2008-01-25 08:28:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR 14 SEER A/C
 SYSTEMS, THE PLANS PAGE M.2 A/C SCHEDULE IS CALLING FOR
 13 SEER A/C SYSTEMS. THE PLANS CAN NOT CALL FOR LESS
 THAN THE ENERGY CALCULATIONS. PLEASE CORRECT.
  