| 2007-10-07 13:20:24 | NOTE ADDED: |
| | |
| | PLEASE KNOW THAT ALL LOW VOLTAGE SYSTEMS ARE REQUIRED |
| | TO BE UNDER SEPARATE PERMITS. IF THE LV IS SHOWN ON |
| | PLANS, THEN THE SUB CONTRACTOR WOULD ONLY NEED TO |
| | REFERENCE PLANS FOR TURN AROUND PERMIT. |
| | FEES ARE SEPARATE FOR VALUE OF THE SCOEP OF WORK AS |
| | SHWON. |
| 2007-10-07 12:24:26 | 2007-10-07 12:24:26 |
| | |
| | |
| | *** DENIED *** |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8 |
| | AND 7.9 NEEDS TO BE MET. |
| | PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY |
| | BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING. PLEASE |
| | KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS PATHS |
| | INCLUDING THAT TO THE EXIT DISCHARGE AREAS/PATHS. FOR |
| | EXAMPLE: PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE |
| | PART OF THE EXIT DISCHARGE WHICH DO NOT CONTAIN BATTERY |
| | BACK UP LIGHTING. |
| | PLEASE SEE THE HALL WHICH DOES NOT INDICATE ANY |
| | EMERGENCY LIGHTING FIXTURES. |
| | PLEASE SEE COURTYARD AREAS AS THESE ARE EXIT PATHS |
| | HOWEVER AS THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF |
| | WAY OR SAFE DISTANCE FROM THE BUILDING, EMERGENCY |
| | LIGHTING FIXTURES WILL BE REQUIRED. |
| | PLEASE SEE ANY TOILETS WHICH ARE NOT A SINGLE POINT OF |
| | USE WILL ALSO REQUIRE A BATTERY BACK UP FIXTURES OF |
| | SOME TYPE. |
| | PLEASE SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL |
| | ARE LISTED. |
| | PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR |
| | ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE |
| | THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE |
| | MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO |
| | GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC |
| | 106.1.2, FAC 61G15-33.004 |
| | NFPA-101 7.8, 7.9 |
| | |
| | 3) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH |
| | EXIT SIGNS APPEAR TO BE MISSING. PLEASE SEE CHAPEL AND |
| | LIBRARY FOR EXAMPLE. IF THE OCCUPANT LOAD EXCEEDS THAT |
| | OF THE FBC FOR THESE AREAS AN EXIT SIGN WILL BE |
| | REQUIRED. |
| | PLEASE SEE BUILDING AND FIRE MARSHAL REVIEW COMMENTS |
| | FOR THESE POSSIBLE LOCATIONS. |
| | PLEASE SEE FBC 1006.3.8.2, .3, LS-101 7.10.1.6 AND |
| | 12.4.7.7.2 AS FLOOR PROXIMITY EXIT LIGHTING IS REQUIRED |
| | IN ASSEMBLY AREAS. |
| | PLEASE PROVIDE LOCATIONS ALONG WITH HEIGHT/LOCATION |
| | REQUIREMENTS. |
| | |
| | 4) NOTE: PLEASE SEE THE MDP/ MAIN AS SHOWN INDICATES |
| | MORE THAN 42 SPACES. PLEASE SEE 408.5 AS THIS IS NOT |
| | PERMITTED IN THIS ENCLOSURE AS SHOWN. |
| | PLEASE LABEL ALL WITH COORDINATION OF CIRCUITING/PHASES |
| | ON PANELS. |
| | FOR EXAMPLE: 1,3,5 WOULD BE 1L1, |
| | |
| | 5) NOTE: PLEASE CLARIFY AIC RATING AS STATED ON THE |
| | PANEL-BOARD. THIS STATES 100K, WHICH IS OK, HOWEVER IS |
| | THIS THE RATING FOR ALL BREAKERS IN THIS SAME |
| | ENCLOSURE? |
| | IF EACH IS RATED AT 100K, PLEASE FIRST VERIFY ALL |
| | BREAKERS AS SHOWN ARE AVAILABLE AT THIS 100K RATING. |
| | THERE IS NO CODE VIOLATION, HOWEVER THE 100K RATING FOR |
| | ALL BREAKERS AS SHOWN IS HIGH AND IF SHOWN AS 100K |
| | RATING FOR EACH, THEN THAT?S WHAT WILL BE REQUIRED TO |
| | BE INSTALLED. |
| | THIS IS ONLY A SUGGESTION TO VERIFY THIS. |
| | |
| | 6) NOTE: PLEASE SEE THE LOCATION OF THE MDP ON E-6.0 IS |
| | NOT THE SAME AS E-000. |
| | PLEASE CORRELATE AND SEE OTHER COMMENTS. |
| | FBC 106.1.2. |
| | NEC 110.26 ETC. |
| | |
| | 7) NOTE: PLEASE SEE THE LOCATIONS OF THE PANELS ALL |
| | APPEAR TO BE IN A EGRESS HALLWAY? |
| | PLEASE VERIFY THIS AS RATED EXIT PASSAGE WAYS MAY NOT |
| | HAVE THESE ELECTRICAL PANELS AS SHOWN. |
| | IF THIS IS NOT A EXIT/HALL WAY, THEN PLEASE ADJUST |
| | IDENTIFICATION OF THIS AREA. |
| | PLEASE SEE FBC CHAPTER 10, 1006.3.1, THIS WILL BE |
| | REVIEWED BY BUILDING, FIRE MARSHAL REVIEW COMMENTS. |
| | THIS IS BEING NOTED ON ELECTRICAL REVIEW AS THIS MAY |
| | AFFECT ELECTRICAL PANELS AND LOCATIONS. |
| | |
| | 8) NOTE: PLEASE INDICATE MINIMUM WIND LOAD DESIGNS FOR |
| | LIGHT POLES ON ELECTRICAL PLANS. |
| | PLEASE SUBMIT WIND LOAD CALCULATIONS WHICH WILL BE |
| | REVIEWED BY THE BUILDING REVIEWER. |
| | PLEASE KNOW THAT ANY RE-LOCATED POLES AS SHOWN WILL BE |
| | REQUIRED TO MEET CURRENT WIND LOADS. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SUBMIT SITE LIGHTING PHOTO-METRICS FOR |
| | VERIFICATION OF ZONING COMPLIANCE. |
| | THERE ARE NO MINIMUMS FOR ELECTRICAL REVIEW HOWEVER |
| | ZONING DOES HAVE REGULATIONS FOR MAXIMUM LIGHTING |
| | LEVELS ACROSS PROPERTY LINES. |
| | PLEASE SEE COMMENTS BELOW WITH RESPECT TO LIGHTING FOR |
| | CHAPTER 13 OF THE FBC. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER |
| | 13 IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS. |
| | |
| | A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING |
| | ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON |
| | AREAS. |
| | PLEASE BE SURE TO PROVIDE ZONES BASED ON MAXIMUM SQ FT |
| | FOR CONTROLS. |
| | PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN IN MANY OF |
| | THE ROOMS AND LOCATIONS NEED TO STATE THE MAXIMUM |
| | TIMES. 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | B) PLEASE SEE THERE ARE SOME AREAS IN WHICH A OCCUPANCY |
| | SWITCH IS LOCATED IN ANOTHER ROOM THAN THE ROOM IN |
| | WHICH THE LIGHTING IS BEING CONTROLLED. |
| | FOR EXAMPLE: PLEASE SEE THE LOCATION OF THE DEVICE FOR |
| | FINANCIAL MANGERS OFFICE WHICH SEEMS TO CONTAIN A |
| | DEVICE IN THE TOILET AREA (313). |
| | PLEASE ALSO SEE THE SAME FM OFFICE 314 WHICH HAS A |
| | DEVICE WHICH FEEDS LIGHTING IN THE ROOM TO THE EAST? |
| | 13-415.1.ABC.1.1, .1.2 |
| | |
| | C) PLEASE PROVIDE MORE INFORMATION ON THE TYPES OF |
| | DEVICES BEING INSTALLED. PLEASE SEE THE BATHROOM/TOILET |
| | AREAS WHICH INDICATE A SINGLE WALL OCCUPANCY DEVICE. IF |
| | THIS IS A MOTION DEVICE ONLY THEN COVERAGE NEEDED IS |
| | NOT PROVIDED. |
| | PLEASE CLARIFY THESE. 13-415.1.ABC.1.1 |
| | |
| | D) PLEASE SEE THAT NO LIGHTING CONTROLS COULD BE FOUND |
| | FOR ACCENT/DISPLAY LIGHTING. 13-415.1.ABC.1.3 |
| | |
| | E) PLEASE SEE PLANS INDICATES A *S* IN A BOX WITH A TD |
| | DESIGNATION NEXT TO THIS, HOWEVER THE DEVICE LEGEND ON |
| | E-12.0 DOES NOT CONTAIN THIS DEVICE. |
| | PLEASE PROVIDE INFORMATION. |
| | 13-415.1.ABC.1.1 |
| | |
| | F) PLEASE PROVIDE DETAIL FOR EXTERIOR LIGHTING CONTROLS |
| | PER 13-415.1.ABC.1.4, 13-415.1.ABC.2 |
| | |
| | G) PLEASE SEE THAT ALL SEPARATE SPACES PER |
| | 13-415.1.ABC.1.2 ARE REQUIRED TO CONTAIN LIGHTING |
| | CONTROL. EXAMPLE: TOILET 316, HALL, ETC |
| | **PLEASE SEE LS 101 7.8.1.2.2 AND CHAPTER 10 OF THE FBC |
| | AS AUTOMATED OCCUPANCY DEVICES ARE PERMITTED HOWEVER |
| | THE SET UP/SCENARIO WILL NEED TO BE GONE OVER WITH THIS |
| | OFFICE. |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE MANY ITEMS WHICH HAVE NOT |
| | YET BEEN PROVIDED FOR LIGHTING CONTROLS, IT IS NOT |
| | POSSIBLE TO PROVIDE A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE. THERE VERY WELL MAY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | PLEASE CALL TO GO OVER ANY OF THESE ITEMS. |
| | |
| | 11) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR |
| | ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS |
| | NEEDS TO BE MET. |
| | PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO |
| | THE INPUT DATA REPORT AS IDR. |
| | |
| | A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND |
| | CONSUMES ENERGY WITH THAT OF THE IDR. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A |
| | *PASSED* STATUS. PLEASE SEE THE IDR SHOWS ONLY *1-ONE* |
| | FIXTURE AND THIS FIXTURE AS SHOWN CONTAINS NO POWER |
| | USAGE. THIS IS NOT POSSIBLE WHEN THE PLANS INDICATE |
| | OVER 100 FIXTURES WHICH HAVE NOT BEEN PLACED ON THE |
| | IDR. |
| | PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE |
| | LIGHTING IN THE IDR. |
| | PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH |
| | NEEDS TO COORDINATE WITH PLANS. |
| | PLEASE SEE THE AREAS DO NOT MATCH. |
| | PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH |
| | AREA/ROOM DESIGNATION DOES NOT CORRELATE. |
| | PLEASE SEE SEVERAL WHICH ONLY INDICATES *ONE* FIXTURE |
| | WHICH IS NOT POSSIBLE. |
| | PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL |
| | ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING |
| | CONTROLS ARE AUTOMATED ETC. |
| | |
| | ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS |
| | WITH THE IDR. |
| | PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW |
| | OF MANY ITEMS CAN NOT BE DONE. |
| | |
| | PLEASE BE SURE TO SEE 13-415.2.ABC.1.2 FOR TRACK |
| | LIGHTING. |
| | PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES |
| | PLEASE SEE 13-415.1.A, 13-415.2 ETC. |
| | |
| | ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL |
| | LIGHTING CONTROLS AND CALCULATIONS REQUIRED. |
| | |
| | 12) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM |
| | AS NOTED. |
| | CALLS FOR *BUILDING STEEL*, IS THIS MEANT TO BE *FOOTER |
| | STEEL*? IF THE STRUCTURE CONTAINS BOTH FOOTER AND |
| | BUILDING STEEL PLEASE SEE 250.50 AS BOTH ARE REQUIRED |
| | TO BE PART OF THE SYSTEM. |
| | PLEASE VERIFY ANY COLD WATER PIPING PER 250.50 **PLEASE |
| | PLACE NOTE ON PLANS FOR FBC 2704 WHICH REQUIRES METAL |
| | FRAMING MEMBERS TO BE BONDED. |
| | |
| | 13) NOTE: PLEASE SEE KITCHEN (207) WHICH STATES A NOTE |
| | TO SEE E-13 FOR ELECTRICAL FOR THAT AREA HOWEVER E-13.0 |
| | DOES NOT CONTAIN THIS. |
| | THIS ARE WAS HOWEVER FOUND ON E-11 |
| | A) PLEASE SEE NEC 210.8B2 AS GFI PROTECTION IS REQUIRED |
| | FOR ALL 15 AND 20AMP 120V IN KITCHEN AREA WHETHER OR |
| | NOT THESE ARE COUNTER SPACE OUTLETS. |
| | PLEASE SEE THERE ARE CIRCUITS WHICH DO NOT CONTAIN THE |
| | REQUIRED PROTECTION. |
| | FOR EXAMPLE: |
| | PLEASE SEE 1K2-17, 1K2-19 ETC. |
| | B) PLEASE SEE THERE ARE WHAT APPEAR TO BE EQUIPMENT |
| | DESIGNATIONS ON THIS SAME LAYOUT ON E-11 WHICH ARE NOT |
| | ON THE EQUIPMENT LIST AS PROVIDED. PLEASE SEE FOR |
| | EXAMPLE: |
| | E-901, E-902, E49B ETC THERE ARE OTHERS. |
| | |
| | 14) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| | SHEETS SUBMITTED. |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| | SETS. |
| | FBC 106.3.5.1.2 |
| | |
| | 15) NOTE: PLEASE CLARIFY SPACE ABOVE LINE #1 ON THE MDP |
| | AS THIS NOTES 2000AMP MAIN? |
| | PLEASE CORRELATE AS THE RISER SHOWS A MDP1, THE |
| | PANEL-BOARD IS MDP AND THE PLANS DO NOT INDICATE |
| | EITHER. |
| | PLEASE CORRELATE AND PLEASE SHOW LOCATION OF THE MDP ON |
| | PLANS. |
| | PLEASE SEE 110.26, 408.36 |
| | |
| | 16) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST |
| | MOTOR LOADS AT 125%. |
| | PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN) |
| | |
| | 17) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE |
| | SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. |
| | PLEASE SEE 408.4. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2, 106.5, 106.1.2 |
| | |
| | ** PLEASE KNOW AS THERE WILL SEVERAL CHANGES TO PLANS, |
| | THERE MAY BE NEW COMMENTS WHICH ARE NOT MADE ON THIS |
| | REVIEW. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-10-07 09:16:44 | 2007-10-07 09:16:44 |
| | |
| | |
| | REVIEW IN PROGRESS |
| 2007-10-06 18:46:42 | 2007-10-06 18:46:42 |
| | |
| | IN ELECTRICAL FOR REVIEW. |