Text |
| 2007-10-23 14:34:20 | 1. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND |
| | AFTER CONSTRUCTION. |
| | |
| | 2. CONSTRUCTION, RENOVATION, AND DEMOLITION SHALL |
| | COMPLY WITH NFPA 241. |
| | |
| | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | |
| | 4. ANY CUTTING AND WELDING OPERATIONS TO COMPLY WITH |
| | NFPA 51B. |
| | |
| | 5. EXITS ARE TO REMAIN CLEAR AND UNOBSTRUCTED. |
| | |
| | 6. IT APPEARS THAT SOME ILLUMINATED EXIT SIGNS ARE |
| | MISSING FROM THE ELECTRICAL DRAWINGS. ALL EXIT ACCESS |
| | AND EXITS ARE TO BE PROPERLY IDENTIFIED BY ILLUMINATED |
| | EXIT SIGNS. |
| | |
| | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR AUTOMATIC |
| | FIRE SPRINKLER SYSTEM INSTALLATION. |
| | |
| | 8. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF THE FIRE ALARM SYSTEM. |
| | |
| | 9. KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. |
| | |
| | 10. KNOX-BOX LOCKING CAPS WILL BE REQUIRED FOR THE FIRE |
| | DEPARTMENT CONNECTION CONNECTED TO THE SPRINKLER |
| | SYSTEM. |
| | |
| | 11. THE REQUIRED FIRE ALARM SYSTEM SHALL BE MONITORED |
| | BY A LICENSED UL LISTED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 12. PLEASE EXPLAIN KEY PAD NOTES THAT ARE LISTED ON THE |
| | PLANS. HOW DO THESE DEVICES IMPACT EXITING FROM THE |
| | BUILDING. |
| | |
| | 13. PLEASE PROVIDE INTERIOR FINISH CLASSIFICATIONS FOR |
| | ALL WALLS. CEILING INFORMATION LOCATED. |
| | |
| | 14. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | HOOD,DUCT, AND FIRE SUPPRESSION SYSTEM PLANNED FOR THE |
| | BUILDING. |
| | |
| | 15. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE |
| | PROTECTED BY AUTOMATIC FIRE SPRINKLER PROTECTION. |
| | |
| | 16. HANDRAILS AND GUARDRAILS TO COMPLY WITH APPLICABLE |
| | BUILDING AND FIRE CODE REQUIREMENTS. |
| | |
| | 17. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6" |
| | HIGH AND AT LEAST 1" NUMBERS ARE REQUIRED. |
| | |
| | 18. PLEASE PROVIDE A COMPLETE LIFE SAFETY PLAN |
| | ILLUSTRATING PROPOSED OCCUPANT LOADS, TRAVEL DISTANCES, |
| | EXIT ROUTES, EXITS AND ALL OTHER RELATED INFORMATION. |
| | |
| | 19. ANY ARCHITECTURAL SOFFITS SHALL NOT INTERFERE WITH |
| | THE OPERATION OF ANY FIRE SPRINKLER HEADS. |
| | |
| | 20. PLEASE PROVIDE EGRESS CAPACITIES FOR DOORS ON PAGE |
| | A-2.3. |
| | |
| | 21. EGRESS SCHEMES NEED TO BE FURTHER DEFINED. |
| | |
| | 22. FLAME SPREAD DETAILS NEEDED FOR FABRIC CEILING |
| | ILLUSTRATED ON PAGE A-3.0. INFORMATION LOCATED ON PAGE |
| | A-6.0 |
| | |
| | 23. PLEASE ILLUSTRATE SEATING AREAS PLANNED FOR THE |
| | HANDICAPPED IN THE ASSEMBLY AREAS. |
| | |
| | 24. PLEASE DISPLAY ALL PROPOSED FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |
| | 25. ACCORDING TO THE DOOR SCHEDULE ON PAGE A-10.1 THE |
| | GROUP SEVEN HARDWARE HAS A DEADBOLT AND AN EXIT PANIC |
| | DEVICE. WHEN PANIC DEVICES ARE INSTALLED ON EXIT DOORS |
| | NO OTHER LOCKS OR HANDWARE IS PERMITTED. |
| | |
| | 26. THE DOOR SCHEDULE DECLARES ON PAGE A-10.1 THAT ONLY |
| | TWO TYPES OF DOORS WILL HAVE PANIC HARDWARE. IS THIS |
| | TRUE AND CORRECT. |
| | |
| | 27. COULD NOT LOCATE AN EMERGENCY LIGHT FIXTURE TYPES |
| | ON PAGE E-15.0. |
| | |
| | 28. ANY OCCUPIED AREA SHALL BE EQUIPPED WITH EMERGENCY |
| | LIGHTING EQUIPMENT. PLEASE ILLUSTRATE EMERGENCY LIGHT |
| | FIXTURES. |
| | |
| | 29. PLEASE DESCRIBE WHAT THE CLASSROOMS WILL BE USED |
| | FOR. IF CHILDREN WILL USE THESE FACILITIES, PLEASE |
| | PROVIDE AGES, STAFFING COUNTS, AND NUMBER OF HOURS. |
| | |
| | 30. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE |
| | FOR THE FIRE ALARM SYSTEM WILL DESCRIBE TO THE |
| | OCCUPANTS. |
| | |
| | 31. WHAT HARDWARE IS EXPECTED ON THE GATES USED TO EXIT |
| | THE ENCLOSED COURTYARD AREA. |
| | |
| | 32. THE LARGE MONUMENTAL STAIRS LOCATED ON THE EXTERIOR |
| | SHALL COMPLY WITH THE APPLICABLE STAIR SECTIONS OF THE |
| | CODE. |
| | |
| | 33. IF THE OCCUPANT LOAD DECLARED ON PAGE A-2.1 CAN BE |
| | EXPECTED TO BE IN THE BUILDING AT ONE TIME, CROWD |
| | MANAGERS MAY BE NECESSARY AND SHALL RECEIVE THE PROPER |
| | TRAINING. |
| | |
| | 34. NO SMOKING SIGNS SHALL BE INSTALLED SINCE SMOKING |
| | IS ASSEMBLY OCCUPANCIES CAN BE REGULATED BY THE |
| | AUTHORITY HAVING JURISDICTION. |
| | |
| | 35. ALL ELECTRICAL EQUIPMENT INSTALLATION TO COMPLY |
| | WITH NFPA 70, THE NATIONAL ELECTRICAL CODE. |
| | |
| | 36. PLEASE ILLUSTRATE ON THE PLANS THE ONE THIRD |
| | DIAGONAL DIMENSION FOR EXITING TO REACH EXITS IN FIRE |
| | SPRINKLER PROTECTED BUILDINGS. |
| | |
| | 37. THE COVERED AREA AND AC AREA DOES NOT REFLECT THE |
| | TOTAL DISPLAYED ON PAGE A-1.0 |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | 804-4709 PHONE |
| | 804-4774 FAX |