Plan Review Notes
Plan Review Notes For Permit 07080952
Permit Number 07080952
Review Stop P
Sequence Number 5
Notes
Date Text
2008-07-23 14:52:40REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA STATUTES
  
 1. SHT P.1 OF 1 REVISIONS TO PLANS SIGNED AND SEALED BY
 A PROFESSIONAL ENGINEER SHALL BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD. FS 471.--PREVIOUS REVIEWED
 SHEET SHOWED REVISIONS 1 & 2. NEW REVISIONS 3, 4 & 5
 ARE NOT INDICATED WITH CLOUDS OR REVISION NUMBERS. MUCH
 OF THE INFORMATION ON THE REVIEWED/STAMPED PLANS HAS
 BEEN DELETED SUCH AS THE WATER RISER DIAGRAM ETC. SHT
 NOW IS INDICATED AS P.1 OF 7. PLEASE CLARIFY. SECTION
 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]