| Plan Review Notes For Permit 07080952 |
| Permit Number |
07080952 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-02-21 15:14:13 | ****************PROVISO**************** | | | PER FBC PLUMBING SECTION *406.3 WASTE CONNECTIONS.THE | | | TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES WASHER | | | SHALL BE A MINIMUM OF 2 INCHES (51MM) IN DIAMETER. THE | | | AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO | | | A BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES | | | (76MM) IN DIAMETER. (REVISION REQUIRED) | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|