| 2008-10-27 15:56:55 | BUILDING PLAN REVIEW |
| | PERMIT: 07090034 |
| | ADD: 314 10TH STREET |
| | CONT: KENNEDY CONTRACTORS, INC. |
| | TEL: (561)434-1307 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: REVISION |
| | ACTION: DENIED |
| | |
| | SHEETS A-01/A-02/A-03/A-04/A-05/A-08 AND SHEETS S-1 - |
| | S-4. |
| | |
| | 1) SHEETS A-03 AND A-04 SHOW DORMERS ON THE ELEVATIONS |
| | PLANS. THESE DORMERS ARE NOT SHOWN ON THE PERMITTED SET |
| | OF DRAWINGS. IF THE DORMERS WILL BE INSTALLED, PROVIDE |
| | THE STRUCTURAL FRAMING DETAILS SHOWING THE ATTACHMENT |
| | METHODS FOR THE DORMERS; THE PLANS ALSO SHOW EIFS |
| | OUTRIGGERS BUT NO INFORMATION OR DETAILS HOW THEY WILL |
| | BE ATTACHED TO THE STRUCTURE. THE BUILDING OFFICIAL MAY |
| | REQUIRE DETAILS, COMPUTATIONS, DIAGRAMS, AND OTHER DATA |
| | NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION |
| | OF SYSTEMS. 106.1.2. |
| | |
| | 2) SHEET A-05 MAKES REFERENCE TO DETAIL #3 / S-2, THE |
| | DETAIL ON S-2 DO NOT CORRESPOND WITH SECTION INDICATED |
| | ON SHEET A-05. THE NEW PLANS ALSO SHOW TWO LAYERS R-21 |
| | INSULATION AND 3? CONTINUOUS SCREEN VENTS ON SHEET A-05 |
| | #4 THEN, ON SHEET S-4 #1 THE INSULATION SHOWN IS R30 |
| | AND THE SCREEN VENTS ARE 7? X 25? SPACED 8? O/C. THE |
| | DETAILS ALSO FAIL TO SHOW THE EIFS AS INDICATED ON THE |
| | ELEVATION DRAWINGS. CLARIFY. |
| | |
| | NOTE: PLEASE MAKE SURE THE DETAILS AND INFORMATION |
| | CORRESPOND WITH THE PLANS. SHOP DRAWINGS WILL BE |
| | REQUIRED FOR THE NEW FLOOR SYSTEM. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |
| | |