Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop G
Sequence Number 1
Notes
Date Text
2008-03-15 08:39:36DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED TO SECURE A PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.-- SHOW ALL PIPING FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL). GAS APPLIANCE SCHEDULE
 NOTE #4 INDICATES TABLE 402.4(24) WHICH IS LP GAS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). --TOTAL DISTANCE FROM
 THE METER TO THE MOST REMOTE OUTLET IS NOT INDICATED ON
 THE PLANS. GAS APPLIANCE SCHEDULE NOTE #4 INDICATES
 80FT DEVELOPED LENGTH FROM THE REGULATOR, BUT ADDING
 ALL CUT SECTION LENGTHS PROVIDED ON THE ISOMETRIC
 SUBMITTED ON SHT P-11.0 197FT IS INDICATED. PLEASE
 CLARIFY.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. -- FOR W/H.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 J. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATOR. INDICATE THE MODEL NUMBER. THE
 REGULATOR SHALL BE LISTED & INDICATE TOTAL BTU OUTPUT
 THAT CORRELATES TO THE TOTAL BTU LOAD DOWNSTREAM OF THE
 REGULATOR.
  
 K. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION 409.4.
 --ALSO A UNION WILL BE REQUIRED DOWNSTREAM OF THE
 SHUT OFF VALVE.PLEASE SHOW ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  