| 2008-08-08 11:17:46 | |
| | |
| | 106.1.3* THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. AS REQUESTED PREVIOUSLY, ALL |
| | CHANGES TO EACH SHEET SHALL BE IDENTIFIED BY CLOUDS, |
| | DATE AND A REVISION NUMBER FOR THE CHANGE. SHEET A.1 |
| | REVISION CHANGES SHOWS REVISIONS 1-6, BUT THE SHEET |
| | SHOWS REVISIONS #5 WHICH IS NOT CLOUDED AND REVISION #7 |
| | WHICH IS NOT ON THE REVISION LIST. ONLY THE REVISIONS |
| | WHICH AFFECT THIS PAGE SHALL BE INDICATED; THE ONES |
| | WHICH DO NOT AFFECT THIS PAGE SHALL BE REMOVED, AND BE |
| | INDICATED ON THE APPROPRIATE PAGE. THIS GOES FOR ALL |
| | SHEETS. THE CHANGES TO THE BATHROOM ARE NOT INDICATED |
| | ON THE NEW SHEETS. |
| | |
| | NOTED: HOWEVER, THE MECHANICAL PLANS SHOW FOUR NEW |
| | OPENINGS FOR INTAKE LOUVERS: THE ARCHITECTURAL PLANS |
| | SHALL REFLECT THE OPENINGS SHOWN ON THE MECHANICAL |
| | PLANS. DETAILED ELEVATION DRAWINGS SHALL BE SUBMITTED |
| | INDICATING HOW THE LOUVERS AND MOTORIZE DAMPER WILL BE |
| | ATTATCH TO THE OPENINGS. SHOW ALL DIMENSIONS ON THE |
| | ELEVATION DRAWINGS. TWO SETS OF PRODUCT APPROVALS ARE |
| | REQUIRED FOR THE LOUVERS. |
| | 1)THE REVISED SHEET NEEDS TO INDICATE ALL THE CHANGES |
| | WITH THE CLOUDED SYMBOL AND THE REVISION NUMBER NEXT TO |
| | IT AROUND THE CHANGED AREA. THE ADDITIONAL PLUMBING |
| | SYSTEMS SHALL BE INDICATED ALONG WITH THE RELOCATION OF |
| | THE DOORS AND WALLS ETC. AGAIN PLEASE SHOW ALL CHANGES |
| | WITH IDENTIFIABLE SYMBOLS AND THE REVISION NUMBER. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. 106.1.1 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |