| Plan Review Notes For Permit 07080952 |
| Permit Number |
07080952 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2008-08-11 10:30:21 | REVISION SHEET P.1 AND ADDED SHEET P.2: "OK" MOVED | | | FIXTURES AND ADDED SHOWER IN BACK BATHROOM. ADDED SINK | | | IN UTILITY ROOM. ADDED HOSE BIBBS. STUBBED FOR FUTURE | | | UTILTY SINK AND ADDED WATER FOR FUTURE ICE MACHINE. | | | | | | ****************PROVISO**************** | | | A} WATER HAMMER ARRESTORS SHALL BE INSTALLED WHERE | | | QUICK CLOSING VALVES ARE UTILIZED. (DISHWASHER, FUTURE | | | ICE MACHINE). PER FBC- PLUMBING SECTION 604.9 WATER | | | HAMMER. | | | B} A TWO-WAY CLEANOUT SHALL BE INSTALLED AT THE | | | JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER. PER | | | FBC- PLUMBING SECTION 708.3.5. BUILDING DRAIN AND | | | BUILDING SEWER JUNCTION. | | | C} SHEET P.1 PLUMBING FIXTURES: SEE RED LINE | | | CORRECTION TO WASHING MACHINE WASTE (3"). | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|