Plan Review Notes
Plan Review Notes For Permit 07080957
Permit Number 07080957
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-23 13:06:36***DENIED***
  
 1) PLEASE ADVISE OCCUPANCY TYPE FOR ENTIRE BUILDING.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED.
 PLEASE SHOW LOCATIONS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) A COMBINATION EXIT/EMERGENCY SIGN IS SHOWN WITH NO
 DOOR PRESENT. IS THAT A DIRECTIONAL SIGN?
  
 6) SMOKE DETECTORS ARE SHOWN ON THE ELECTRICAL PLAN. IS
 THAT EQUIPMENT REQUIRED?
  
 7) EMERGENCY LIGHTS ON ONE OF THE EXIT SIGNS ARE
 POSITIONED TOWARD THE EXTERIOR OF THE BUILDING.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756