Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-07 13:20:24NOTE ADDED:
  
 PLEASE KNOW THAT ALL LOW VOLTAGE SYSTEMS ARE REQUIRED
 TO BE UNDER SEPARATE PERMITS. IF THE LV IS SHOWN ON
 PLANS, THEN THE SUB CONTRACTOR WOULD ONLY NEED TO
 REFERENCE PLANS FOR TURN AROUND PERMIT.
 FEES ARE SEPARATE FOR VALUE OF THE SCOEP OF WORK AS
 SHWON.
2007-10-07 12:24:262007-10-07 12:24:26
  
  
 *** DENIED ***
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8
 AND 7.9 NEEDS TO BE MET.
 PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY
 BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING. PLEASE
 KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS PATHS
 INCLUDING THAT TO THE EXIT DISCHARGE AREAS/PATHS. FOR
 EXAMPLE: PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE
 PART OF THE EXIT DISCHARGE WHICH DO NOT CONTAIN BATTERY
 BACK UP LIGHTING.
 PLEASE SEE THE HALL WHICH DOES NOT INDICATE ANY
 EMERGENCY LIGHTING FIXTURES.
 PLEASE SEE COURTYARD AREAS AS THESE ARE EXIT PATHS
 HOWEVER AS THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF
 WAY OR SAFE DISTANCE FROM THE BUILDING, EMERGENCY
 LIGHTING FIXTURES WILL BE REQUIRED.
 PLEASE SEE ANY TOILETS WHICH ARE NOT A SINGLE POINT OF
 USE WILL ALSO REQUIRE A BATTERY BACK UP FIXTURES OF
 SOME TYPE.
 PLEASE SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL
 ARE LISTED.
 PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR
 ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE
 MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC
 106.1.2, FAC 61G15-33.004
 NFPA-101 7.8, 7.9
  
 3) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH
 EXIT SIGNS APPEAR TO BE MISSING. PLEASE SEE CHAPEL AND
 LIBRARY FOR EXAMPLE. IF THE OCCUPANT LOAD EXCEEDS THAT
 OF THE FBC FOR THESE AREAS AN EXIT SIGN WILL BE
 REQUIRED.
 PLEASE SEE BUILDING AND FIRE MARSHAL REVIEW COMMENTS
 FOR THESE POSSIBLE LOCATIONS.
 PLEASE SEE FBC 1006.3.8.2, .3, LS-101 7.10.1.6 AND
 12.4.7.7.2 AS FLOOR PROXIMITY EXIT LIGHTING IS REQUIRED
 IN ASSEMBLY AREAS.
 PLEASE PROVIDE LOCATIONS ALONG WITH HEIGHT/LOCATION
 REQUIREMENTS.
  
 4) NOTE: PLEASE SEE THE MDP/ MAIN AS SHOWN INDICATES
 MORE THAN 42 SPACES. PLEASE SEE 408.5 AS THIS IS NOT
 PERMITTED IN THIS ENCLOSURE AS SHOWN.
 PLEASE LABEL ALL WITH COORDINATION OF CIRCUITING/PHASES
 ON PANELS.
 FOR EXAMPLE: 1,3,5 WOULD BE 1L1,
  
 5) NOTE: PLEASE CLARIFY AIC RATING AS STATED ON THE
 PANEL-BOARD. THIS STATES 100K, WHICH IS OK, HOWEVER IS
 THIS THE RATING FOR ALL BREAKERS IN THIS SAME
 ENCLOSURE?
 IF EACH IS RATED AT 100K, PLEASE FIRST VERIFY ALL
 BREAKERS AS SHOWN ARE AVAILABLE AT THIS 100K RATING.
 THERE IS NO CODE VIOLATION, HOWEVER THE 100K RATING FOR
 ALL BREAKERS AS SHOWN IS HIGH AND IF SHOWN AS 100K
 RATING FOR EACH, THEN THAT?S WHAT WILL BE REQUIRED TO
 BE INSTALLED.
 THIS IS ONLY A SUGGESTION TO VERIFY THIS.
  
 6) NOTE: PLEASE SEE THE LOCATION OF THE MDP ON E-6.0 IS
 NOT THE SAME AS E-000.
 PLEASE CORRELATE AND SEE OTHER COMMENTS.
 FBC 106.1.2.
 NEC 110.26 ETC.
  
 7) NOTE: PLEASE SEE THE LOCATIONS OF THE PANELS ALL
 APPEAR TO BE IN A EGRESS HALLWAY?
 PLEASE VERIFY THIS AS RATED EXIT PASSAGE WAYS MAY NOT
 HAVE THESE ELECTRICAL PANELS AS SHOWN.
 IF THIS IS NOT A EXIT/HALL WAY, THEN PLEASE ADJUST
 IDENTIFICATION OF THIS AREA.
 PLEASE SEE FBC CHAPTER 10, 1006.3.1, THIS WILL BE
 REVIEWED BY BUILDING, FIRE MARSHAL REVIEW COMMENTS.
 THIS IS BEING NOTED ON ELECTRICAL REVIEW AS THIS MAY
 AFFECT ELECTRICAL PANELS AND LOCATIONS.
  
 8) NOTE: PLEASE INDICATE MINIMUM WIND LOAD DESIGNS FOR
 LIGHT POLES ON ELECTRICAL PLANS.
 PLEASE SUBMIT WIND LOAD CALCULATIONS WHICH WILL BE
 REVIEWED BY THE BUILDING REVIEWER.
 PLEASE KNOW THAT ANY RE-LOCATED POLES AS SHOWN WILL BE
 REQUIRED TO MEET CURRENT WIND LOADS.
 FBC 106.1.2
  
 9) NOTE: PLEASE SUBMIT SITE LIGHTING PHOTO-METRICS FOR
 VERIFICATION OF ZONING COMPLIANCE.
 THERE ARE NO MINIMUMS FOR ELECTRICAL REVIEW HOWEVER
 ZONING DOES HAVE REGULATIONS FOR MAXIMUM LIGHTING
 LEVELS ACROSS PROPERTY LINES.
 PLEASE SEE COMMENTS BELOW WITH RESPECT TO LIGHTING FOR
 CHAPTER 13 OF THE FBC.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER
 13 IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS.
  
 A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING
 ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON
 AREAS.
 PLEASE BE SURE TO PROVIDE ZONES BASED ON MAXIMUM SQ FT
 FOR CONTROLS.
 PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN IN MANY OF
 THE ROOMS AND LOCATIONS NEED TO STATE THE MAXIMUM
 TIMES. 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE THERE ARE SOME AREAS IN WHICH A OCCUPANCY
 SWITCH IS LOCATED IN ANOTHER ROOM THAN THE ROOM IN
 WHICH THE LIGHTING IS BEING CONTROLLED.
 FOR EXAMPLE: PLEASE SEE THE LOCATION OF THE DEVICE FOR
 FINANCIAL MANGERS OFFICE WHICH SEEMS TO CONTAIN A
 DEVICE IN THE TOILET AREA (313).
 PLEASE ALSO SEE THE SAME FM OFFICE 314 WHICH HAS A
 DEVICE WHICH FEEDS LIGHTING IN THE ROOM TO THE EAST?
 13-415.1.ABC.1.1, .1.2
  
 C) PLEASE PROVIDE MORE INFORMATION ON THE TYPES OF
 DEVICES BEING INSTALLED. PLEASE SEE THE BATHROOM/TOILET
 AREAS WHICH INDICATE A SINGLE WALL OCCUPANCY DEVICE. IF
 THIS IS A MOTION DEVICE ONLY THEN COVERAGE NEEDED IS
 NOT PROVIDED.
 PLEASE CLARIFY THESE. 13-415.1.ABC.1.1
  
 D) PLEASE SEE THAT NO LIGHTING CONTROLS COULD BE FOUND
 FOR ACCENT/DISPLAY LIGHTING. 13-415.1.ABC.1.3
  
 E) PLEASE SEE PLANS INDICATES A *S* IN A BOX WITH A TD
 DESIGNATION NEXT TO THIS, HOWEVER THE DEVICE LEGEND ON
 E-12.0 DOES NOT CONTAIN THIS DEVICE.
 PLEASE PROVIDE INFORMATION.
 13-415.1.ABC.1.1
  
 F) PLEASE PROVIDE DETAIL FOR EXTERIOR LIGHTING CONTROLS
 PER 13-415.1.ABC.1.4, 13-415.1.ABC.2
  
 G) PLEASE SEE THAT ALL SEPARATE SPACES PER
 13-415.1.ABC.1.2 ARE REQUIRED TO CONTAIN LIGHTING
 CONTROL. EXAMPLE: TOILET 316, HALL, ETC
 **PLEASE SEE LS 101 7.8.1.2.2 AND CHAPTER 10 OF THE FBC
 AS AUTOMATED OCCUPANCY DEVICES ARE PERMITTED HOWEVER
 THE SET UP/SCENARIO WILL NEED TO BE GONE OVER WITH THIS
 OFFICE.
  
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS WHICH HAVE NOT
 YET BEEN PROVIDED FOR LIGHTING CONTROLS, IT IS NOT
 POSSIBLE TO PROVIDE A COMPLETE REVIEW FOR CODE
 COMPLIANCE. THERE VERY WELL MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
 PLEASE CALL TO GO OVER ANY OF THESE ITEMS.
  
 11) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR
 ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS
 NEEDS TO BE MET.
 PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO
 THE INPUT DATA REPORT AS IDR.
  
 A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND
 CONSUMES ENERGY WITH THAT OF THE IDR.
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A
 *PASSED* STATUS. PLEASE SEE THE IDR SHOWS ONLY *1-ONE*
 FIXTURE AND THIS FIXTURE AS SHOWN CONTAINS NO POWER
 USAGE. THIS IS NOT POSSIBLE WHEN THE PLANS INDICATE
 OVER 100 FIXTURES WHICH HAVE NOT BEEN PLACED ON THE
 IDR.
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE
 LIGHTING IN THE IDR.
 PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH
 NEEDS TO COORDINATE WITH PLANS.
 PLEASE SEE THE AREAS DO NOT MATCH.
 PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH
 AREA/ROOM DESIGNATION DOES NOT CORRELATE.
 PLEASE SEE SEVERAL WHICH ONLY INDICATES *ONE* FIXTURE
 WHICH IS NOT POSSIBLE.
 PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL
 ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING
 CONTROLS ARE AUTOMATED ETC.
  
 ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS
 WITH THE IDR.
 PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW
 OF MANY ITEMS CAN NOT BE DONE.
  
 PLEASE BE SURE TO SEE 13-415.2.ABC.1.2 FOR TRACK
 LIGHTING.
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES
 PLEASE SEE 13-415.1.A, 13-415.2 ETC.
  
 ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL
 LIGHTING CONTROLS AND CALCULATIONS REQUIRED.
  
 12) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM
 AS NOTED.
 CALLS FOR *BUILDING STEEL*, IS THIS MEANT TO BE *FOOTER
 STEEL*? IF THE STRUCTURE CONTAINS BOTH FOOTER AND
 BUILDING STEEL PLEASE SEE 250.50 AS BOTH ARE REQUIRED
 TO BE PART OF THE SYSTEM.
 PLEASE VERIFY ANY COLD WATER PIPING PER 250.50 **PLEASE
 PLACE NOTE ON PLANS FOR FBC 2704 WHICH REQUIRES METAL
 FRAMING MEMBERS TO BE BONDED.
  
 13) NOTE: PLEASE SEE KITCHEN (207) WHICH STATES A NOTE
 TO SEE E-13 FOR ELECTRICAL FOR THAT AREA HOWEVER E-13.0
 DOES NOT CONTAIN THIS.
 THIS ARE WAS HOWEVER FOUND ON E-11
 A) PLEASE SEE NEC 210.8B2 AS GFI PROTECTION IS REQUIRED
 FOR ALL 15 AND 20AMP 120V IN KITCHEN AREA WHETHER OR
 NOT THESE ARE COUNTER SPACE OUTLETS.
 PLEASE SEE THERE ARE CIRCUITS WHICH DO NOT CONTAIN THE
 REQUIRED PROTECTION.
 FOR EXAMPLE:
 PLEASE SEE 1K2-17, 1K2-19 ETC.
 B) PLEASE SEE THERE ARE WHAT APPEAR TO BE EQUIPMENT
 DESIGNATIONS ON THIS SAME LAYOUT ON E-11 WHICH ARE NOT
 ON THE EQUIPMENT LIST AS PROVIDED. PLEASE SEE FOR
 EXAMPLE:
 E-901, E-902, E49B ETC THERE ARE OTHERS.
  
 14) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 15) NOTE: PLEASE CLARIFY SPACE ABOVE LINE #1 ON THE MDP
 AS THIS NOTES 2000AMP MAIN?
 PLEASE CORRELATE AS THE RISER SHOWS A MDP1, THE
 PANEL-BOARD IS MDP AND THE PLANS DO NOT INDICATE
 EITHER.
 PLEASE CORRELATE AND PLEASE SHOW LOCATION OF THE MDP ON
 PLANS.
 PLEASE SEE 110.26, 408.36
  
 16) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST
 MOTOR LOADS AT 125%.
 PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN)
  
 17) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE 408.4.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.5, 106.1.2
  
 ** PLEASE KNOW AS THERE WILL SEVERAL CHANGES TO PLANS,
 THERE MAY BE NEW COMMENTS WHICH ARE NOT MADE ON THIS
 REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-07 09:16:442007-10-07 09:16:44
  
  
 REVIEW IN PROGRESS
2007-10-06 18:46:422007-10-06 18:46:42
  
 IN ELECTRICAL FOR REVIEW.