| 2007-11-20 11:18:08 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)ADDRESSED. |
| | |
| | 2.)SEE ZONING COMMENTS REGARDING CONVEYANCE OF CITY |
| | PROPERTY.THIS IS NOT REFLECTED ON THE SITE PLAN. DOES |
| | THE SITE PLAN SHOW ALL CURRENT PROPERTY LINES? WILL |
| | UNITY OF TITLE BE REQUIRED? |
| | |
| | 3.)DECLARE THE TOTAL NUMBER OF PARKINGS SPACES |
| | INCLUDING NEW SPACES, TOTAL NUMBER OF ACCESSIBLE |
| | SPACES, FBC11-4.1.295)(A). |
| | |
| | 4.)PROVIDE A COMPLETE SITE PLAN SHOWING BUILDING |
| | LOCATION AND ALL ACCESSIBLE PARKING SPACES, |
| | FBC11-4.6.2. |
| | |
| | 5.)ADDRESSED. |
| | |
| | 6.)DECLARE GOVERNING CODE.INCLUDE 2007 AMENDMENTS |
| | IN THE GOVERNING CODE. |
| | |
| | 6.)PROVIDE PRODUCT APPROVALS FOR THE MODIFIED |
| | BITUMEN.PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | DESIGNER OF RECORD FBC*106 |
| | |
| | 7.)PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. |
| | |
| | 8.)IT APPEARS THAT THE ELEVATED DECK WILL BE |
| | APPROXIMATELY 7' ABOVE GRADE.GUARD(RAIL)S REQUIRED, |
| | FBC1012.1.THE PLANTERS SHOWN ARE NOT CONTINUOUS AND |
| | DO NOT MEET THE HEIGHT REQUIREMENT. |
| | |
| | NEW COMMENTS: |
| | |
| | 9.)IT IS UNCLEAR HOW THE COMMENTS HAVE BEEN |
| | ADDRESSED.PLEASE INCLUDE A RESPONSE LETTER IN THE |
| | NEXT SUBMITTAL. |
| | |
| | 10.)SEE ATTACHED FS553.80(2)(B).A 4X PLAN REVIEW |
| | FEE WILL BE CHARGED ON THE NEXT SUBMITTAL IF THE |
| | COMMENTS ARE NOT PROPERLY ADDRESSED. |