| Plan Review Notes For Permit 07080957 |
| Permit Number |
07080957 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-23 13:06:36 | ***DENIED*** | | | | | | 1) PLEASE ADVISE OCCUPANCY TYPE FOR ENTIRE BUILDING. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED. | | | PLEASE SHOW LOCATIONS. | | | | | | 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) A COMBINATION EXIT/EMERGENCY SIGN IS SHOWN WITH NO | | | DOOR PRESENT. IS THAT A DIRECTIONAL SIGN? | | | | | | 6) SMOKE DETECTORS ARE SHOWN ON THE ELECTRICAL PLAN. IS | | | THAT EQUIPMENT REQUIRED? | | | | | | 7) EMERGENCY LIGHTS ON ONE OF THE EXIT SIGNS ARE | | | POSITIONED TOWARD THE EXTERIOR OF THE BUILDING. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|