| 2007-11-03 06:53:14 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. CODE ADOPTED IS THE FBC-2004 W/2006 REVISIONS. |
| | PLEASE INDICATE THAT PLANS WERE DESIGNED TO THESE |
| | CODES. |
| | |
| | 2. THE ADDRESS ON THE COVER SHEET, SHT LA-1 & SHT SP-1 |
| | DOES NOT CORRELATE WITH THE ADDRESS ON THE OTHER |
| | SHEETS, THE APPLICATION AND THE ADDRESS ON OUR SYSTEM. |
| | PLEASE CORRELATE THE ADDRESS ON THESE SHEETS. SECTION |
| | 106.1.1. |
| | |
| | 3. SHT LA-1 THE CERTIFICATE OF AUTHROIZATION, (FIRM |
| | LICENSE NUMBER), IS MISSING FROM THE TITLE BLOCK FOR |
| | DIXIE LANDSCAPE. FAC 61G1-16.004(2) & FS 481.306. |
| | |
| | 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE. |
| | SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL |
| | SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET |
| | DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH |
| | FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA |
| | THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE. |
| | PLEASE INDICATE TURNING AREA. |
| | |
| | 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5 |
| | FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS, |
| | AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO |
| | THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.-- |
| | 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION |
| | 11-4.19.2. 28" IS SHOWN. |
| | |
| | 6. SHT A-02 DETAIL 1. SHOW THE W/C'S TO BE 18" OFF THE |
| | WALL TO THE CENTERLINE OF THE FIXTURE, (FIG 28), AND |
| | THE LAV SHALL BE A MINIMUM 15" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE 30" |
| | MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE REQUIRED |
| | FOR THE LAV. SECTION 11-4.19.3. |
| | |
| | 7. SUBMIT A SECOND FLOOR PLUMBING PLAN SHOWING THE |
| | LOCATION OF ALL FIXTURES, SANITARY PIPING, VENTS, WATER |
| | LINES ETC. SECTION 106.3.5.1.3(1)(2)(3)(4)(5)(6)(10). |
| | |
| | 8. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE |
| | EEMAX INSTA-HOT WATER HEATER. SPECIFICATION SHEETS |
| | SHALL SHOW THE LISTING FOR THE WATER HEATER. |
| | |
| | 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER |
| | HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS |
| | INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE. |
| | SECTION 13-103. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |