2008-02-21 15:14:13****************PROVISO****************
 PER FBC PLUMBING SECTION *406.3 WASTE CONNECTIONS.THE
 TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES WASHER
 SHALL BE A MINIMUM OF 2 INCHES (51MM) IN DIAMETER. THE
 AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO
 A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES
 (76MM) IN DIAMETER. (REVISION REQUIRED)
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER