Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-23 14:34:201. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND
 AFTER CONSTRUCTION.
  
 2. CONSTRUCTION, RENOVATION, AND DEMOLITION SHALL
 COMPLY WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4. ANY CUTTING AND WELDING OPERATIONS TO COMPLY WITH
 NFPA 51B.
  
 5. EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED.
  
 6. IT APPEARS THAT SOME ILLUMINATED EXIT SIGNS ARE
 MISSING FROM THE ELECTRICAL DRAWINGS. ALL EXIT ACCESS
 AND EXITS ARE TO BE PROPERLY IDENTIFIED BY ILLUMINATED
 EXIT SIGNS.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR AUTOMATIC
 FIRE SPRINKLER SYSTEM INSTALLATION.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 9. KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
  
 10. KNOX-BOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION CONNECTED TO THE SPRINKLER
 SYSTEM.
  
 11. THE REQUIRED FIRE ALARM SYSTEM SHALL BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 12. PLEASE EXPLAIN KEY PAD NOTES THAT ARE LISTED ON THE
 PLANS. HOW DO THESE DEVICES IMPACT EXITING FROM THE
 BUILDING.
  
 13. PLEASE PROVIDE INTERIOR FINISH CLASSIFICATIONS FOR
 ALL WALLS. CEILING INFORMATION LOCATED.
  
 14. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 HOOD,DUCT, AND FIRE SUPPRESSION SYSTEM PLANNED FOR THE
 BUILDING.
  
 15. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE
 PROTECTED BY AUTOMATIC FIRE SPRINKLER PROTECTION.
  
 16. HANDRAILS AND GUARDRAILS TO COMPLY WITH APPLICABLE
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 17. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" NUMBERS ARE REQUIRED.
  
 18. PLEASE PROVIDE A COMPLETE LIFE SAFETY PLAN
 ILLUSTRATING PROPOSED OCCUPANT LOADS, TRAVEL DISTANCES,
 EXIT ROUTES, EXITS AND ALL OTHER RELATED INFORMATION.
  
 19. ANY ARCHITECTURAL SOFFITS SHALL NOT INTERFERE WITH
 THE OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 20. PLEASE PROVIDE EGRESS CAPACITIES FOR DOORS ON PAGE
 A-2.3.
  
 21. EGRESS SCHEMES NEED TO BE FURTHER DEFINED.
  
 22. FLAME SPREAD DETAILS NEEDED FOR FABRIC CEILING
 ILLUSTRATED ON PAGE A-3.0. INFORMATION LOCATED ON PAGE
 A-6.0
  
 23. PLEASE ILLUSTRATE SEATING AREAS PLANNED FOR THE
 HANDICAPPED IN THE ASSEMBLY AREAS.
  
 24. PLEASE DISPLAY ALL PROPOSED FIRE EXTINGUISHER
 LOCATIONS.
  
 25. ACCORDING TO THE DOOR SCHEDULE ON PAGE A-10.1 THE
 GROUP SEVEN HARDWARE HAS A DEADBOLT AND AN EXIT PANIC
 DEVICE. WHEN PANIC DEVICES ARE INSTALLED ON EXIT DOORS
 NO OTHER LOCKS OR HANDWARE IS PERMITTED.
  
 26. THE DOOR SCHEDULE DECLARES ON PAGE A-10.1 THAT ONLY
 TWO TYPES OF DOORS WILL HAVE PANIC HARDWARE. IS THIS
 TRUE AND CORRECT.
  
 27. COULD NOT LOCATE AN EMERGENCY LIGHT FIXTURE TYPES
 ON PAGE E-15.0.
  
 28. ANY OCCUPIED AREA SHALL BE EQUIPPED WITH EMERGENCY
 LIGHTING EQUIPMENT. PLEASE ILLUSTRATE EMERGENCY LIGHT
 FIXTURES.
  
 29. PLEASE DESCRIBE WHAT THE CLASSROOMS WILL BE USED
 FOR. IF CHILDREN WILL USE THESE FACILITIES, PLEASE
 PROVIDE AGES, STAFFING COUNTS, AND NUMBER OF HOURS.
  
 30. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE
 FOR THE FIRE ALARM SYSTEM WILL DESCRIBE TO THE
 OCCUPANTS.
  
 31. WHAT HARDWARE IS EXPECTED ON THE GATES USED TO EXIT
 THE ENCLOSED COURTYARD AREA.
  
 32. THE LARGE MONUMENTAL STAIRS LOCATED ON THE EXTERIOR
 SHALL COMPLY WITH THE APPLICABLE STAIR SECTIONS OF THE
 CODE.
  
 33. IF THE OCCUPANT LOAD DECLARED ON PAGE A-2.1 CAN BE
 EXPECTED TO BE IN THE BUILDING AT ONE TIME, CROWD
 MANAGERS MAY BE NECESSARY AND SHALL RECEIVE THE PROPER
 TRAINING.
  
 34. NO SMOKING SIGNS SHALL BE INSTALLED SINCE SMOKING
 IS ASSEMBLY OCCUPANCIES CAN BE REGULATED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 35. ALL ELECTRICAL EQUIPMENT INSTALLATION TO COMPLY
 WITH NFPA 70, THE NATIONAL ELECTRICAL CODE.
  
 36. PLEASE ILLUSTRATE ON THE PLANS THE ONE THIRD
 DIAGONAL DIMENSION FOR EXITING TO REACH EXITS IN FIRE
 SPRINKLER PROTECTED BUILDINGS.
  
 37. THE COVERED AREA AND AC AREA DOES NOT REFLECT THE
 TOTAL DISPLAYED ON PAGE A-1.0
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX