU ROOF AS REQUIRED IN SECTION
 903.3. PLEASE CLARIFY.
  
 37. SHT P-11.0 SANITARY RISER DIAGRAM THE DISH WASHER
 SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT THE
 GREASE SYSTEM. ARTICLE III SECTION 90-124(7)(B). PLEASE
 CONNECT DISHWASHER TO SANITARY.
  
 38. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED TO SECURE A PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL). GAS APPLIANCE SCHEDULE
 NOTE #4 INDICATES TABLE 402.4(24) WHICH IS LP GAS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM
 THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON
 THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES
 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING
 ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC
 SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE
 CLARIFY.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. -- FOR W/H.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE
 REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT
 THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE
 REGULATOR.
  
 K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4.
 --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE
 SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS