| 2008-07-28 15:12:44 | |
| | ** FAILED REVIEW ** |
| | |
| | |
| | 1) NOTE:EGRESS LIGHTING FOR STAIR #2 DOES NOT MEET |
| | THE LIFE SAFETY CODE. 7.9.2.1,7.9.2.2 THE LIGHTING FOOT |
| | CANDLES LEVEL IS SHOWING LEVELS FROM .09, .08, .07 AND |
| | THEN UP TO 15.3, 14.1 ETC. THIS IS NOT POSSIBLE AS THE |
| | SINGLE BATTERY BACK UP FIXTURE IS AT THE TOP OF THE |
| | STAIRS. ALSO SHOWS TAKING ALLOWANCE AVERAGE FROM THE |
| | INTERIOR LIGHTING WHICH IS NOT PERMITTED. |
| | CALLED AND SPOKE TO ENGINEER MR. FORMICA AND HE WILL |
| | CALL BACK ONCE HE OBTAINS INFORMATION FROM STAFF. |
| | LIGHTING LEVELS ON ALL STAIRS ARE IN QUESTION. THE |
| | LIGHTING LUMENS UNDER CONDITIONS OF NORMAL AND |
| | EMERGENCY ARE TO BE VERIFIED. |
| | |
| | 2) NOTE: TYPE SA FIXTURES INDICATE 210WATTS ON SITE |
| | PLANS. THE IDR OF THE ENERGY CALCULATIONS STATE 175W. |
| | THE FIXTURE WATTAGE NOT BULB IS REQUIRED TO BE USED PER |
| | 13-415.2.ABC.1.3. |
| | THIS WILL ALSO BE GONE OVER. |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |