| Date |
Text |
| 2007-10-15 17:05:09 | BUILDING PLAN REVIEW |
| | PERMIT: 07090034 |
| | ADD: 314 10TH ST |
| | CONT: KENNEDY CONTRACTORS, INC |
| | TEL: (561)434-1300 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 REVISIONS. |
| | |
| | 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT |
| | IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED INTABLE 503 |
| | & TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | .H ) SQ. FT. FOOTPRINT |
| | |
| | 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 4) SP-1 PLEASE PROVIDE ADDITIONAL INFORMATION AS HOW |
| | THE ACCESSIBLE ROUTE FROM THE HANDICAPPED PARKING SPACE |
| | AT ELEVATION 13.5?TO THE FINISH FLOOR ELEVATION OF |
| | 14.0?. |
| | 11-4.3.2(3). SHEET S-1 DETAIL# 7 IS NOT CLEAR IF THERE |
| | IS A |
| | |
| | 5) AREAS OF RESCUE ASSISTANCE ARE REQUIRED IN 2 STORY |
| | BUILDINGS NOT HAVING FIRE SPRINKLERS, PLEASE SEE |
| | 11-4.1.3 EXCEPTION# 9. |
| | IN BUILDINGS OR FACILITIES, OR PORTIONS OF |
| | BUILDINGS OR FACILITIES, REQUIRED TO BE ACCESSIBLE, |
| | ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN THE |
| | SAME NUMBER AS REQUIRED FOR EXITS BY LOCAL |
| | BUILDING/LIFE SAFETY REGULATIONS. WHERE A REQUIRED EXIT |
| | FROM AN OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL OF |
| | ACCESSIBLE EXIT DISCHARGE IS NOT ACCESSIBLE, AN AREA OF |
| | RESCUE ASSISTANCE SHALL BE PROVIDED ON EACH SUCH LEVEL |
| | (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE REQUIRED |
| | EXITS).AREAS OF RESCUE ASSISTANCE SHALL COMPLY WITH |
| | SECTION 11-4.3.11 . A HORIZONTAL EXIT, MEETING THE |
| | REQUIREMENTS OF LOCAL BUILDING/LIFE SAFETY REGULATIONS, |
| | SHALL SATISFY THE REQUIREMENT FOR AN AREA OF RESCUE |
| | ASSISTANCE. |
| | EXCEPTION: AREAS OF RESCUE ASSISTANCE ARE NOT REQUIRED |
| | IN BUILDINGS OR FACILITIES HAVING A SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 6) SHEET A-01 PLANS INDICATE A SECOND FLOOR, THERE IS |
| | NO MENTION OF THE USE OF FIRE SPRINKLERS FOR THIS |
| | BUILDING. PLEASE SEE 11-4.3.11 (1-5) THESE REQUIREMENTS |
| | ARE TO BE MET FORAREAS OF RESCUE ASSISTANCE, PLEASE |
| | PROVIDE INFORMATION FOR COMPLIANCE WITH THESE SECTIONS. |
| | |
| | |
| | 7) SHEET A-01 & A-04 INDICATE STAIRWELL# 1, THE DETAILS |
| | DO NOT PROVIDE INFORMATION FOR BARRIERS TO WARN |
| | VISUALLY IMPAIRED PERSONS SEE 11-4.4.2 & FIGURE 8-C1. |
| | THE EXTERIOR STAIRS WILL NEED THE SAME BARRIER FOR THE |
| | VISUALLY IMPAIRED. |
| | |
| | 8) SHEET A-04 STAIR# 1 SECTION OF GUARDRAIL/ HANDRAIL |
| | .THIS IS AN OFFICE OCCUPANCY THAT WILL NEED TO HAVE THE |
| | GUARDRAIL CONFORM TO SECTION 1012.3. 4? CENTERS. |
| | |
| | 9) SHEET A-04 DETAIL# 3 IS FOR A 1-HR RATED WALL, |
| | PLEASE PROVIDE THE UL NUMBER OR GYPSUM |
| | ASSOCIATION LISTING NUMBER FOR A 1 HOUR RATED ASSEMBLY. |
| | 707.4. |
| | |
| | 10)SHEET A-01 THE FIRST FLOOR LOBBY WILL REQUIRE A |
| | 1-HR RATING. THIS BUILDING DOES NOT INDICATE THE USE OF |
| | FIRE SPRINKLERS, PLEASE SEE TABLE 1016.1 BUSINESS |
| | OCCUPANCY CORRIDORS SERVING A OCCUPANT LOAD GREATER |
| | THAN 30 WILL REQUIRE A 1 HR RATING. |
| | |
| | 11) SHEET A-01 THERE IS NO WALL TAGS IDENTIFYING THE |
| | TYPE OF WALL CONFIGURATION TO BE USED. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. ELEVATOR PUMP |
| | ROOM, ELEVATOR, STAIRWELL, LOBBY AND OR TENANT |
| | SEPARATION WALLS. |
| | |
| | 12) SHEET A-4 STAIRWELL NUMBER 1 DOES NOT PROVIDE A CUT |
| | SECTION THROUGH THE CEILING PROVIDING WHAT TYPE OF |
| | MATERIAL AND OR RATING WILL BE APPLIED TO THE CEILING |
| | OF THE STAIRWELL. ADDITIONAL INFORMATION REQUIRED, |
| | 106.1.2. |
| | |
| | 13) SHEET A-01 DOOR NUMBER 6 & 7 WILL REQUIRE FIRE |
| | RATED DOORS, PLEASE SEE 715.3 FOR OPENING |
| | PROTECTIVE?S. |
| | |
| | 14)SHEET A-01 & A-03 INDICATE THE USE OF EXTERIOR |
| | STAIRS. PLEASE SEE 1022.6 FOR REQUIRED SEPARATION FROM |
| | THE INTERIOR OF THE BUILDING AS REQUIRED IN 1019.1, |
| | ALSO SEE ATTACHED FIGURE 1022.6(1) FROM THE 2004 FBC |
| | CODE COMMENTARY. |
| | |
| | 15) SHEET A-01 & A-03 STAIR # 2 DOES NOT PROVIDE THE |
| | RISERNOR TREAD DIMENSION, SEE 1009.3. |
| | |
| | 16) STAIR# 2 DOES NOT PROVIDE INFORMATION ON THE |
| | HANDRAIL OR GUARDRAIL FOR THIS EXTERIOR STAIR, NOTED |
| | THIS IS A PRE-FAB ENGINEERED STEEL STAIR, AGAIN THERE |
| | IS NO INFORMATION FOR ATTACHMENT OF STAIRS TO |
| | STRUCTURE. ADDITIONAL INFORMATION REQUIRED. 106.1.2. |
| | |
| | 17)SHEET A-01 ON THE 2ND FLOOR THE PLANS INDICATE THE |
| | USE OF A BREAK ROOM SINK, THE PLANS DO NOT PROVIDE AN |
| | ELEVATION OF THIS AREA PLEASE COMPLY WITH THE |
| | FOLLOWING: |
| | SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED |
| | WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH |
| | FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| | SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 18) PLANS DO NOT PROVIDE ANY INFORMATION ON |
| | PENETRATIONS OF HORIZONTAL ASSEMBLIES, |
| | 711.5 PENETRATIONS .PENETRATIONS THROUGH |
| | FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL |
| | COMPLY WITH SECTION 712 . 712.4.1.1 |
| | FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| | PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH THE |
| | FLOOR/ CEILING ASSEMBLY. |
| | |
| | |
| | |
| | 19)ENERGY CALCULATIONS SUBMITTED ARE FORM ?A? WHOLE |
| | BUILDING METHOD WHERE AS THE FIRST FLOOR IS ONLY |
| | ASSUMPTIONS AT THIS TIME, THE CORRECT FORM WOULD BE |
| | EITHER ?B? OR ?C?. |
| | 13-400.0A. NOTE NO INSULATION IS INDICATED ON THE FIRST |
| | FLOOR EXTERIOR WALLS, THE WHOLE BUILDING APPROACH , |
| | METHOD ?A? CAN NOT BE USED. |
| | |
| | 20) THE SEALED SIGNATURE ON THE ENERGY CALCULATION IS |
| | EITHER A STAMP OR COPY OF THE ORIGINAL SIGNATURE. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| | PROFESSIONAL AFFIXED TO THE DOCUMENT. FL STATE STAT: |
| | 61G15-23.002 ENGINEERS |
| | |
| | 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE |
| | RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND |
| | WALL FACE, AS WELL AS DOORS. THE EXTERIOR DOORS WERE |
| | NOT EVEN FILLED IN! 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 22)PLANS FAIL TO INDICATE COMPLIANCE WITH 1209.2 |
| | ATTIC ACCESS, PLEASE PROVIDE WHERE THE ATTIC ACCESS |
| | SHALL BE. |
| | |
| | 23) SHEET A-04 DETAIL NUMBER 4 PROVIDES A EXTERIOR WALL |
| | AND ROOF SECTION. THE PLANS NEED TO SHOW COMPLIANCE |
| | WITH : 1203.250 PERCENT OF THE REQUIRED VENTILATING |
| | AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER |
| | PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET |
| | (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE |
| | OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE |
| | VENTS. |
| | |
| | 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) SINGLE HUNG WINDOWS |
| | B) FIXED/ STOREFRONT WINDOWS |
| | C) MULLIONS VERTICAL |
| | D) SIDE LITES |
| | E) SWING GLAZED DOORS |
| | F) EXTERIOR HOLLOW METAL SWING DOORS |
| | G) TRUSS ANCHORS |
| | H) ROOF ASSEMBLIES |
| | |
| | 25)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | 26) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 27) SHEET S-2 ROOF FRAMING PLAN IS MISSING THE DORMER |
| | SECTION OF THE ROOF, PLEASE PROVIDE |
| | A SECTION INDICATING HOW THE FRONT, SIDE WALLS WILL TIE |
| | INTO THE MAIN ROOFING SYSTEM. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 28) SHEET S-2 ROOF FRAMING PLAN AND NOTES INDICATE THE |
| | UPLIFT LOAD CALCS ARE LOCATED ON SHEET S-4, WHERE? |
| | ADDITIONAL INFORMATION REQUIRED 106.1.2. |
| | |
| | 29)SHEET S-2ND FLOOR DETAIL# 11 INDICATES A METAL |
| | DECK AND CONCRETE BUT NO INFORMATION AS TO THE TYPE OF |
| | STEEL NOR STRENGTH AND TYPE OF THE CONCRETE MIX TO BE |
| | USED FOR THIS SLAB. |
| | NOTE S-3 FLOOR DECK NOTE# 4 INDICATES A MINIMUM YIELD |
| | STRENGTH OF 33,000PSI? |
| | |
| | 30)NOTE PLANS DO NOT INDICATE ANY WINDOW BUCK |
| | ATTACHMENT TO THE STRUCTURE. |
| | 1714.5.4.1 ANCHORING REQUIREMENTS. |
| | WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN |
| | ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S |
| | RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE |
| | SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR |
| | SUBSTRATES NOT SPECIFIED BY THE FENESTRATION |
| | MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING |
| | PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING |
| | PRACTICE. |
| | |
| | 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL |
| | SUBSTRATE. |
| | WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1? |
| | INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE |
| | ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR |
| | SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S |
| | PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE |
| | SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE |
| | OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS |
| | OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE |
| | MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE |
| | LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF |
| | SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED |
| | TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE |
| | ROUGH OPENING SUBSTRATE. |
| | |
| | 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |