| Plan Review Notes For Permit 07090017 |
| Permit Number |
07090017 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-25 09:15:33 | DENIED | | | REFERENCE: | | | ** FBC-2004 WITH 2006 REVISIONS SECTIONS 424.2 AND | | | R4101 SWIMMING POOLS. | | | ** FBC-2004 WITH 2006 REVISIONS, PLUMBING. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | 1. THE EQUIPMENT LAYOUT AND LEGEND ITEM NUMBERS TWO | | | (2) AND FIVE (5) ARE INDICATING A TOTAL OF FOUR (4) | | | 1-1/2" WALL FOUNTAIN SUPPLY LINES BUT THE POOL PLAN IS | | | ONLY INDICATING THREE (3) 1-1/2" WALLFEATURES. ARE | | | THE WALL FEATURES THE SAME AS THE WALL FOUNTAIN SUPPLY | | | LINE? PLEASE CLARIFY AND CORRELATE THE PLANS ON THE | | | RESUBMITTAL PER FBC-2004 CHAPTER 1, SECTION 106.1.1 | | | INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE | | | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, | | | AS DETERMINED BY THE | | | BUILDING OFFICIAL. | | | | | | 2. INDICATE THAT THE AUTO FILL LINE IS TO BE PROTECTED | | | FROM CROSS CONNECTION PER FBC-2004 W/2006 REV. PLUMBING | | | SECTION 608. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|