Plan Review Notes
Plan Review Notes For Permit 07080952
Permit Number 07080952
Review Stop M
Sequence Number 6
Notes
Date Text
2008-06-26 12:27:46PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
 1) MECHANICAL PLANS ON FILE WERE SIGNED AND SEALED BY
 AN ENGINEER (MICHAEL M. BASSFORD) SO ONLY HE CAN MAKE
 REVISIONS TO THEM, PER FAC 61G15-23.002.
  
 2) PLEASE HAVE THE ENGINEER ALSO REVISE THE ENERGY
 CALCULATIONS AND COOLING LOAD CALCULATIONS AS THEY HAVE
 BEEN SIGNED AND SEALED BY HIM ALSO AND WILL NEED TO BE
 REVISED AS A RESULT OF THE CHANGES IN THE MECHANICAL
 PLANS, PER 2004 FBC 13-600.3.ABC.2.
  
 3) PLEASE SHOW THE OUTSIDE AIR CALCULATIONS ON THE
 MECHANICAL PLAN AND PROVIDE OUTSIDE AIR WERE REQUIRED
 BY 2004 FBC/R R303 AND FBC/M TABLE 403.3.
  
 4) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE 26X26 MOTORIZED
 DAMPERS, AND 30" WEATHER HOOD FOR THE EXHAUST FAN,
 SHOWING COMPLIANCE WITH 2004 FBC 1609 WIND LOADS.
 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR LOUVERS IF
 BEING USED, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 5) THE BUILDING PLANS WILL NEED TO BE REVISED SHOWING
 THE NEW OUTDOOR AIR OPENINGS AND EXHAUST OPENING, PER
 2004 FBC 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]