Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop M
Sequence Number 1
Notes
Date Text
2007-11-03 15:08:32REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-1.0: GIVEN THE CONGESTED NATURE OF THE DUCT LAYOUT
 IN THE ROOM 101 SANCTUARY AREA, IT IS NOT POSSIBLE TO
 REVIEW THIS AREA OF THE PLANS. WHILE IT IS UNDERSTOOD
 THAT THE PLANS ARE DRAWN AT THE MINIMUM ALLOWED 1/8IN.
 SCALE, THE NATURE OF THE WORK AND THE VOLUME OF
 INFORMATION INCLUDED IN THIS SMALL AREA MAKES IT
 DIFFICULT TO ASCERTAIN THE NATURE AND SCOPE OF WORK IN
 THIS AREA. IT IS REQUESTED THAT, UPON RESUBMITTAL, THIS
 AREA BE REPRESENTED IN A MANNER WHICH MORE CLEARLY
 DELINEATES THE SIZES, ROUTING, LOCATIONS AND
 DESIGNATIONS OF EQUIPMENT, DUCTS AND DIFFUSERS. ONE
 SUGGESTION WOULD BE TO SHOW THIS AREA (ROOM 101
 SANCTUARY) AT A LARGER SCALE. FBC 106.1.1 AND 106.1.3.
  
 2. M-1.0: ROOM 102 SOCIAL HALL, THE AIR QUANTITIES IN
 THIS AREA DO NOT APPEAR IN BALANCE. GRILL DESIGNATIONS
 CALL FOR 8000 TOTAL CFM OF SUPPLY AND 12,800 CFM OF
 RETURN. ALSO, THE OUTDOOR AIR SCHEDULE CALLS FOR 2400
 CFM OF O.A. IN THIS AREA. HOW WILL THIS O.A. BE
 INTRODUCED IF THE RTUS ARE RETURNING MORE AIR THAN THEY
 ARE SUPPLYING? WILL ANY AIR BE EXHAUSTED TO BE REPLACED
 BY THE 2400 CFM OF O.A.? THE AMOUNT OF SUPPLY AIR SHALL
 BE APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN AND
 EXHAUST AIR IN ACCORDANCE WITH FBC,M 403.1 AND THE
 MECHANICAL SYSTEM SHALL BE DESIGNED TO ASSURE THAT THE
 BUILDING IS PRESSURIZED WITH RESPECT TO OUTDOORS IN
 ACCORDANCE WITH FBC 13-409.1.ABC.2.
 NOTE: THESE COMMENTS APPLY TO ALL AREAS WHICH ARE
 REQUIRED TO BE PROVIDED WITH OUTSIDE AIR IN ACCORDANCE
 WITH FBC,M 403.3. VERIFY AIR BALANCES FOR ALL SYSTEMS
 IN ALL AFFECTED AREAS AND MAKE CORRECTIONS AS NEEDED
 PRIOR TO RESUBMITTAL.
  
 3. A-6.1: ELEVATION DRAWINGS SHOW ACCESS LADDERS FROM
 LOWER ROOF TO HIGHER ROOF AREAS. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET, SUCH
 ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS
 OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH IN
 ACCORDANCE WITH FBC,M 306.5. PLEASE SHOW THE PERMANENT
 MEANS OF ACCESS TO BE FROM FLOOR OR GRADE TO THE ROOF
 LEVEL.
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1) THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES.
 2) LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES ON CENTER.
 3) LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES DEEP.
 4) THERE SHALL BE A MINIMUM OF 18 INCHES BETWEEN
 RAILS.
 5) RUNGS SHALL HAVE A MINIMUM 0.75-INCH DIAMETER AND BE
 CAPABLE OF WITHSTANDING A 300-POUND LOAD.
 THERE ARE MULTIPLE LEVELS OF ROOF WHICH APPEAR TO BE
 SEPARATED BY PARAPETS SHOWN ON PG M-4.0. SHOW A MEANS
 OF PERMANENT ACCESS AS REQUIRED BY THIS SECTION ON EACH
 OF THESE LEVELS WHERE EQUIPMENT REQUIRING SERVICE
 ACCESS IS LOCATED.
  
 4. NO WALL SCHEDULE OR FLOOR PLAN COULD BE FOUND IN
 ARCHITECTURAL PLANS SHOWING LOCATIONS OF
 FIRE-RESISTANCE RATED WALL ASSEMBLIES. PLANS COULD NOT
 BE REVIEWED FOR POTENTIAL REQUIRED OPENING PROTECTIVES
 IN DUCT PENETRATIONS OF WALLS. PLEASE INCLUDE THE
 LOCATION OF ALL FIRE RESISTANCE RATED ASSEMBLIES IN THE
 ARCHITECTURAL PLANS TO DETERMINE WHERE OPENING
 PROTECTIVES MAY BE REQUIRED. PLEASE COORDINATE BETWEEN
 MECHANICAL AND ARCHITECTURAL DESIGNERS TO ENSURE ALL
 REQUIRED OPENING PROTECTIVES ARE SHOWN ON PLANS PRIOR
 TO RESUBMITTAL. FBC,M 607.5 AND 607.8.
  
 5. M-2.0 AND M-3.0: PLEASE SEE COMMENT #1 REGARDING
 CLARITY OF PLANS AND SCOPE OF WORK. IT IS NOT POSSIBLE
 BASED ON THE LAYOUT ON THE PLANS TO DETERMINE WHICH
 DESIGNATION SYMBOL GOES WITH WHICH GRILL, DIFFUSER OR
 FAN ON THIS FLOOR PLAN. PLEASE CLARIFY. FBC 106.1.1.
  
 6. M-4.0: WHAT IS THE FUNCTION OF THE GRAVITY RELIEF
 VENTILATORS? THERE IS NO INDICATION ON FLOOR PLANS THAT
 THESE VENTILATORS COMMUNICATE WITH ANY INTERIOR
 PORTIONS OF THE BUILDING. ARE THESE FOR THE RELIEF OF
 POSITIVE PRESSURE CREATED BY THE INTRODUCTION OF
 OUTDOOR AIR? PLEASE SEE COMMENT #2 REGARDING AIR
 BALANCES.
  
 7. M-4.0: WHAT IS THE ELEVATION OF KITCHEN EXHAUST FANS
 IN RELATION TO THE PARAPET WALL TO THE SOUTH OF THE
 FANS? NO ELEVATION IS GIVEN ON THE KITCHEN ROOF
 EXHAUSTER DETAIL SHOWN ON M-9.0. EXHAUST OUTLETS THAT
 TERMINATE ABOVE THE ROOF SHALL HAVE THE DISCHARGE
 OPENING LOCATED NOT LESS THAN 40 INCHES ABOVE THE ROOF
 SURFACE IN ACCORDANCE WITH FBC,M 506.3.12.1. ALSO,
 EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET
 HORIZONTALLY FROM PARTS OF THE SAME OR CONTIGUOUS
 BUILDINGS. EXCEPTION: THE MINIMUM HORIZONTAL DISTANCE
 BETWEEN VERTICAL DISCHARGE FANS AND PARAPET-TYPE
 BUILDING STRUCTURES SHALL BE 2 FEET PROVIDED THAT SUCH
 STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE FAN
 DISCHARGE OPENING IN ACCORDANCE WITH FBC,M 506.3.12.3
 AND 506.5.5. CURRENTLY THE EXHAUST FANS ARE SHOWN LESS
 THAN 10 FEET FROM THE PARAPET. SHOW COMPLIANCE WITH
 THESE SECTIONS.
  
 8. KITCHEN EXHAUST: NO INFORMATION WAS PROVIDED IN
 THESE PLANS REGARDING THE COMMERCIAL KITCHEN EXHAUST
 SYSTEM OTHER THAN THAT SHOWN ON FAN SCHEDULE. THIS
 SYSTEM CAN NOT BE REVIEWED FOR CODE COMPLIANCE AT THIS
 TIME. PROVIDE SUFFICIENT DETAIL AND DOCUMENTATION TO
 DEMONSTRATE COMPLIANCE WITH FBC,M SEC. 506, 507 AND 508
 PRIOR TO PERMIT ISSUANCE AS THESE ARE CODE REQUIRED
 SYSTEMS FOR COMMERCIAL KITCHENS. SEE FBC,M 507.2.
 PROVIDE A KITCHEN LAYOUT SHOWING THE LOCATION OF ALL
 COOKING EQUIPMENT IN RELATION TO THE KITCHEN HOOD. FBC
 106.1.2. ALSO, PG A-1.0 INDICATES THAT THE YOUTH CENTER
 ROOM 213 IS TO CONTAIN A ?SECONDARY KITCHEN.? PLEASE
 SHOW ON PLANS THE LAYOUT OF THIS KITCHEN ALONG WITH
 COOKING EQUIPMENT AND REQUIRED EXHAUST SYSTEMS.
  
 9. M-5.0: PROVIDE DETAILED INFORMATION SHOWING ACCESS
 FOR SERVICE AND REPLACEMENT FOR AHU?S 12A AND 12B IN
 THE CHAPEL. SHOW COMPLIANCE WITH FBC,M 306.1 AND EITHER
 306.2 OR 306.3, WHICHEVER IS MORE APPROPRIATE FOR
 CONDITIONS. IT IS UNCLEAR WHETHER THESE UNITS ARE
 HOUSED IN AN ATTIC SPACE OR A ROOM ON A SEPARATE
 MEZZANINE-TYPE LEVEL.
  
 10. M-6.0: ROOF-TOP A/C UNIT SCHEDULE, NONE OF THE
 RTU?S ARE SHOWN ON ENERGY CALCULATIONS IN THE INPUT
 DATA REPORT (FURTHER REFERENCED AS IDR) UNDER THE
 ?SYSTEMS? PORTION. DATA SHALL BE INPUT INTO FLA/COM FOR
 EACH ZONE BY EQUIPMENT TYPE, SIZE AND EFFICIENCY IN
 ACCORDANCE WITH FBC 13-407.2.A. ALSO, NEITHER COOLING
 LOAD CALCULATIONS NOR SYSTEM SIZING SUMMARIES WERE
 INCLUDED WITH THE ENERGY CALCULATIONS. THESE
 CALCULATIONS SHALL BE ATTACHED TO THE CODE COMPLIANCE
 FORM SUBMITTED TO THE BUILDING DEPARTMENT AT TIME OF
 PERMIT APPLICATION IN ACCORDANCE WITH FBC
 13-407.1.ABC.1. PROVIDE ALL MISSING
 INFORMATION/CALCULATIONS/SUMMARIES AND MAKE THEM PART
 OF A COMPLETE METHOD A CODE COMPLIANCE FORM AS REQUIRED
 BY THESE SECTIONS.
  
 11. M-6.0: RTU SCHEDULE NOTES, AUXILIARY DRAIN
 PROTECTION IS REQUIRED ON DOWNDRAFT RTU?S AS ANY
 OVERFLOW OF CONDENSATE FROM THE PRIMARY DRAIN PAN WOULD
 INEVITABLY LEAK INTO THE BUILDING. THIS MAY BE
 ACCOMPLISHED WITH A WATER LEVEL DETECTION DEVICE (SUCH
 AS A FLOAT SWITCH) LOCATED INTERNALLY ON THE PRIMARY
 DRAIN PAN IN ACCORDANCE WITH FBC,M 307.2.3(2).
  
 12. M-6.0 SUPPLY AIR UNIT SCHEDULE:MUCH OF THE
 INFORMATION IN THE COOLING LOAD CALCULATIONS DOES NOT
 CORRESPOND WITH THIS SCHEDULE. EXAMPLE (A): AIR HANDLER
 #3 IS SHOWN WITH 95 TOTAL CFM IN CALCULATIONS BUT SHOWS
 1300 CFM ON SCHEDULE. EXAMPLE (B): AIR HANDLER #4 IS
 SHOWN WITH 14,839 CFM AND 38.57 TONS OF TOTAL COOLING
 IN CALCULATIONS BUT SHOWS 1300 CFM AND A LITTLE OVER 3
 TONS OF TOTAL COOLING ON SCHEDULE. PLEASE VERIFY THAT
 ALL INFORMATION IN SYSTEM SIZING CALCULATIONS AND THE
 IDR CORRESPONDS WITH THE EQUIPMENT SHOWN ON SCHEDULE.
  
 13. M-6.0: FAN SCHEDULE, EF-1 THROUGH EF-11 SHOW THEY
 ARE TO BE CONTROLLED BY WALL SWITCH. THESE AREAS ARE
 REQUIRED TO HAVE MECHANICAL EXHAUST IN ACCORDANCE WITH
 FBC,M TABLE 403.3 AND AS SUCH, ALL AIR SUPPLIED TO SUCH
 SPACES SHALL BE EXHAUSTED IN ACCORDANCE WITH FBC,M
 403.2.1(3). PLEASE SHOW HOW THESE FANS ARE TO BE
 CONTROLLED IN WAY THAT ASSURES THAT THEY WILL OPERATE
 WHENEVER AIR IS BEING SUPPLIED TO THESE SPACES (BY AHU
 OR RTU) AS WELL AS WHENEVER THESE SPACES ARE OCCUPIED
 IN ACCORDANCE WITH FBC,M 401.3 AND 403.2.1(3).
  
 14. M-6.0: FAN SCHEDULE, EF-14 AND EF-15 HAVE A NOTE
 (NOTE 5) INDICATING THEY ARE TO BE PROVIDED WITH
 WEATHER HOODS AND 2 INCH ALUMINUM MESH FILTERS. PLEASE
 CLARIFY AS IT APPEARS THIS NOTE SHOULD ONLY APPLY TO
 SF-1 AND SF-2. ALSO, SF-1 AND SF-2 HAVE A NOTE (NOTE 6)
 INDICATED THEY ARE TO HAVE GREASE DRAINS, HINGED CURBS
 CAPS, ETC. PLEASE CLARIFY AS IT APPEARS THIS NOTE
 SHOULD ONLY APPLY TO EF-14 AND EF-15. EQUIPMENT AND
 APPLIANCES SHALL BE INSTALLED AS REQUIRED BY THE TERMS
 OF THEIR APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF
 THE LISTING, THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND THIS CODE. FBC 304.1
  
 15. M-6.0 OUTDOOR AIR SCHEDULE: NOTE (1) INDICATES 50%
 DIVERSITY USED IN SEVERAL AREAS. THIS IS ASSUMED TO BE
 A REDUCTION OF THE OUTDOOR AIR RATE BASED ON A LIMITED
 DURATION OF THE TIME OF OCCUPANCY. THIS IS NOT OFFERED
 AS AN ADJUSTMENT UNDER FBC,M TABLE 403.3. THERE IS ALSO
 A NOTE IN THE RTU SCHEDULE INDICATING OUTDOOR AIRFLOW
 IS TO BE CONTROLLED BY CO2 SENSORS AND MODULATING
 DAMPERS. IF THE INTENT IS TO DESIGN THE SYSTEM BASED ON
 ASHRAE 62.1-2004 THEN THAT SHALL BE DECLARED ON PLANS.
 THE O.A. SCHEDULE INDICATES OA RATES ARE BASED ON TABLE
 403.3. IN LIEU OF COMPLIANCE WITH SECTION 403.1 THROUGH
 SECTION 403.3, MECHANICAL VENTILATION MAY BE
 IMPLEMENTED IN COMPLIANCE WITH ASHRAE 62.1-2004
 INCLUDING APPROVED ADDENDA IN ACCORDANCE WITH FBC,M
 403.4. PLEASE INDICATE WHICH METHOD IS TO BE USED AND
 PROVIDE FULL COMPLIANCE WITH THE METHOD CHOSEN.
  
 16. M-6.0 O.A. SCHEDULE: NOTE (2) INDICATES ?OCCUPANCY
 PROVIDED BY OWNER.? THE OCCUPANT LOAD IS NOT REQUIRED
 TO BE DETERMINED, BASED ON THE ESTIMATED MAXIMUM
 OCCUPANT LOAD RATE INDICATED IN TABLE 403.3 WHERE
 APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY OF AN
 ALTERNATE ANTICIPATED OCCUPANT DENSITY (SEE FBC,M 403.3
 EXCEPTION). NO SUCH STATISTICAL DATA HAS BEEN PROVIDED
 TO JUSTIFY THESE OCCUPANT LOADS. ALSO, PG A-2.4
 INDICATES THAT THE SOCIAL HALL HAS A POTENTIAL OCCUPANT
 LOAD OF 711 PERSONS, NOT THE 300 SHOWN ON O.A.
 SCHEDULE. SELECT THE CORRECT OCCUPANT LOAD FOR THIS
 AREA AND DESIGN THE VENTILATION SYSTEM TO PROVIDE
 ADEQUATE VENTILATION IN ACCORDANCE WITH THE METHOD
 CHOSEN. FBC,M 403.3 AND FBC 106.1.2.
  
 17. M-9.0: PROVIDE MANUFACTURER?S SUBMITTAL DATA
 SHOWING OUTDOOR EQUIPMENT SUCH AS CONDENSING UNITS,
 RTU?S, ROOFTOP EXHAUST FANS AND VENTILATORS DESIGNED TO
 WITHSTAND WIND LOADS IN ACCORDANCE WITH FBC,M 301.13
 AND FBC 1609. MANUFACTURER?S INSTRUCTIONS SHALL ONLY BE
 USED FOR STRAPPING AND CURB ATTACHMENT IF THE DESIGN IS
 ENGINEERED TO MEET WIND LOAD REQUIREMENTS IN ACCORDANCE
 WITH THESE SECTIONS. PROVIDE ATTACHMENT DETAIL WIT WIND
 LOAD CALCULATIONS IF DIFFERENT FROM OR NOT INCLUDED IN
 MANUFACTURER?S INSTRUCTIONS. FBC 106.1.2.
  
 18. M-9.0 CONDENSER SUPPORT DETAIL: IS THIS TO BE A
 FIELD-FABRICATED SUPPORT OR A PRE-ENGINEERED A/C STAND?
 IF A PRE-ENGINEERED STAND IS TO BE USED, PRODUCT
 APPROVAL IS REQUIRED AS A/C STANDS ARE CLASSIFIED AS
 STRUCTURAL COMPONENTS BY FAC RULE 9B-72. ALSO, EXTERIOR
 WALL LOUVERS REQUIRE PRODUCT APPROVAL AS THEY ARE
 CLASSIFIED AS PANEL WALLS BY RULE 9B-72. PROVIDE ALL
 SUPPORTING DOCUMENTATION. FOR MORE INFORMATION ON THE
 FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT
 WWW.FLORIDABUILDING.ORG. ALSO, THE CLEARANCE UNDER THE
 A/C SUPPORTS SHALL BE DETERMINED BY THE WIDTH OF THE
 EQUIPMENT BEING SUPPORTED IN ACCORDANCE WITH FBC TABLE
 1509.7. THE 18 INCHES AS STATED ON THE DETAIL MAY OR
 MAY NOT BE ADEQUATE PER THIS SECTION.
  
 19. M-10.0: IF O.A. DAMPERS ON RTUS ARE TO BE MODULATED
 BY CO2 SENSORS, THEY SHOULD BE INCLUDED IN THE CONTROL
 DIAGRAM. FBC 106.1.1.
  
 20. M-11.0: LOCATIONS OF FIRE DAMPERS IS NOT SHOWN ON
 PLANS. THE SPECIFIC LOCATION AND INSTALLATION DETAILS
 OF EACH FIRE DOOR, FIRE DAMPER, CEILING DAMPER AND
 SMOKE DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED ON
 THE BUILDING PLANS BY THE DESIGNER IN ACCORDANCE WITH
 FBC,M 607.8.
  