| 2007-09-23 11:17:36 | 2007-09-23 11:17:36 |
| | |
| | PLANS REMOVED FROM INCOMING FOR REVIEW. ROUTED BACK TO |
| | INCOMING WHERE PLANS ARE WAITING FOR COMM BOARD. |
| 2007-09-23 11:16:53 | 2007-09-23 11:16:53 |
| | |
| | ** DENIED** |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE THE ADDRESS FOR UNIT/SUITE SHALL BE |
| | STATED ON PERMIT APPLICATION AND TITLE BLOCKS FOR |
| | PLANS. |
| | A COPY OF PERMIT APPLICATION WAS ROUTED TO ADDRESSING |
| | REVIEWER. PLEASE BE AWARE OF ANY DESIGNATIONS WHICH MAY |
| | BE ASSIGNED. |
| | |
| | 3) NOTE: PLEASE PROVIDE LICENSE INFORMATION FOR MI |
| | DESIGN. PLEASE SEE FS 481.229, 471.003 AS A |
| | DESIGNER/DRAFTSMAN MAY NOT PERFORM SCOPE OF WORK AS |
| | SHOWN ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE THE NEW ELECTRICAL SERVICE BEING |
| | PROPOSED IS NOT PERMITTED OR GRANTED PER 230.2. PLEASE |
| | SEE THIS WILL BE REVIEWED BY ZONING AND BUILDING WHICH |
| | MAY PERMIT THIS AS A TENANT SPACE WHICH WOULD STILL |
| | REQUIRE ELECTRICAL TO BE FED FROM THE EXISTING SERVICE |
| | OR UPGRADE THE EXISTING SERVICE IF NOT SUFFICIENT. |
| | PLEASE ALSO SEE COMMENTS BELOW AS A REVIEW OF PLANS |
| | SUBMITTED WILL BE DONE EVEN AS SERVICE AS SHOWN IS NOT |
| | PERMITTED. |
| | |
| | 5) NOTE: PLEASE SEE PLANS INDICATE PANEL AS 200AMPS, |
| | YET RISER SHOWS THIS PANEL AS 150AMPS. |
| | PLEASE CORRELATE, HOWEVER SEE NOTE ABOVE AS SERVICE |
| | RISER WILL REQUIRE A COMPLETE CHANGE. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE CALCULATIONS AS SUBMITTED ARE |
| | SHOWN FOR A RESIDENTIAL UNIT. THIS IS FOR COMMERCIAL |
| | AND CALCULATIONS ARE NOT THE SAME. |
| | PLEASE BE SURE TO SEE THAT ALL CONTINUOUS LOADS ARE TO |
| | BE FIGURED AT 125%. |
| | PLEASE SEE 220.12,220.14,220.42,220.43,220.44, ETC |
| | 215.3, 230.42 |
| | PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH NOW REQUIRES |
| | WATER HEATER LOADS TO BE FIGURED AT 125%. |
| | |
| | 7) NOTE: PLEASE SEE MISSING DEDICATED SIGN CIRCUIT PER |
| | 600.5 AND LOADS ON LOAD CALCULATIONS REQUIRED FOR SIGN |
| | CIRCUIT. |
| | |
| | 8) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER |
| | 210.62 AND LOADS TO BE FIGURED PER 220.43 |
| | |
| | 9) NOTE: PLEASE SEE 700.12FFOR CIRCUITING OF |
| | EMERGENCY AND EXIT LIGHTS. THE CIRCUITING AS SHOWN IS |
| | NOT CODE COMPLIANT. |
| | |
| | 10) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR OUTSIDE |
| | CU. PER 210.63, 210.8B |
| | |
| | 11) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR |
| | THE AHU/AIR HANDLER UNIT HEAT IS TOO LOW. PLEASE SEE |
| | 424.3B FOR MINIMUM OCP. |
| | |
| | 12) NOTE: PLEASE SEE FBC CHAPTER 13 FOR LIGHTING |
| | CALCULATIONS AND PERFORMANCE CALCULATIONS. |
| | PLEASE SEE 13-415.1.B, 13-415.1.C, 13-415.2 |
| | PLEASE SEE AS NO DESIGN WAS SUBMITTED FOR CHAPTER 13 |
| | COMPLIANCE, NO REVIEW CAN BE DONE. |
| | PLEASE SEE MISSING ENERGY CALCULATIONS. |
| | |
| | 13) NOTE: PLEASE SEE THE LOCATIONS OF EXIT AND |
| | EMERGENCY LIGHTING FIXTURES NEED TO BE GONE OVER WITH |
| | THE LS CODE, NFPA-101 7.8 AND 7.9. |
| | PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL |
| | AND/OR BUILDING REVIEWER. |
| | |
| | ** PLEASE KNOW AS THERE ARE NUMEROUS ITEMS WHICH NEED |
| | TO BE CORRECTED AND/OR ARE NOT SUBMITTED YET FOR |
| | REVIEW, THERE MAY VERY WELL BE NEW NOTES ON THE NEXT |
| | REVIEW. |
| | PLEASE BE SURE TO SEE COMMENT #3 AS NOTED ABOVE. |
| | LICENSED PROFESSIONALS WITH KNOWLEDGE OF WORK BEING |
| | PERFORMED MAY ONLY SIGN AND SEAL PLANS. |
| | PLEASE SEE FS 471.025 FOR ENGINEERS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |