| 2007-10-24 18:29:15 | PLAN DENIED | | | 1- PLEASE INDICATE ON PLANS WHERE THE 24X12 RTG IS | | | GOING. | | | 2- PLEASE REFER TO SECTION 602.2.1 MATERIALS EXPOSED | | | WITHIN PLENUMS 2004 FBC (M) ( CONDENSATE MUST BE COPPER | | | ) | | | 3- PLEASE REFER TO TABLE 403.3 REQUIRED OUTDOOR | | | VENTILATION . 2004 FBC(M) | | | 4-PLEASE INDICATE ON PLANS THE TERMINATION OF THE | | | CONDENSATE LINE. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|