| Plan Review Notes For Permit 07090034 |
| Permit Number |
07090034 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-03-04 15:47:33 | ***DENIED*** | | | | | | PLEASE NOTE THAT MOST OF THE PREVIOUS COMMENTS HAVE NOT | | | BEEN ADDRESSED. IT WOULD HELP EXPEDITE THIS PROCESS IF | | | YOU INCLUDE A RESPONSE LETTER INDICATING HOW AND WHERE | | | EACH COMMENT WAS ADDRESSED. | | | | | | 1) OK | | | | | | 2) FUTURE TENANT SEPARATIONS WILL BE REQUIRED WHEN THE | | | FUTURE SPACES ARE LEASED. PLEASE ACKNOWLEDGE. | | | | | | 3) BUILDING ADDRESS IS REQUIRED ON ELEVATIONS THAT | | | ILLUSTRATES A MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND | | | CONTRASING WITH BACKGROUND. | | | | | | 4) PLEASE CLARIFY EXITING PROTECTION FROM STAIR #1 AND | | | EXTERIOR STAIRS REGARDING DOORS AND WINDOW EXPOSURES. | | | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR | | | HANDRAILS AND GUARDS. INDICATE ON DETAILS. | | | | | | 6) WHAT SLIP RESISTANT METHODS ARE PLANNED FOR THE | | | EXTERIOR FIRE STAIR? | | | | | | 7) ELEVATOR WARNING SIGNS REQUIRED AT ELEVATOR OPENINGS | | | IN LOBBIES. | | | | | | 8) OK | | | | | | 9) TACTILE SIGNS REQUIRED AT EXIT DOORS. | | | | | | 10) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 11) DEBRIS TO BE REMOVED FROM THE SITE DAILY. | | | | | | 12) OK | | | | | | 13) PLEASE INDICATE FIRE EXTINGUISHER LOCATIONS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|