Plan Review Notes
Plan Review Notes For Permit 07090042
Permit Number 07090042
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-05 11:57:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.THIS MUST BE DONE
 PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL SETS OF ALL
 DOCUMENTS ARE REQUIRED FOR PERMITTING AND FOR ALL
 SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6.
  
 4.)PROVIDE THE THRESHOLD INSPECTION PLAN.THE
 APPROVED CONTRACT WITH THE THRESHOLD INSPECTOR WILL BE
 REQUIRED IN THE PERMIT PACKAGE PRIOR TO PERMIT
 ISSUANCE.
  
 5.)THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT IS TO BE ON EACH SHEET, SLIDER ENGINEERING,
 FAC61G15-23.002.
  
 6.)THIS PROJECT IS IN AN A5 HIGH HAZARD FLOOD ZONE. A
 FORM BOARD ELEVATION CERTIFICATE AND FFE CERTIFICATE
 WILL BE REQUIRED TO BE FILED WITH THIS OFFICE DURING
 THE CONSTRUCTION PROCESS.ALL FFES, INCLUDING
 MECHANICAL EQUIPMENT, ARE TO BE 6? ABOVE BASE FLOOD
 ELEVATION, CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(B).INCLUDE THIS REQUIREMENT ON THE PLAN.
  
 7.)PROVIDE A CODE SUMMARY; HOW COMPLIANCE WITH FBC
 TABLE 503, DECLARE MIXED OR NONSEPARATED USE,
 INCIDENTAL OR ACCESSORY USES, FBC302.ALL AREA
 INCREASE CALCULATIONS ARE TO BE ON THE PLAN.IF ANY
 FIRE RATED WALLS ARE REQUIRED, SHOW ON THE PLAN AND
 PROVIDE DETAILS.
  
 8.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
 9.)SEE CITY OF WEST PALM BEACH STANDARD FOR PARKING
 STRIPING, SEE ATTACHED AND ZONING COMMENTS, SHEET
 A1.0.
  
 10.)PLEASE NOTE THAT THE ROOM DESIGNATION NUMBERS ARE
 DIFFERENT ON SHEET A1.0 FROM OTHER SHEETS IN THE PLAN.
 IT IS NOT A REQUIREMENT FOR THEM TO BE CONSISTENT, BUT
 NOTE THAT SHEET A1.0 IS THE EASIEST SHEET TO USE FOR
 REFERENCE AS IT SHOWS THE ENTIRE PLAN.
  
 11.)SIMMONS & WHITE SHEET 2, RAMP SLOPE IS SHOWN AS
 12:1 MAX.DO YOU MEAN 1:12?
  
 12.)NO ACCESS AISLE SHOWN FOR PARKING SPACE 55,
 A1.0.
  
 13.)THERE APPEARS TO BE AN UNNECESSARY ACCESS AISLE
 BETWEEN TWO NON ACCESSIBLE SPACES, 58 AND 59, IS THIS
 CORRECT?A1.0
  
 14.)SHOW THE PASSENGER LOADING ZONE FBC11-4.6.6.
  
 15.)PROVIDE A DETAIL FOR THE RAMP HANDRAIL SHOWN ON
 A1.0, EAST SIDE.FBC11-4.8.5.
  
 16.)PROVIDE A DETAIL FOR THE STAIR HANDRAILS,
 FBC11-4.9.4.THE HANDRAILS SHOWN DO NOT APPEAR TO HAVE
 THE HANDRAIL EXTENSIONS AT THE BOTTOM FBC11-4.9.4(2)
 (12INCHES PLUS WIDTH OF ONE TREAD).
  
 17.)A LANDING IS REQUIRED AT THE BOTTOM OF THE RAMP,
 A2.0 FBC11-4.8.4.
  
 18.)HANDRAIL EXTENSIONS REQUIRED TOP AND BOTTOM OF
 THE RAMP A2.0 FBC11-4.8.5.
  
 19.)A2.0 SHOWS DETAIL INDICATOR 7-A7.5 IN THE
 SANCTUARY AREA, BUT THIS DETAIL IS FOR A GATE.ALSO
 SEE 2-A7.3, CHECK ALL.
  
 20.)A2.0 DETAIL INDICATOR 3-A7.5 AT THE RAMP IS FOR
 THE STAIR DETAIL; SHOULD THIS BE 4-A7.5?PROVIDE THE
 HEIGHT, SEE FBC11-4.4.
  
 21.)ON THE LIFE SAFETY PLAN, PLEASE SHOW EGRESS WIDTH
 AND OCCUPANT LOAD SERVED FOR EACH COMPONENT, OCCUPANT
 LOAD, TRAVEL DISTANCE, WIDTH OF COMPONENTS OF MEANS OF
 EGRESS (HALLWAYS AND DOORS, ETC.), OVER ALL DIMENSIONS
 FOR THE AREAS.THE EGRESS PLAN A2.3 SHOWS EXITING FROM
 THE SANCTUARY, BUT EXIT DISCHARGE IS TO BE TO THE
 PUBLIC WAY.THE LIFE SAFETY PLAN SHOULD CLEARLY SHOW
 COMPLIANCE WITH FBC CHAPTER 10.TOTAL OCCUPANT LOAD
 WAS SHOWN ON ANOTHER SHEET, BUT SOME OF THESE AREAS
 SHARE THE EXIT ACCESS AND THIS NUMBER IS NOT SHOWN ON
 THE PLAN.PLEASE LABEL ROOM NUMBERS.PLEASE CONTACT
 ME IF YOU WISH TO DISCUSS.
  
 22.)AREAS INCLUDED IN THE OCCUPANT LOAD ON A2-2 ARE
 NOT ENTIRELY CLEAR.FOR INSTANCE, HOW WAS THE STAGE
 AREA INCLUDED IN THIS CHART, OR ACCESSORY STORAGE
 AREAS?SEE FBC TABLE 1004.1.2.
  
 23.)AREA 201 DOES NOT APPEAR TO BE INCLUDED AS HAVING
 AN OCCUPANT LOAD.SEE FBC1004.1.2, NUMBER OF OCCUPANTS
 CANNOT BE LESS THAN FBC TABLE 1004.1.2.IT APPEARS
 THAT THE OCCUPANT LOAD PROVIDED IS ACTUAL OCCUPANT
 LOAD, FBC1004.1.1.
  
 24.)TOTAL OCCUPANT LOAD GOING THROUGH EXIT DISCHARGE
 336A, 336D IS NOT SHOWN.
  
 25.)THE GATES ARE REQUIRED TO BE ACCESSIBLE,
 FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS.PROVIDE A
 DETAIL TO SHOW COMPLIANCE.
  
 26.)SHOW WHEELCHAIR AREAS AND SEATING, FBC11-4.33.3.
  
 27.)IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC
 AND COMMON USE TOILET ROOM SHALL COMPLY WITH
 FBC11-4.22, FBC11-4.1.3(11).PRIVATE TOILET SPACES
 SHALL BE ADAPTABLE, SEE BATHROOM ADJACENT TO AREA 103
 SHEET A2.1.PROVIDE A GRAB BAR BACKING DETAIL AND SHOW
 TURNING RADIUS, DOOR MANEUVERING CLEARANCE FBC11 FIGURE
 25.ALSO SHOW DISTANCE REQUIRED FOR TWO DOORS IN A
 SERIES, FBC11-4.13.7.
  
 28.)LOUNGE SINKS ARE TO COMPLY WITH FBC11-4.2.4,
 PROVIDE A DETAIL.THE SECTIONS SHOWN ON A7.2 SHOW
 DOORS BLOCKING THE REQUIRED KNEE CLEARANCE.
 FBC11-4.24.3.
  
 29.)DOUBLE DOORS IN ROOMS 316 AND 317, ONE LEAF IS TO
 MEET THE REQUIREMENTS OF FBC11-4.13, FBC11-4.13.4.
  
 30.)PROVIDE A DETAIL AND SHOW LOCATION OF SEATING
 COMPLYING WITH FBC11-4.1.3(18) AND (19).
  
 31.)SHOW COMPLIANCE WITH FBC11-4.1.3(19)(B).IF YOU
 FEEL THAT THIS (OR ANY OF THE ACCESSIBILITY
 REQUIREMENTS) DOES NOT APPLY, PLEASE CONTACT ME AND
 DOCUMENT THE EXEMPTION IN WRITING WITH THE
 RESUBMITTAL.
  
 32.)PROVIDE ROOF DRAINAGE CALCULATIONS, FBC1503.4.
 SHOW LOCATION OF SCUPPERS AND HEIGHT OF SCUPPER IN THE
 PARAPET WALL.
  
 33.)A10.0, WALL FINISH W1 STATES TO SEE SHEET A- FOR
 DETAILS.PLEASE COMPLETE REFERENCE.
  
 34.)ROOM 316 AND 317 SHOW W1 ON THE FLOOR PLAN DETAIL
 A7.0, W1* FOR FINISH.IT IS NOT CLEAR WHAT THE
 ASTERISK DESIGNATES.PROVIDE THE DETAIL FBC1210.2.
 CHECK ALL BATHROOM WALL FINISHES AND REVISE A10.0
 ACCORDINGLY.
  
 35.)DETAIL 2 A6.0 HAD TEXT AT THE TOP RIGHT WHICH IS
 ILLEGIBLE (CUT OFF).EITHER REMOVE THE PARTIAL TEXT OR
 PROVIDE THE TEXT IN A LEGIBLE FORMAT.
  
 36.)SHEET S10 STATES EDGE ZONE IS *'*", PLEASE
 REVISE.
  
 37.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 38.)PROVIDE ROOF COMPONENTS AND CLADDING DESIGN
 PRESSURE, FBC1603.1.4.
  
 39.)SELECT THE APPROVED ASSEMBLY YOU ARE USING IN THE
 ROOF PRODUCT APPROVAL.
  
 40.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL IN
 ADDITION TO THE NOAS PROVIDED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS UNAVAILABLE, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 41.)FOR THE EXCLUSIVE WOOD DOORS AND THE REPUBLIC
 DOORS, PRINT THE FLORIDA STATE PRODUCT APPROVAL,
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FROM
 THE INTERNET.
  
 42.)FOR THE REPUBLIC DOORS, MARK WHICH PRODUCT(S) YOU
 ARE INSTALLING.
  
 43.)WHEN RESUBMITTING, PLEASE INCLUDE A RESPONSE
 LETTER STATING HOW AND WHERE EACH ITEM WAS ADDRESSED.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved