Plan Review Notes
Plan Review Notes For Permit 07080952
Permit Number 07080952
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-15 07:39:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. DECLARE THE OCCUPANCY. IT APPEARS THAT THESE ARE
 WAREHOUSES AND THE RESIDENTIAL AREA DOES NOT MEET THE
 DEFINITION OF DWELLING IN AS IT DOES NOT HAVE SLEEPING
 PROVISIONS. SECTION 310.2. COMMERCIAL LIVE/WORK DOES
 NOT INDICATE THE OCCUPANCY OF THE COMMERCIAL SECTION.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED.
 JOHN ROACH IS NOT A BUILDING OR PLUMBING PLAN REVIEWER
 AND HAS NO KNOWLEDGE OF OUR REQUIREMENTS. THERE HAS
 BEEN PLAN DEVELOPMENT BETWEEN THE FIRST REVIEW AND THE
 PRESENT REVIEW. AS SUCH NEW COMMENTS WILL BE INDICATED.
 THE OCCUPANCY STILL IS NOT INDICATED.
  
 3. SHT A-1 THE STORAGE OCCUPANCIES REQUIRES DRINKING
 FOUNTAINS AND SERVICES SINKS IF, AS INDICATED ON THE
 ENERGY CALCULATIONS, THERE WILL BE FOUR WAREHOUSE BAYS.
 PLEASE ALSO INDICATE THE TYPE OF MATERIAL & THE AMOUNT
 THAT WILL BE STORED IN THE STORAGE BAYS. MSDS SHEETS
 MAY BE REQUIRED AS WELL AS AN EYE WASH/EMERGENCY SHOWER
 DEPENDING ON THE RESPONSE OF THIS COMMENT AND THE MSDS
 SHEETS. SECTION 106.1.2 & TABLE 403.1.
 ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED.
 JOHN ROACH IS NOT A BUILDING OR PLUMBING PLAN REVIEWER
 AND HAS NO KNOWLEDGE OF OUR REQUIREMENTS. THERE IS A 2
 HRFIRE SEPARATION WALL INDICATED, BUT THE SPACE IS
 INDICATED AS AN ACCESSORY TO RESIDENCE. MORE
 INFORMATION IS STILL REQUIRED.
  
 4. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE
 WORK CAN BE ESTABLISHED. SECTION 106.1.2, MORE
 INFORMATION REQUIRED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE DEMO
 SHOWS NOT EXISTING TOILET ROOMS, KITCHEN, WASH MACHINE
 CONNECTIONS, SLEEPING PROVISIONS ETC THAT ARE REQUIRED
 IN A RESIDENCE. IF THIS IS AN EXISTING RESIDENCE, WHERE
 ARE ALL OF THE EXISTING REQUIRED ELEMENTS? A
 PRE-INSPECTION MAY BE REQUIRED TO VERIFY INFORMATION
 INDICATED IN THE PLANS.
  
 5. SHT A.1 THE FUTURE TOILET ROOMS SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTIONS 11-4.15, 11-4.16, 11-4.19
 & 11-4.22 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.--SUBMIT DETAILS IN
 BOTH A FLOOR PLAN AND ELEVATIONS.
 ****RESPONSE NOTED, BUT THE "COMMERCIAL" INDICATION ON
 SHT A.0 REQUIRES THAT ALL TOILET ROOMS PROVIDED SHALL
 BE ACCESSIBLE AND SHALL BE ON AN ACCESSIBLE ROUTE.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ALSO
 SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A).
  
 6. OK
  
 7. N/A PLAN DEVELOPMENT.
  
 8. OK
  
 9. SHT P.1 NO SANITARY OR WATER PIPING ARE SHOWN TO THE
 WASH MACHINE. TABLE 403.1.
 ****RESPONSE NOTED, BUT WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINE PER SECTION 604.9.
  
 **********NEW COMMENT**********
  
 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]