| Date |
Text |
| 2008-03-14 09:22:24 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED RO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. **OK** COMMENT ADDRESSED. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | 3. **OK** COMMENT ADDRESSED. |
| | |
| | 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE. |
| | SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL |
| | SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET |
| | DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH |
| | FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA |
| | THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE. |
| | PLEASE INDICATE TURNING AREA. |
| | **RESPONSE NOTED, HOWEVER THE TURNING AREA THAT |
| | COMPLIES WITH SECTION 11-4.2.3 WAS NOT INDICATED FOR |
| | THE BREAKROOM. |
| | |
| | 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5 |
| | FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS, |
| | AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO |
| | THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.-- |
| | 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION |
| | 11-4.19.2. 28" IS SHOWN. |
| | **RESPONSE NOTED HOWEVER THERE ARE STILL ISSUES ON THE |
| | DETAIL WITH THE FOLLOWING: 11-4.16.5 FLUSH CONTROLS |
| | (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS (LEVER TYPE, PUSH |
| | TYPE, AND ELECTRONICALLY CONTROLED MECHANISMS ARE |
| | EXAMPLES OF ACCEPTABLE DESIGN). PLEASE INDICATE THESE |
| | REQUIRED ITEMS ON THE PLANS. |
| | |
| | 6. **OK** COMMENT ADDRESSED. |
| | |
| | 7. **OK** COMMENT ADDRESSED. |
| | |
| | 8. **OK** COMMENT ADDRESSED. |
| | |
| | 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER |
| | HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS |
| | INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE. |
| | SECTION 13-103. |
| | **RESPONSE NOTED, HOWEVER THE WRONG FORM (400A) IS |
| | BEING USED. THIS IS NOT A WHOLE BUILDING WITH THE FIRST |
| | FLOOR BEING A SHEEL BY INDICATING FUTURE LEASABLE |
| | SPACE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |