| 2008-06-26 12:27:46 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | REVISION TO MECHANICAL PLANS |
| | *** DENIED *** |
| | 1) MECHANICAL PLANS ON FILE WERE SIGNED AND SEALED BY |
| | AN ENGINEER (MICHAEL M. BASSFORD) SO ONLY HE CAN MAKE |
| | REVISIONS TO THEM, PER FAC 61G15-23.002. |
| | |
| | 2) PLEASE HAVE THE ENGINEER ALSO REVISE THE ENERGY |
| | CALCULATIONS AND COOLING LOAD CALCULATIONS AS THEY HAVE |
| | BEEN SIGNED AND SEALED BY HIM ALSO AND WILL NEED TO BE |
| | REVISED AS A RESULT OF THE CHANGES IN THE MECHANICAL |
| | PLANS, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 3) PLEASE SHOW THE OUTSIDE AIR CALCULATIONS ON THE |
| | MECHANICAL PLAN AND PROVIDE OUTSIDE AIR WERE REQUIRED |
| | BY 2004 FBC/R R303 AND FBC/M TABLE 403.3. |
| | |
| | 4) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S AND |
| | INSTALLATION INSTRUCTIONS FOR THE 26X26 MOTORIZED |
| | DAMPERS, AND 30" WEATHER HOOD FOR THE EXHAUST FAN, |
| | SHOWING COMPLIANCE WITH 2004 FBC 1609 WIND LOADS. |
| | PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR LOUVERS IF |
| | BEING USED, SEE FS 553.842(1) AND FAC RULE 9B-72, |
| | 9B-72.005, AND FAC 9B-72.010(31)(C). |
| | |
| | 5) THE BUILDING PLANS WILL NEED TO BE REVISED SHOWING |
| | THE NEW OUTDOOR AIR OPENINGS AND EXHAUST OPENING, PER |
| | 2004 FBC 1609. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |