| 2008-01-11 16:17:48 | *** DENIED REVIEW *** |
| | |
| | 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING MINIMUM |
| | CODE COMPLIANCE FOR ANY EGRESS, EXITS AND EXIT |
| | DISCHARGE FROM STRUCTURE. |
| | LS 101 2003 7.8 AND 7.9 |
| | |
| | 2) NOTE: PLEASE SEE THAT ANY NEW AREAS, CIRCUITS, |
| | ELECTRICAL ETC WHICH IS GOING TO BE PART OF THIS |
| | STRUCTURE IS TO BE SUBMITTED AT THIS TIME. |
| | FBC 106.3.5.1.2, 106.1.2, NEC 210,220,230,225,408, 240, |
| | 310.16 ETC. |
| | PLEASE CLARIFY SCOPE OF WORK. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |