| Plan Review Notes For Permit 07090034 |
| Permit Number |
07090034 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-05-23 14:23:09 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 3-4-08 NOTE #1. THE WALL | | | BETWEEN THE FIRST FLOOR MECHANICAL ROOM AND LOBBY IS | | | FIRE RATED, THE 14X12 SUPPLY AIR DUCT PENETRATING THE | | | WALL NEEDS A FIRE DAMPER, PER 2004 FBC/M 607.5.3 OR | | | MEET THE EXCEPT. | | | | | | 2) AS NOTED IN LAST REVIEW 3-4-08 NOTE #2. THE 16" | | | FLEXIBLE RETURN AIR DUCT MAY NOT PASS THROUGH THE FIRE | | | RATED WALL, PER 2004 FBC/M 607.7, PLEASE CORRECT. | | | | | | 3) SEE ELECTRICAL REVIEW NOTE #1 REGARDING THE ENERGY | | | CALCULATIONS, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|