Plan Review Notes
Plan Review Notes For Permit 07080957
Permit Number 07080957
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-23 11:17:362007-09-23 11:17:36
  
 PLANS REMOVED FROM INCOMING FOR REVIEW. ROUTED BACK TO
 INCOMING WHERE PLANS ARE WAITING FOR COMM BOARD.
2007-09-23 11:16:532007-09-23 11:16:53
  
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE ADDRESS FOR UNIT/SUITE SHALL BE
 STATED ON PERMIT APPLICATION AND TITLE BLOCKS FOR
 PLANS.
 A COPY OF PERMIT APPLICATION WAS ROUTED TO ADDRESSING
 REVIEWER. PLEASE BE AWARE OF ANY DESIGNATIONS WHICH MAY
 BE ASSIGNED.
  
 3) NOTE: PLEASE PROVIDE LICENSE INFORMATION FOR MI
 DESIGN. PLEASE SEE FS 481.229, 471.003 AS A
 DESIGNER/DRAFTSMAN MAY NOT PERFORM SCOPE OF WORK AS
 SHOWN ON PLANS.
  
 4) NOTE: PLEASE SEE THE NEW ELECTRICAL SERVICE BEING
 PROPOSED IS NOT PERMITTED OR GRANTED PER 230.2. PLEASE
 SEE THIS WILL BE REVIEWED BY ZONING AND BUILDING WHICH
 MAY PERMIT THIS AS A TENANT SPACE WHICH WOULD STILL
 REQUIRE ELECTRICAL TO BE FED FROM THE EXISTING SERVICE
 OR UPGRADE THE EXISTING SERVICE IF NOT SUFFICIENT.
 PLEASE ALSO SEE COMMENTS BELOW AS A REVIEW OF PLANS
 SUBMITTED WILL BE DONE EVEN AS SERVICE AS SHOWN IS NOT
 PERMITTED.
  
 5) NOTE: PLEASE SEE PLANS INDICATE PANEL AS 200AMPS,
 YET RISER SHOWS THIS PANEL AS 150AMPS.
 PLEASE CORRELATE, HOWEVER SEE NOTE ABOVE AS SERVICE
 RISER WILL REQUIRE A COMPLETE CHANGE.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE CALCULATIONS AS SUBMITTED ARE
 SHOWN FOR A RESIDENTIAL UNIT. THIS IS FOR COMMERCIAL
 AND CALCULATIONS ARE NOT THE SAME.
 PLEASE BE SURE TO SEE THAT ALL CONTINUOUS LOADS ARE TO
 BE FIGURED AT 125%.
 PLEASE SEE 220.12,220.14,220.42,220.43,220.44, ETC
 215.3, 230.42
 PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH NOW REQUIRES
 WATER HEATER LOADS TO BE FIGURED AT 125%.
  
 7) NOTE: PLEASE SEE MISSING DEDICATED SIGN CIRCUIT PER
 600.5 AND LOADS ON LOAD CALCULATIONS REQUIRED FOR SIGN
 CIRCUIT.
  
 8) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62 AND LOADS TO BE FIGURED PER 220.43
  
 9) NOTE: PLEASE SEE 700.12FFOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS. THE CIRCUITING AS SHOWN IS
 NOT CODE COMPLIANT.
  
 10) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR OUTSIDE
 CU. PER 210.63, 210.8B
  
 11) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR
 THE AHU/AIR HANDLER UNIT HEAT IS TOO LOW. PLEASE SEE
 424.3B FOR MINIMUM OCP.
  
 12) NOTE: PLEASE SEE FBC CHAPTER 13 FOR LIGHTING
 CALCULATIONS AND PERFORMANCE CALCULATIONS.
 PLEASE SEE 13-415.1.B, 13-415.1.C, 13-415.2
 PLEASE SEE AS NO DESIGN WAS SUBMITTED FOR CHAPTER 13
 COMPLIANCE, NO REVIEW CAN BE DONE.
 PLEASE SEE MISSING ENERGY CALCULATIONS.
  
 13) NOTE: PLEASE SEE THE LOCATIONS OF EXIT AND
 EMERGENCY LIGHTING FIXTURES NEED TO BE GONE OVER WITH
 THE LS CODE, NFPA-101 7.8 AND 7.9.
 PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE MARSHAL
 AND/OR BUILDING REVIEWER.
  
 ** PLEASE KNOW AS THERE ARE NUMEROUS ITEMS WHICH NEED
 TO BE CORRECTED AND/OR ARE NOT SUBMITTED YET FOR
 REVIEW, THERE MAY VERY WELL BE NEW NOTES ON THE NEXT
 REVIEW.
 PLEASE BE SURE TO SEE COMMENT #3 AS NOTED ABOVE.
 LICENSED PROFESSIONALS WITH KNOWLEDGE OF WORK BEING
 PERFORMED MAY ONLY SIGN AND SEAL PLANS.
 PLEASE SEE FS 471.025 FOR ENGINEERS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]